12.1.1 Cargo pump-rooms and
other enclosed spaces which contain cargo-handling equipment and similar
spaces in which work is performed on the cargo shall be fitted with
mechanical ventilation systems, capable of being controlled from outside
such spaces.
12.1.2 Provision shall be
made to ventilate such spaces prior to entering the compartment and
operating the equipment and a warning notice requiring the use of
such ventilation shall be placed outside the compartment.
12.1.3 Mechanical ventilation
inlets and outlets shall be arranged to ensure sufficient air movement
through the space to avoid the accumulation of toxic or flammable
vapours or both (taking into account their vapour densities) and to
ensure sufficient oxygen to provide a safe working environment, but
in no case shall the ventilation system have a capacity of less than
30 changes of air per hour, based upon the total volume of the space.
For certain products, increased ventilation rates for cargo pump-rooms
are prescribed in 15.17.
12.1.4 Ventilation systems
shall be permanent and shall normally be of the extraction type. Extraction
from above and below the floor plates shall be possible. In rooms
housing motors driving cargo pumps, the ventilation shall be of the
positive-pressure type.
12.1.5 Ventilation exhaust
ducts from spaces within the cargo area shall discharge upwards in
locations at least 10 m in the horizontal direction from ventilation
intakes and openings to accommodation, service and machinery spaces
and control stations and other spaces outside the cargo area.
12.1.6 Ventilation intakes
shall be so arranged as to minimize the possibility of recycling hazardous
vapours from any ventilation discharge opening.
12.1.7 Ventilation ducts
shall not be led through accommodation, service and machinery spaces
or other similar spaces.
12.1.8 Electric motors driving
fans shall be placed outside the ventilation ducts if the carriage
of flammable products is intended. Ventilation fans and fan ducts,
in way of fans only, for hazardous locations referred to in chapter 10 shall be of non-sparking construction,
defined as:
-
.1 impellers or housing of non-metallic construction,
due regard being paid to the elimination of static electricity;
-
.2 impellers and housing of non-ferrous
materials;
-
.3 impellers and housing of austenitic stainless
steel; and
-
.4 ferrous impellers and housing with not less than
13 mm design tip clearance.
Any combination of an aluminium or a magnesium alloy fixed or
rotating component and a ferrous fixed or rotating component, regardless
of tip clearance, is considered a sparking hazard and shall not be
used in these places.
12.1.9 Sufficient spare parts
shall be carried for each type of fan on board required by this chapter.
12.1.10 Protection screens
of not more than 13 mm square mesh shall be fitted in outside openings
of ventilation ducts.