CHAPTER II-2 - Construction – Fire protection, fire detection and fire extinction

Regulation 9.2 – Containment of fire, thermal and structural boundaries

In cases where urea or sodium hydroxide solution tanks for selective catalytic reduction (SCR) systems, exhaust gas recirculation (EGR) systems or exhaust gas cleaning systems (EGCS) are installed in a space separated from the engine-room, in determining fire integrity of divisions, the solution tank space should be considered as "similar spaces" in the definition of "machinery spaces" in regulation 3.30 and should be categorized as:

  • "(10) Tanks, voids and auxiliary machinery spaces having little or no fire risk" in regulation 9.2.2.3.2.2, for ships carrying more than 36 passengers; or

  • "(7) Other machinery spaces" in regulations 9.2.2.4.2.2, 9.2.3.3.2.2 or 9.2.4.2.2.2, for ships carrying not more than 36 passengers and cargo ships.

The division between the engine-room and the solution tank space should have a fire integrity of at least "A-0" class.

Regulation 9.7.5 – Containment of fire, Ventilation systems, Exhaust ducts from galley ranges

The reference to ISO 15371:2009 in the footnote to both regulations 9.7.5.1.1.3 and 9.7.5.2.4 is given as an example of a suitable performance standard for pre-engineered galley duct fixed fire-extinguishing systems.

CO2 fire-extinguishing systems, which are not pre-engineered fixed fire-extinguishing systems, should be designed according to the requirements set out in regulation 10.6.3.1.1 (spaces containing flammable liquids) or another suitable standard acceptable to the Administration.

Regulation 10.10.4 – Fire-fighting, Fire-fighter's outfits, Fire-fighter's communication

Two-way portable radiotelephone apparatus for fire-fighter's communication required by regulation 10.10.4 should be of certified safe type suitable for use in zone 1 hazardous areas, as defined in IEC Publication 60079.

The minimum requirements in respect to the apparatus group and temperature class are to be consistent with the most restrictive requirements for the hazardous area zone on board which is accessible to fire party.


Copyright 2022 Clasifications Register Group Limited, International Maritime Organization, International Labour Organization or Maritime and Coastguard Agency. All rights reserved. Clasifications Register Group Limited, its affiliates and subsidiaries and their respective officers, employees or agents are, individually and collectively, referred to in this clause as 'Clasifications Register'. Clasifications Register assumes no responsibility and shall not be liable to any person for any loss, damage or expense caused by reliance on the information or advice in this document or howsoever provided, unless that person has signed a contract with the relevant Clasifications Register entity for the provision of this information or advice and in that case any responsibility or liability is exclusively on the terms and conditions set out in that contract.