The attention of the Administration is drawn to the fact
that particular installation conditions (excessive ambient temperature,
incomplete filling of the tank etc.) may lead to an abnormal ageing
of the concentrates.
For the periodical control of foam concentrate, the tests
under 4.1 to 4.5 should be performed. They should be carried out at
laboratories acceptable to the Administration.
The deviations in the values obtained by these tests, in
respect of those obtained during she type approval tests, should be
within ranges acceptable to the Administration.
Tests under 4.1, 4.3 and 4.4 should be carried out on samples
maintained at 60°C for 24 h and subsequently cooled to the test
temperature.
4.1 Sedimentation
According to 3.3 above.
4.2 pH value
According to 3.5 above.
4.3 Expansion ratio
According to 3.6 above.
4.4 Drainage time
According to 3.7 above.
4.5 Volumic mass
According to 3.10 above.