Materials for bulkhead, wall and ceiling linings and primary
deck coverings shall not produce burning droplets during the test.
The burning droplets shall be considered as a reject material regardless
of the surface flammability criteria. For floor coverings, no more
than 10 burning drops are acceptable.
Table 1 – Surface flammability criteria
|
Bulkhead, wall and ceiling linings
|
Floor coverings
|
Primary deck coverings
|
CFE (kW/m2)
|
≥20.0
|
≥7.0
|
≥7.0
|
Qsb (MJ/m2)
|
≥1.5
|
≥0.25
|
≥0.25
|
Qt (MJ)
|
≤0.7
|
≤2.0
|
≤2.0
|
Qp (kW)
|
≤4.0
|
≤10.0
|
≤10.0
|
Burning droplets
|
Not
produced
|
No more
than 10 burning drops
|
Not
produced
|
Where:
|
|
|
|
|
CFE=
|
Critical flux at
extinguishment
|
|
|
Qsb=
|
Heat for sustained burning
|
|
|
Qt=
|
Total heat release
|
|
|
Qp=
|
Peak heat release rate
|
|
Note:
|
Qsb means
an average of heat for sustained burning, as defined in paragraph 9.3 of
appendix 1.
|