Chapter 9 - Fixed Fire
Detection and Fire Alarm Systems
2 Engineering specifications
2.1 General requirements
1 The following new paragraph 2.1.8 is inserted after existing paragraph
2.1.7:
-
"2.1.8 In cargo ships and on passenger ship cabin balconies,
where an individually identifiable system is fitted, notwithstanding the
provisions in paragraph 2.1.6.1, isolator modules need not be provided at
each fire detector if the system is arranged in such a way that the number
and location of individually identifiable fire detectors rendered
ineffective due to a fault would not be larger than an equivalent section in
a section identifiable system, arranged in accordance with paragraph
2.4.1."