The fire test procedures are intended for pressurized wet-pipe
systems with individually activated (automatic) nozzles.
Water without any fire-extinguishing additives should be used,
unless the additives have been approved for fire protection service
by an independent authority. The approval of the additives should
consider possible adverse health effects to exposed personnel, including
inhalation toxicity.
These test procedures are applicable
to either overhead nozzles installed on the ceiling, or sidewall nozzles
installed on bulkheads below the ceiling. Separate approval tests
should be conducted for each nozzle type.
The testing
organization should be responsible for assuring that the nozzles for
each fire test are installed in accordance with the manufacturer’s
design and installation instructions. The tests should be performed
at the maximum specified spacings, installation height and distances
below the ceiling. In addition, if the testing organization finds
it necessary, selected fire tests should also be conducted at minimum
specified spacings, installation height and distances below the ceiling.
Where two types of nozzles are installed in the same area, an overlap
of the different nozzle spray patterns should be provided equal to
at least one half of the maximum approved nozzle spacing.