4 Larger doors exceeding 50% in surface area
Clasification Society 2024 - Version 9.40
Statutory Documents - IMO Publications and Documents - Circulars - Maritime Safety Committee - MSC.1/Circular.1319 – Recommendation for the Evaluation of Fire Performance and Approval of Large Fire Doors – (11 June 2009) - Annex – Recommendation for the Evaluation of Fire Performance and Approval of Large Fire Doors - 4 Larger doors exceeding 50% in surface area

4 Larger doors exceeding 50% in surface area

  4.1 For larger doors exceeding 50% in surface area, a full analysis based on SOLAS regulation II-2/17 should be performed to assess the safety of the vessel.

  4.2 The approach should be based on the results of the fire test of the door having the maximum dimensions permitted by the furnace (considering a furnace with an aperture of 2,440 mm width x 2,500 mm height) according to the procedure described under section 3.


Copyright 2022 Clasifications Register Group Limited, International Maritime Organization, International Labour Organization or Maritime and Coastguard Agency. All rights reserved. Clasifications Register Group Limited, its affiliates and subsidiaries and their respective officers, employees or agents are, individually and collectively, referred to in this clause as 'Clasifications Register'. Clasifications Register assumes no responsibility and shall not be liable to any person for any loss, damage or expense caused by reliance on the information or advice in this document or howsoever provided, unless that person has signed a contract with the relevant Clasifications Register entity for the provision of this information or advice and in that case any responsibility or liability is exclusively on the terms and conditions set out in that contract.