2 Engineering specifications
2.1 Definitions
For the purposes of this chapter:
2.1.1
Cargo tanks means those cargo tanks, including slop tanks, which carry
cargoes, or cargo residues, having a flashpoint not exceeding 60ºC.
2.1.2
Inert gas system includes inert gas systems using flue gas, inert gas
generators, and nitrogen generators and means the inert gas plant and inert gas
distribution together with means for preventing backflow of cargo gases to machinery
spaces, fixed and portable measuring instruments and control devices.
2.1.3
Gas-safe space is a space in which the entry of gases would produce hazards
with regard to flammability or toxicity.
2.1.4
Gas-free is a condition in a tank where the content of hydrocarbon or other
flammable vapour is less than 1% of the lower flammable limit (LFL), the oxygen
content is at least 21%, and no toxic gases are presentfootnote.
2.2 Requirements for all systems
2.2.1 General
2.2.1.1 The inert gas system referred to in chapter
II-2 of the Convention shall be designed, constructed and tested to the
satisfaction of the Administration. It shall be designed to be capable of
rendering and maintaining the atmosphere of the relevant cargo tanks
non-flammablefootnote.
2.2.1.2 The system shall be capable of:
-
.1 inerting empty cargo tanks and maintaining
the atmosphere in any part of the tank with an oxygen content not exceeding
8% by volume and at a positive pressure in port and at sea except when it is
necessary for such a tank to be gas-free;
-
.2 eliminating the need for air to enter a tank
during normal operations except when it is necessary for such a tank to be
gas-free;
-
.3 purging empty cargo tanks of hydrocarbon or
other flammable vapours, so that subsequent gas-freeing operations will at
no time create a flammable atmosphere within the tank;
-
.4 delivering inert gas to the cargo tanks at a
rate of at least 125% of the maximum rate of discharge capacity of the ship
expressed as a volume. For chemical tankers and chemical/product tankers,
the Administration may accept inert gas systems having a lower delivery
capacity provided that the maximum rate of discharge of cargoes from cargo
tanks being protected by the system is restricted to not more than 80% of
the inert gas capacity; and
-
.5 delivering inert gas with an oxygen content
of not more than 5% by volume to the cargo tanks at any required rate of
flow.
2.2.1.3 Materials used in inert gas systems shall be
suitable for their intended purpose. In particular, those components which may be
subjected to corrosive action of the gases and/or liquids are to be either
constructed of corrosion-resistant material or lined with rubber, glass fibre
epoxy resin or other equivalent coating material.
2.2.1.4 The inert gas supply may be:
-
.1 treated flue gas from main or auxiliary
boilers, or
-
.2 gas from an oil or gas-fired gas generator,
or
-
.3 gas from nitrogen generators.
The Administration may accept systems using inert gases from one or
more separate gas generators or other sources or any combination thereof, provided
that an equivalent level of safety is achieved. Such systems shall, as far as
practicable, comply with the requirements of this chapter. Systems using stored
carbon dioxide shall not be permitted unless the Administration is satisfied that
the risk of ignition from generation of static electricity by the system itself is
minimized.
2.2.2 Safety measures
2.2.2.1 The inert gas system shall be so designed
that the maximum pressure which it can exert on any cargo tank will not exceed the
test pressure of any cargo tank.
2.2.2.2 Automatic shutdown of the inert gas system
and its components parts shall be arranged on predetermined limits being reached,
taking into account the provisions of paragraphs 2.2.4, 2.3.2 and 2.4.2.
2.2.2.3 Suitable shutoff arrangements shall be
provided on the discharge outlet of each generator plant.
2.2.2.4 The system shall be designed to ensure that
if the oxygen content exceeds 5% by volume, the inert gas shall be automatically
vented to atmosphere.
2.2.2.5 Arrangements shall be provided to enable the
functioning of the inert gas plant to be stabilized before commencing cargo
discharge. If blowers are to be used for gas-freeing, their air inlets shall be
provided with blanking arrangements.
2.2.2.6 Where a double block and bleed valve is
installed, the system shall ensure upon of loss of power, the block valves are
automatically closed and the bleed valve is automatically open.
2.2.3 System components
2.2.3.1
Non-return devices
2.2.3.1.1 At least two non-return devices shall be
fitted in order to prevent the return of vapour and liquid to the inert gas plant,
or to any gas-safe spaces.
2.2.3.1.2 The first non-return device shall be a deck
seal of the wet, semi-wet, or dry type or a double-block and bleed arrangement.
Two shut-off valves in series with a venting valve in between, may be accepted
provided:
-
.1 the operation of the valve is automatically
executed. Signal(s) for opening/closing is (are) to be taken from the
process directly, e.g. inert gas flow or differential pressure; and
-
.2 alarm for faulty operation of the valves is
provided, e.g. the operation status of "blower stop" and "supply valve(s)
open" is an alarm condition.
2.2.3.1.3 The second non-return device shall be a
non-return valve or equivalent capable of preventing the return of vapours and
liquids and fitted between the deck water seal (or equivalent device) and the
first connection from the inert gas main to a cargo tank. It shall be provided
with positive means of closure. As an alternative to positive means of closure, an
additional valve having such means of closure may be provided between the
non-return valve and the first connection to the cargo tanks to isolate the deck
water seal, or equivalent device, from the inert gas main to the cargo tanks.
2.2.3.1.4 A water seal, if fitted, shall be capable
of being supplied by two separate pumps, each of which shall be capable of
maintaining an adequate supply at all times. The audible and visual alarm on the
low level of water in the water seal shall operate at all times.
2.2.3.1.5 The arrangement of the water seal, or
equivalent devices, and its associated fittings shall be such that it will prevent
backflow of vapours and liquids and will ensure the proper functioning of the seal
under operating conditions.
2.2.3.1.6 Provision shall be made to ensure that the
water seal is protected against freezing, in such a way that the integrity of seal
is not impaired by overheating.
2.2.3.1.7 A water loop or other approved arrangement
shall also be fitted to each associated water supply and drain pipe and each
venting or pressure-sensing pipe leading to gas-safe spaces. Means shall be
provided to prevent such loops from being emptied by vacuum.
2.2.3.1.8 Any water seal, or equivalent device, and
loop arrangements shall be capable of preventing return of vapours and liquids to
an inert gas plant at a pressure equal to the test pressure of the cargo
tanks.
2.2.3.1.9 The non-return devices shall be located in
the cargo area on deck.
2.2.3.2.1 The inert gas main may be divided into two
or more branches forward of the non-return devices required by paragraph
2.2.3.1.
2.2.3.2.2 The inert gas main shall be fitted with
branch piping leading to the cargo tank. Branch piping for inert gas shall be
fitted with either stop valves or equivalent means of control for isolating each
tank. Where stop valves are fitted, they shall be provided with locking
arrangements. The control system shall provide unambiguous information of the
operational status of such valves to at least the control panel required in
paragraph 2.2.4.
2.2.3.2.3 Each cargo tank not being inerted shall be
capable of being separated from the inert gas main by:
-
.1 removing spool-pieces, valves or other pipe
sections, and blanking the pipe ends; or
-
.2 arrangement of two spectacle flanges in
series with provisions for detecting leakage into the pipe between the two
spectacle flanges; or
-
.3 equivalent arrangements to the satisfaction
of the Administration, providing at least the same level of protection.
2.2.3.2.4 Means shall be provided to protect cargo
tanks against the effect of overpressure or vacuum caused by thermal variations
and/or cargo operations when the cargo tanks are isolated from the inert gas
mains.
2.2.3.2.5 Piping systems shall be so designed as to
prevent the accumulation of cargo or water in the pipelines under all normal
conditions.
2.2.3.2.6 Arrangements shall be provided to enable
the inert gas main to be connected to an external supply of inert gas. The
arrangements shall consist of a 250 mm nominal pipe size bolted flange, isolated
from the inert gas main by a valve and located forward of the non-return valve.
The design of the flange should conform to the appropriate class in the standards
adopted for the design of other external connections in the ship's cargo piping
system.
2.2.3.2.7 If a connection is fitted between the inert
gas main and the cargo piping system, arrangements shall be made to ensure an
effective isolation having regard to the large pressure difference which may exist
between the systems. This shall consist of two shutoff valves with an arrangement
to vent the space between the valves in a safe manner or an arrangement consisting
of a spool-piece with associated blanks.
2.2.3.2.8 The valve separating the inert gas main
from the cargo main and which is on the cargo main side shall be a non-return
valve with a positive means of closure.
2.2.3.2.9 Inert gas piping systems shall not pass
through accommodation, service and control station spaces.
2.2.3.2.10 In combination carriers, the arrangement
to isolate the slop tanks containing oil or oil residues from other tanks shall
consist of blank flanges which will remain in position at all times when cargoes
other than oil are being carried except as provided for in the relevant section of
the guidelines developed by the Organizationfootnote.
2.2.4 Indicators and alarms
2.2.4.1 The operation status of the inert gas system
shall be indicated in a control panel.
2.2.4.2 Instrumentation shall be fitted for
continuously indicating and permanently recording, when inert gas is being
supplied:
2.2.4.3 The indicating and recording devices shall be
placed in the cargo control room where provided. But where no cargo control room
is provided, they shall be placed in a position easily accessible to the officer
in charge of cargo operations.
2.2.4.4 In addition, meters shall be fitted:
-
.1 in the navigating bridge to indicate at all
times the pressure referred to in paragraph 2.2.4.2.1 and the pressure in
the slop tanks of combination carriers, whenever those tanks are isolated
from the inert gas main; and
-
.2 in the machinery control room or in the
machinery space to indicate the oxygen content referred to in paragraph
2.2.4.2.2.
2.2.4.5
Audible and visual alarms
2.2.4.5.1 Audible and visual alarms shall be
provided, based on the system designed, to indicate:
-
.1 oxygen content in excess of 5% by
volume;
-
.2 failure of the power supply to the
indicating devices as referred to in paragraph 2.2.4.2;
-
.3 gas pressure less than 100 mm water gauge.
The alarm arrangement shall be such as to ensure that the pressure in slop
tanks in combination carriers can be monitored at all times;
-
.4 high-gas pressure; and
-
.5 failure of the power supply to the automatic
control system.
2.2.4.5.2 The alarms required in paragraphs
2.2.4.5.1.1, 2.2.4.5.1.3 and 2.2.4.5.1.5 shall be fitted in the machinery space
and cargo control room, where provided, but in each case in such a position that
they are immediately received by responsible members of the crew.
2.2.4.5.3 An audible alarm system independent of that
required in paragraph 2.2.4.5.1.3 or automatic shutdown of cargo pumps shall be
provided to operate on predetermined limits of low pressure in the inert gas main
being reached.
2.2.4.5.4 Two oxygen sensors shall be positioned at
appropriate locations in the space or spaces containing the inert gas system. If
the oxygen level falls below 19%, these sensors shall trigger alarms, which shall
be both visible and audible inside and outside the space or spaces and shall be
placed in such a position that they are immediately received by responsible
members of the crew.
2.2.5 Instruction manuals
Detailed instruction manuals shall be provided on board, covering the
operations, safety and maintenance requirements and occupational health hazards
relevant to the inert gas system and its application to the cargo tank systemfootnoteThe manuals shall include guidance on procedures to be followed in
the event of a fault or failure of the inert gas system.
2.3 Requirements for flue gas and inert gas generator
systems
In addition to the provisions in paragraph 2.2, for inert gas systems
using flue gas or inert gas generators, the provisions of this section shall
apply.
2.3.1 System requirements
2.3.1.1
Inert gas generators
2.3.1.1.1 Two fuel oil pumps shall be fitted to the
inert gas generator. Suitable fuel in sufficient quantity shall be provided for
the inert gas generators.
2.3.1.1.2 The inert gas generators shall be located
outside the cargo tank area. Spaces containing inert gas generators shall have no
direct access to accommodation service or control station spaces, but may be
located in machinery spaces. If they are not located in machinery spaces, such a
compartment shall be separated by a gastight steel bulkhead and/or deck from
accommodation, service and control station spaces. Adequate positive-pressure-type
mechanical ventilation shall be provided for such a compartment.
2.3.1.2
Gas regulating valves
2.3.1.2.1 A gas regulating valve shall be fitted in
the inert gas main. This valve shall be automatically controlled to close, as
required in paragraph 2.2.2.2. It shall also be capable of automatically
regulating the flow of inert gas to the cargo tanks unless means are provided to
automatically control the inert gas flow rate.
2.2.1.2.2 The gas regulating valve shall be located
at the forward bulkhead of the forward most gas-safe space through which the inert
gas main passes.
2.3.1.3
Cooling and scrubbing arrangement
2.3.1.3.1 Means shall be fitted which will
effectively cool the volume of gas specified in paragraph 2.2.1.2 and remove
solids and sulphur combustion products. The cooling water arrangements shall be
such that an adequate supply of water will always be available without interfering
with any essential services on the ship. Provision shall also be made for an
alternative supply of cooling water.
2.3.1.3.2 Filters or equivalent devices shall be
fitted to minimize the amount of water carried over to the inert gas blowers.
2.3.1.4.1 At least two inert gas blowers shall be
fitted and be capable of delivering to the cargo tanks at least the volume of gas
required by paragraph 2.2.1.2. For systems fitted with inert gas generators the
Administration may permit only one blower if that system is capable of delivering
the total volume of gas required by paragraph 2.2.1.2 to the cargo tanks, provided
that sufficient spares for the blower and its prime mover are carried on board to
enable any failure of the blower and its prime mover to be rectified by the ship's
crew.
2.3.1.4.2 Where inert gas generators are served by
positive displacement blowers, a pressure relief device shall be provided to
prevent excess pressure being developed on the discharge side of the blower.
2.3.1.4.3 When two blowers are provided, the total
required capacity of the inert gas system shall be divided evenly between the two
and in no case is one blower to have a capacity less than 1/3 of the total
required
2.3.1.5
Inert gas isolating valves
For systems using flue gas, flue gas isolating valves shall be fitted
in the inert gas mains between the boiler uptakes and the flue gas scrubber. These
valves shall be provided with indicators to show whether they are open or shut,
and precautions shall be taken to maintain them gastight and keep the seatings
clear of soot. Arrangements shall be made to ensure that boiler soot blowers
cannot be operated when the corresponding flue gas valve is open.
2.3.1.6
Prevention of flue gas leakage
2.3.1.6.1 Special consideration shall be given to the
design and location of scrubber and blowers with relevant piping and fittings in
order to prevent flue gas leakages into enclosed spaces.
2.3.1.6.2 To permit safe maintenance, an additional
water seal or other effective means of preventing flue gas leakage shall be fitted
between the flue gas isolating valves and scrubber or incorporated in the gas
entry to the scrubber.
2.3.2 Indicators and alarms
2.3.2.1 In addition to the requirements in paragraph
2.2.4.2, means shall be provided for continuously indicating the temperature of
the inert gas at the discharge side of the system, whenever it is operating.
2.3.2.2 In addition to the requirements of paragraph
2.2.4.5, audible and visual alarms shall be provided to indicate:
-
.1 insufficient fuel oil supply to the
oil-fired inert gas generator;
-
.2 failure of the power supply to the
generator;
-
.3 low water pressure or low water flow rate to
the cooling and scrubbing arrangement;
-
.4 high water level in the cooling and
scrubbing arrangement;
-
.5 high gas temperature;
-
.6 failure of the inert gas blowers; and
-
.7 low water level in the water seal.
2.4 Requirements for nitrogen generator systems
In addition to the provisions in paragraph 2.2, for inert gas systems
using nitrogen generators, the provisions of this section shall apply.
2.4.1 System requirements
2.4.1.1 The system shall be provided with one or more
compressors to generate enough positive pressure to be capable of delivering the
total volume of gas required by paragraph 2.2.1.2.
2.4.1.2 A feed air treatment system shall be fitted
to remove free water, particles and traces of oil from the compressed air.
2.4.1.3 The air compressor and nitrogen generator may
be installed in the engine-room or in a separate compartment. A separate
compartment and any installed equipment shall be treated as an "Other machinery
space" with respect to fire protection. Where a separate compartment is provided
for the nitrogen generator, the compartment shall be fitted with an independent
mechanical extraction ventilation system providing six air changes per hour. The
compartment is to have no direct access to accommodation spaces, service spaces
and control stations.
2.4.1.4 Where a nitrogen receiver or a buffer tank is
installed, it may be installed in a dedicated compartment, in a separate
compartment containing the air compressor and the generator, in the engine room,
or in the cargo area. Where the nitrogen receiver or a buffer tank is installed in
an enclosed space, the access shall be arranged only from the open deck and the
access door shall open outwards. Adequate, independent mechanical ventilation, of
the extraction type, shall be provided for such a compartment.
2.4.2 Indicators and alarms
2.4.2.1 In addition to the requirements in paragraph
2.2.4.2, instrumentation is to be provided for continuously indicating the
temperature and pressure of air at the suction side of the nitrogen generator.
2.4.2.2 In addition to the requirements in paragraph
2.2.4.5, audible and visual alarms shall be provided to include:
-
.1 failure of the electric heater, if
fitted;
-
.2 low feed-air pressure or flow from the
compressor;
-
.3 high-air temperature; and
-
.4 high condensate level at automatic drain of
water separator.
|