2 Engineering specifications
2.1
General requirements
2.1.1 Any required fixed fire detection
and fire alarm system with manually operated call points shall be
capable of immediate operation at all times (this does not require
a backup control panel). Notwithstanding this, particular spaces may
be disconnected, for example, workshops during hot work and ro-ro
spaces during on and off-loading. The means for disconnecting the
detectors shall be designed to automatically restore the system to
normal surveillance after a predetermined time that is appropriate
for the operation in question. The space shall be manned or provided
with a fire patrol when detectors required by regulation are disconnected.
Detectors in all other spaces shall remain operational.
2.1.2 The fire detection system shall be designed
to:
-
.1 control and monitor input signals from all
connected fire and smoke detectors and manual call points;
-
.2 provide output signals to the navigation bridge,
continuously manned central control station or onboard safety centre
to notify the crew of fire and fault conditions;
-
.3 monitor power supplies and circuits necessary
for the operation of the system for loss of power and fault conditions;
and
-
.4 the system may be arranged with output signals
to other fire safety systems including:
-
.1 paging systems, fire alarm or public address
systems;
-
.2 fan stops;
-
.3 fire doors;
-
.4 fire dampers;
-
.5 sprinkler systems;
-
.6 smoke extraction systems;
-
.7 low-location lighting systems;
-
.8 fixed local application fire-extinguishing
systems;
-
.9 closed circuit television (CCTV) systems; and
-
.10 other fire safety systems.
2.1.3 The fire detection system may be connected
to a decision management system provided that:
-
.1 the decision management system is proven to
be compatible with the fire detection system;
-
.2 the decision management system can be disconnected
without losing any of the functions required by this chapter for the
fire detection system; and
-
.3 any malfunction of the interfaced and connected
equipment should not propagate under any circumstance to the fire
detection system.
2.1.4 Detectors and manual call points shall be
connected to dedicated sections of the fire detection system. Other
fire safety functions, such as alarm signals from the sprinkler valves,
may be permitted if in separate sections.
2.1.5 The system and equipment shall be suitably
designed to withstand supply voltage variation and transients, ambient
temperature changes, vibration, humidity, shock, impact and corrosion
normally encountered in ships. All electrical and electronic equipment
on the bridge or in the vicinity of the bridge shall be tested for
electromagnetic compatibility, taking into account the recommendations
developed by the Organizationfootnote.
2.1.6 Fixed fire detection and fire alarm systems
with individually identifiable fire detectors shall be so arranged
that:
-
.1 means are provided to ensure that any fault
(e.g., power break, short circuit, earth, etc.) occurring in the section
will not prevent the continued individual identification of the remainder
of the connected detectors in the section;
-
.2 all arrangements are made to enable the initial
configuration of the system to be restored in the event of failure
(e.g., electrical, electronic, informatics, etc.);
-
.3 the first initiated fire alarm will not prevent
any other detector from initiating further fire alarms; and
-
.4 no section will pass through a space twice.
When this is not practical (e.g., for large public spaces), the part
of the section which by necessity passes through the space for a second
time shall be installed at the maximum possible distance from the
other parts of the section.
2.1.7 In passenger ships, the fixed fire detection
and fire alarm system shall be capable of remotely and individually
identifying each detector and manually operated call point. Fire detectors
fitted in passenger ship cabins, when activated, shall also be capable
of emitting, or cause to be emitted, an audible alarm within the space
where they are located. In cargo ships and on passenger ship cabin
balconies the fixed fire detection and fire alarm system shall, as
a minimum, have section identification capability.
2.2
Sources of power supply
2.2.1 There shall be not less than two sources
of power supply for the electrical equipment used in the operation
of the fixed fire detection and fire alarm system, one of which shall
be an emergency source of power. The supply shall be provided by separate
feeders reserved solely for that purpose. Such feeders shall run to
an automatic change-over switch situated in or adjacent to the control
panel for the fire detection system. On ships constructed on or after
1 July 2014, the changeover switch shall be arranged such that a fault
will not result in the loss of both power supplies. The main (respective
emergency) feeder shall run from the main (respective emergency) switchboard
to the change-over switch without passing through any other distributing
switchboard.
2.2.2 On ships constructed on or after 1 July
2014, the operation of the automatic changeover switch or a failure
of one of the power supplies shall not result in loss of fire detection
capability. Where a momentary loss of power would cause degradation
of the system, a battery of adequate capacity shall be provided to
ensure continuous operation during changeover.
2.2.3 There shall be sufficient power to permit
the continued operation of the system with all detectors activated,
but not more than 100 if the total exceeds this figure.
2.2.4 The emergency source of power specified
in paragraph 2.2.1 above may be supplied by accumulator batteries
or from the emergency switchboard. The power source shall be sufficient
to maintain the operation of the fire detection and fire alarm system
for the periods required under chapter II-1, regulations 42 and 43,
of the Convention and, at the end of that period, shall be capable
of operating all connected visual and audible fire alarm signals for
a period of at least 30 min.
2.2.5 On ships constructed on or after 1 July
2014, where the system is supplied from accumulator batteries, they
shall be located in or adjacent to the control panel for the fire
detection system, or in another location suitable for use in an emergency.
The rating of the battery charge unit shall be sufficient to maintain
the normal output power supply to the fire detection system while
recharging the batteries from a fully discharged condition.
2.3
Component requirements
2.3.1.1 Detectors shall be operated
by heat, smoke or other products of combustion, flame, or any combination
of these factors. Detectors operated by other factors indicative of
incipient fires may be considered by the Administration provided that
they are no less sensitive than such detectors.
2.3.1.2 Smoke detectors required in all stairways,
corridors and escape routes within accommodation spaces shall be certified
to operate before the smoke density exceeds 12.5% obscuration per
metre, but not until the smoke density exceeds 2% obscuration per
metre, when tested according to standards EN 54:2001 and IEC 60092-504.
Alternative testing standards may be used as determined by the Administration.
Smoke detectors to be installed in other spaces shall operate within
sensitivity limits to the satisfaction of the Administration having
regard to the avoidance of detector insensitivity or oversensitivity.
2.3.1.3 Heat detectors shall be certified to operate
before the temperature exceeds 78ºC but not until the temperature
exceeds 54ºC, when the temperature is raised to those limits
at a rate less than 1ºC per min, when tested according to standards
EN 54:2001 and IEC 60092-504. Alternative testing standards may be
used as determined by the Administration. At higher rates of temperature
rise, the heat detector shall operate within temperature limits to
the satisfaction of the Administration having regard to the avoidance
of detector insensitivity or oversensitivity.
2.3.1.4 The operation temperature of
heat detectors in drying rooms and similar spaces of a normal high
ambient temperature may be up to 130ºC, and up to 140ºC
in saunas.
2.3.1.5 Flame detectors shall be tested according
to standards EN 54-10:2001 and IEC 60092-504. Alternative testing
standards may be used as determined by the Administration.
2.3.1.6 All detectors shall be of a
type such that they can be tested for correct operation and restored
to normal surveillance without the renewal of any component.
2.3.1.7 Fixed fire detection and fire
alarm systems for cabin balconies shall be approved by the Administration,
based on the guidelines developed by the Organizationfootnote.
2.3.1.8 Detectors fitted in hazardous
areas shall be tested and approved for such service. Detectors required
by regulation II-2/20.4 and
installed in spaces that comply with regulation
II-2/20.3.2.2 of the Convention need not be suitable for hazardous
areas. Detectors fitted in spaces carrying dangerous goods, required
by regulation II-2/19, table
19.3, of the Convention to comply with regulation
II-2/19.3.2 of the Convention, shall be suitable for hazardous
areas.
The control panel for the fire detection system
shall be tested according to standards EN 54-2:1997, EN 54-4:1997
and IEC 60092-504:2001. Alternative standards may be used as determined
by the Administration.
Cables used in the electrical circuits shall be
flame retardant according to standard IEC 60332-1. On passenger ships,
cables routed through other main vertical zones that they serve, and
cables to control panels in an unattended fire control station shall
be fire resisting according to standard IEC 60331, unless duplicated
and well separated.
2.4
Installation requirements
2.4.1.1 Detectors and manually operated call points
shall be grouped into sections.
2.4.1.2 A section of fire detectors which covers
a control station, a service space or an accommodation space shall
not include a machinery space of category A or a ro-ro space. A section
of fire detectors which covers a ro-ro space shall not include a machinery
space of category A. For fixed fire detection systems with remotely
and individually identifiable fire detectors, a section covering fire
detectors in accommodation, service spaces and control stations shall
not include fire detectors in machinery spaces of category A or ro-ro
spaces.
2.4.1.3 Where the fixed fire detection and fire
alarm system does not include means of remotely identifying each detector
individually, no section covering more than one deck within accommodation
spaces, service spaces and control stations shall normally be permitted
except a section which covers an enclosed stairway. In order to avoid
delay in identifying the source of fire, the number of enclosed spaces
included in each section shall be limited as determined by the Administration.
If the detection system is fitted with remotely and individually identifiable
fire detectors, the sections may cover several decks and serve any
number of enclosed spaces.
2.4.1.4 In passenger ships, a section of detectors
and manually operated call points shall not be situated in more than
one main vertical zone, except on cabin balconies.
2.4.2 Positioning of detectors
2.4.2.1 Detectors shall be located for optimum
performance. Positions near beams and ventilation ducts, or other
positions where patterns of air flow could adversely affect performance,
and positions where impact or physical damage is likely, shall be
avoided. Detectors shall be located on the overhead at a minimum distance
of 0.5 m away from bulkheads, except in corridors, lockers and stairways.
2.4.2.2 The maximum spacing of detectors shall
be in accordance with the table below:
Table 9.1 – Spacing of detectors
Type of detector
|
Maximum floor area per detector (m2)
|
Maximum distance apart between centres (m)
|
Maximum distance away from bulkheads (m)
|
Heat
|
37
|
9
|
4.5
|
Smoke
|
74
|
11
|
5.5
|
The Administration may require or permit other spacing based
upon test data which demonstrate the characteristics of the detectors.
Detectors located below moveable ro-ro decks shall be in accordance
with the above.
2.4.2.3 Detectors in stairways shall be located
at least at the top level of the stair and at every second level beneath.
2.4.2.4 When fire detectors are installed in freezers,
drying rooms, saunas, parts of galleys used to heat food, laundries
and other spaces where steam and fumes are produced, heat detectors
may be used.
2.4.2.5 Where a fixed fire detection and fire
alarm system is required by regulation
II-2/7.5 of the Convention, spaces having little or no fire
risk need not be fitted with detectors. Such spaces include void spaces
with no storage of combustibles, private bathrooms, public toilets,
fire-extinguishing medium storage rooms, cleaning gear lockers (in
which flammable liquids are not stowed), open deck spaces and enclosed
promenades having little or no fire risk and that are naturally ventilated
by permanent openings.
2.4.3 Arrangement of cables
2.4.3.1 Cables which form part of the system shall
be so arranged as to avoid galleys, machinery spaces of category A,
and other enclosed spaces of high fire risk except where it is necessary
to provide for fire detection or fire alarms in such spaces or to
connect to the appropriate power supply.
2.4.3.2 A section with individually identifiable
capability shall be arranged so that it cannot be damaged at more
than one point by a fire.
2.5
System control requirements
2.5.1 Visual and audible fire signalsfootnote
2.5.1.1 The activation of any detector
or manually operated call point shall initiate a visual and audible
fire detection alarm signal at the control panel and indicating units.
If the signals have not been acknowledged within 2 min, an audible
fire alarm shall be automatically sounded throughout the crew accommodation
and service spaces, control stations and machinery spaces of category
A. This alarm sounder system need not be an integral part of the detection
system.
2.5.1.2 In passenger ships, the control
panel shall be located in the onboard safety centre. In cargo ships,
the control panel shall be located on the navigation bridge or in
the fire control station.
2.5.1.3 In passenger ships, an indicating unit
that is capable of individually identifying each detector that has
been activated or manually operated call point that has operated shall
be located on the navigation bridge. In cargo ships, an indicating
unit shall be located on the navigation bridge if the control panel
is located in the fire control station. In ships constructed on or
after 1 July 2014, with a cargo control room, an additional indicating
unit shall be located in the cargo control room. In cargo ships and
on passenger cabin balconies, indicating units shall, as a minimum,
denote the section in which a detector has activated or manually operated
call point has operated.
2.5.1.4 Clear information shall be displayed
on or adjacent to each indicating unit about the spaces covered and
the location of the sections.
2.5.1.5 Power supplies and electric
circuits necessary for the operation of the system shall be monitored
for loss of power and fault conditions as appropriate including:
-
.1 a single open or power break fault caused by
a broken wire;
-
.2 a single ground fault caused by the contact
of a wiring conductor to a metal component; and
-
.3 a single wire to wire fault caused by the contact
of two or more wiring conductors.
Occurrence of a fault condition shall initiate a visual
and audible fault signal at the control panel which shall be distinct
from a fire signal.
2.5.1.6 Means to manually acknowledge
all alarm and fault signals shall be provided at the control panel.
The audible alarm sounders on the control panel and indicating units
may be manually silenced. The control panel shall clearly distinguish
between normal, alarm, acknowledged alarm, fault and silenced conditions.
2.5.1.7 The system shall be arranged
to automatically reset to the normal operating condition after alarm
and fault conditions are cleared.
2.5.1.8 When the system is required
to sound a local audible alarm within the cabins where the detectors
are located, a means to silence the local audible alarms from the
control panel shall not be permitted.
2.5.1.9 In general, audible alarm sound
pressure levels at the sleeping positions in the cabins and 1 m from
the source shall be at least 75 dB(A) and at least 10 dB(A) above
ambient noise levels existing during normal equipment operation with
the ship under way in moderate weather. The sound pressure level should
be in the 1/3 octave band about the fundamental frequency. Audible
alarm signals shall not exceed 120 dB(A).
Suitable instructions and component spares for testing and
maintenance shall be provided. Detectors shall be periodically tested
using equipment suitable for the types of fires to which the detector
is designed to respond. On ships constructed on or after 1 July 2014,
detectors installed within cold spaces such as refrigerated compartments
shall be tested using procedures having due regard for such locations.footnote Ships with self-diagnostic systems that
have in place a cleaning regime for areas where heads may be prone
to contamination may carry out testing in accordance with the requirements
of the Administration.
|