4.1.1
Best Practices and design
-
.1 Manual pressure relief procedures (tank pressure
control);
-
.2 P/V valve condition and maintenance;
-
.3 Condition of gaskets for hatches and piping;
-
.4 Inert gas topping up procedures;
-
.5 Partially filled tanks;
-
.6 Loading sequence and rate; and
-
.7 Use of vapour return manifold and pipelines
when shore facilities are available.
4.1.2
Vapour Emission Control Systems
The principle behind VECS is that VOC generated in cargo tanks
during loading is returned to the shore terminal for processing, as
opposed to being emitted to atmosphere through the mast riser.
Vapour Emission Control Systems (VECS) were introduced in 1990
as a requirement for tankers loading oil and noxious liquid substances
at terminals in the United States (USCG 46 CFR Part 39). IMO followed
up with the introduction of IMO MSC/Circ.585 “Standards
for vapour emission control systems” in 1992. International
regulation requiring vapour emission control was introduced through regulation 15 of MARPOL Annex VI adopted
in 1997, although it is only required for ships loading cargo at terminals
where IMO has been informed that VECS is mandatory.
Since
1990, most crude tankers have installed a VECS system in compliance
with USCG regulations. The regulations cover both the technical installation
(vapour recovery piping and manifold, vapour pressure sensors and
alarms, level gauging, high level and independent overflow alarms)
as well as operational restrictions and training. The operational
restrictions are found in a mandatory VECS manual which also includes
maximum allowable loading rates. The maximum allowable loading rate
is limited by one of the following:
-
.1 the pressure drop in the VECS system from cargo
tank to vapour manifold (not to exceed 80% of the P/V valve setting);
-
.2 the maximum pressure relief flow capacity of
the P/V valve for each cargo tank;
-
.3 the maximum vacuum relief flow capacity of
the P/V valve for each cargo tank (assuming loading stopped while
terminal vacuum fans are still running); and
-
.4 the time between activation of overfill alarm
to relevant cargo tank being full (min. 1 minute).
The calculations are to be based on maximum cargo vapour/air
densities as well as maximum cargo vapour growth rates, which again
may limit the cargoes that can be loaded with VECS.
Further,
the calculations are to be carried out both for single tank and multiple
tank loading scenarios.
The USCG regulations also contain
additional requirements to vapour balancing, i.e. for tankers involved
in lightering operations. These include operational requirements as
well as technical requirements for an in-line detonation arrestor,
oxygen sensors with alarms and possibly means to prevent hazards from
electrostatic charges.
For ships provided with a VECS
system as per IMO or USCG regulations, the control of VOC emissions
will be through returning VOC to the shore terminal in accordance
with the procedures found in the onboard VECS manual.
The
maximum allowable loading rates and corresponding maximum vapour/air
densities and vapour growth rates should be specified in the VOC management
plan.
4.1.3
Vapour Pressure Release Control Valve
(VOCON valve)
The VOCON valve operates as a hydraulically controlled valve
that controls the closing pressure for the valve and therefore undertakes
a similar procedure to the manual VOCON procedure as described in
4.2.2 below. However, for the loading programme, the valve also allows
a higher pressure to be maintained throughout the loading process
in order to limit the extent of vapour evolution from the crude oil
once saturated vapour pressure is achieved within the tank vapour
system. This valve is normally a single valve facility and located
at the bottom of the mast riser by way of a by-pass pipeline to the
mast riser control valve. The relevant closing pressure setting for
the valve may be done locally or remotely in the Cargo Control Room
depending upon the sophistication of the installed system.
Figure 4.1 Hydraulically controlled VOCON valve
Similar valves with fixed pressure arrangements are to be
found and are currently installed on tankers and located at the same
position; namely at the bottom of the mast riser by way of a by-pass
pipeline to the mast riser control valve. These valves operate as
a form of “tank breather” valve but release vapour through
the mast riser.
4.1.4
Cargo Pipeline Partial Pressure control
system (KVOC)
The purpose of the KVOC system installation is to minimize VOC
release to the atmosphere by preventing the generation of VOC during
loading and transit. The basic principle of KVOC is to install a new
drop pipeline column specially designed for each tanker with respect
to expected loading rate. The new drop pipeline column will normally
have an increased diameter compared to an ordinary drop line. The
increased diameter will reduce the velocity of the oil inside the
column and by that means ensure that the pressure adjusts itself to
approximately the boiling point of the oil independent of the loading
rate. In the initial phase of the loading process some VOC might be
generated. The pressure inside the column will adjust itself to the
SVP of the oil so that there is a balance between the pressure inside
the column and the oil SVP. When this pressure has been obtained in
the column the oil will be loaded without any additional VOC generation.
This means that KVOC column prevents under pressure to occur in the
loading system during loading.
The KVOC system is not
designed to remove all VOC, but to minimize generation of VOC. VOC
remaining in the tanks from the last cargo and COW operations has
to be displaced from the cargo tanks when loading. Also, if the oil
boiling point (SVP) is higher than the tank pressure, some crude oil
will generate VOC in the tanks and additional VOC be released. Bad
weather together with very volatile oil will also increase the VOC
emissions due to its SVP also when KVOC is applied.
The
KVOC column has an effect on the VOC release during transit, because
gas bubbles have been prevented from forming. This means that the
amount of gas bubbles in the oil available for release during transit
will be minimized. To further reduce the release of VOC, the pressure
in the cargo tanks should be held as high as possible. A high pressure,
from about 800 to 1,000 mmWG, will reduce possible boiling and diffusion
of VOC in the crude oil cargo tanks.
KVOC has also shown
a similar effect on H2S as on minimizing VOC generation.
If the KVOC system has been installed, it should therefore always
be used when loading sour crude to minimize H2S concentration in the
void spaces and release during loading and transit.
Pipeline Flow Plan for KVOC
4.1.5
Increased pressure relief settings
(Applicable also for transit conditions)
As described in sections 2 and 3, as long as the tank pressure
is maintained above the Saturated Vapour Pressure of the cargo, then
equilibrium is obtained between the liquid and vapour phase of the
cargo and no further VOC will evolve from the cargo. This means that
if the pressure/vacuum relief settings are increased to, e.g., 2,100
mmWG, VOC will not evolve from a cargo as long as the Saturated Vapour
Pressure of said cargo is below the pressure relief setting.
As indicated earlier, the maximum design pressure of a cargo
tank is at least 2,500 mmWG and, as such, increasing the settings
of the pressure/vacuum devices up to, e.g., 2,100 mmWG, should not
require additional strengthening. It will however require adjustment/replacement
of P/V valves. Note that for some P/V valves designs, the pressure
after initial opening increases, and this has to be taken into account
if an owner intends to increase the setting of P/V valves.
Needless
to say it will also require replacement/modifications to the P/V breaker,
as well as water loops serving the inert gas deck water seal, as well
as settings of pressure sensors and alarms in the inert gas and VECS
system. It is of course also essential that onboard operational procedures
in terms of manual pressure release have to be adjusted.
One
additional benefit is that increasing the pressure/vacuum relief settings
will increase the acceptable loading rate during VECS.
Although
the primary benefit of increasing set pressure will occur during voyage.
It will also have an effect related to loading, as the increased set
pressure will limit the existing vapour in the cargo tanks, i.e. the
vapour generated during the previous discharge and Crude Oil Washing.
For ships that have been provided with increased pressure relief
settings, the VOC emissions will be controlled when the saturated
vapour pressure of the crude oil is below that of the pressure relief
valve settings.
It is important that terminals and cargo
surveyors acknowledge that if ships with higher pressure settings
are required to de-pressurize prior to cargo handling operations,
this will limit the ships’ ability to control VOC emissions.
4.1.6 Vapour recovery systems – General
In the late 1990s certain Administrations required offshore
installations to reduce their emissions of VOC and this led to the
development and installation of vapour recovery systems on board shuttle
tankers in the North Sea. Different concepts were developed for the
purpose of reducing the emissions of non-methane VOC (VOC). The initial
efficiency requirement was set to 78% (i.e. 78% less VOC emissions
when using vapour recovery systems). The systems can recover VOC in
all operational phases.
For ships that have been provided
with vapour recovery systems, the VOC emissions will be controlled
when the recovery plant is in operation.
The VOC recovery
plant efficiency as well as any operational limitations related to,
e.g., applicability for different cargo handling modes (loading, transit,
COW), maximum allowable loading rates or crude vapour pressures, are
to be specified in the VOC management plan.
4.1.6.1
Vapour Recovery Systems –
Condensation Systems
The principle is similar to that of re-liquefaction plants on
LPG carriers, i.e. condensation of VOC emitted from cargo tanks. In
the process, the VOC passes through a knock out drum before it is
pressurized and liquefied in a two stage process. The resulting liquefied
gas is stored in a deck tank under pressure and could either be discharged
to shore, or be used as fuel (possibly including methane and ethane)
for boilers or engines subject to strict safety requirements. It is
also conceivable that the stored gas could be used as an alternative
to inert gas subject to the Administration’s acceptance.
4.1.6.2
Vapour Recovery Systems –
Absorption Systems
The technology is based on the absorption of VOCs in a counter-current
flow of crude oil in an absorber column. The vapour is fed into the
bottom of the column, with the side stream of crude oil acting as
the absorption medium. The oil containing the absorbed VOC is then
routed from the bottom of the column back to the loading line where
it is mixed with the main crude oil loading stream. Oil pumps and
compressors are used to pressurize the oil and gas. Unabsorbed gases
are relieved to the riser to increase the recovery efficiency. Similar
concepts have been developed using swirl absorbers instead of an absorption
column.
4.1.6.3 Vapour Recovery Systems – Absorption
Carbon Vacuum-Regenerated Adsorption
In the CVA process, the crude oil vapours are filtered through
active carbon, which adsorbs the hydrocarbons. Then the carbon is
regenerated in order to restore its adsorbing capacity and adsorb
hydrocarbons in the next cycle. The pressure in the carbon bed is
lowered by a vacuum pump until it reaches the level where the hydrocarbons
are desorbed from the carbon. The extracted, very highly concentrated
vapours then pass into the absorber, where the gas is absorbed in
a stream of crude oil taken from and returned to the cargo tanks.
As carbon bed adsorption systems are normally sensitive to high
concentrations of hydrocarbons in the VOC inlet stream, the VOC feed
stream first passes through an inlet absorber where some hydrocarbons
are removed by absorption. The recovered VOC stream may be reabsorbed
in the originating crude oil in the same inlet absorber.