Where the space containing the foam generators is close
                                 to the protected space, the relevant delivery ducts should meet the
                                 following requirements:
                              
                              
                              
                              
                                 - 
                                    
                                    
                                    
                                       .1 they should be made of steel having a thickness
                                       of not less than 5 mm;
                                     
- 
                                    
                                    
                                    
                                       .2 they should have a length, within the foam
                                       generator space, of a least 450 mm; and
                                     
- 
                                    
                                    
                                    
                                       .3 their openings at the bulkhead or deck between
                                       the foam generator space and the protected space should be provided
                                       with a damper (single or multi-bladed) made of stainless steel with
                                       a thickness of not less than 3 mm. Those dampers should be automatically
                                       operated (electrically, pneumatically or hydraulically) by means of
                                       remote control of the foam generator related to them.