Regulation 10.5: Number of systems, appliances, and extinguishers required in machinery spaces
Clasification Society 2024 - Version 9.40
Statutory Documents - IMO Publications and Documents - Circulars - Maritime Safety Committee - MSC/Circular.1120 – Unified Interpretations of SOLAS Chapter II-2, the FSS Code, the FTP Code and Related Fire Test Procedures – (2 June 2004)Amended by MSC.1/Circular.1436 - Annex - Unified Interpretations of SOLAS Chapter II-2, the FSS Code, the FTP Code and Related Fire Test Procedures - Appendix - Explanatory Sketches - Regulation 10.5: Number of systems, appliances, and extinguishers required in machinery spaces

Regulation 10.5: Number of systems, appliances, and extinguishers required in machinery spaces

Table 1

Systems appliances & extinguishers → Fixed fire extinguishing system Portable foam applicator *1 Portable foam extinguishers Add'l Portable foam extinguishers 135 l foam extinguisher 45 l foam extinguishers *2 Sand boxes *3
Category A Machinery ↓ spaces
SOLAS paragraph → 10.5.1.1,
10.5.2.1
10.5.1.2.1
10.5.2.2.1
10.5.1.2.2 10.5.2.2.2 10.5.1.2.2 10.5.2.2.2 10.5.2.2.2
Oil-fired boilers 1 1 2N NA 1*4 - N
Oil-fired boilers and oil fuel units 1 1 2N+2 NA 1*4 - N
Engine room containing:
Oil fuel units only 1 - 2 NA - - -
Internal combustion machinery 1 1 x - y -
Internal combustion machinery and oil fuel units 1 1 x - y -
Combined engine/boiler room containing:
Internal combustion machinery, oil fired boilers and oil fuel units 1 1 (2N+2) or x
whichever is greater
1*4 y*5 N

N = number of firing spaces.

"2N" means that two extinguishers are to be located in each firing space.

X = sufficient number, minimum two in each space, so located that there are at least one portable fire extinguisher within 10 m walking distance from any point.

y = sufficient number to enable foam to be directed onto any part of the fuel lubricating oil pressure systems, gearing and other fire hazard.

Notes:

*1. May be located at outside of the entrance to the room.

*2. May be arranged outside of the space concerned for smaller spaces of cargo ships.

*3. The amount of sand is to be at least 0.1 m3.

*4. Not required for such spaces in cargo ships wherein all boilers contained therein are for domestic services and are less than 175kW.

*5. In case of machinery spaces containing both boilers and internal combustion engines (case not explicitly considered in regulation 10.5) regulation 10.5.1 and 10.5.2 apply, with the exception that one of the foam fire-extinguishers of at least 45 l capacity or equivalent (required by regulation 10.5.2.2.2) may be omitted on the condition that the 135 l extinguisher (required by regulation 10.5.1.2.2) can protect efficiently and readily the area covered by 45 l extinguisher.

*6. Oil fired machinery other than boilers such as fired inert gas generators, incinerators and waste disposal units are to be considered the same as boilers insofar as the required number and type of fire fighting appliances are concerned.


Copyright 2022 Clasifications Register Group Limited, International Maritime Organization, International Labour Organization or Maritime and Coastguard Agency. All rights reserved. Clasifications Register Group Limited, its affiliates and subsidiaries and their respective officers, employees or agents are, individually and collectively, referred to in this clause as 'Clasifications Register'. Clasifications Register assumes no responsibility and shall not be liable to any person for any loss, damage or expense caused by reliance on the information or advice in this document or howsoever provided, unless that person has signed a contract with the relevant Clasifications Register entity for the provision of this information or advice and in that case any responsibility or liability is exclusively on the terms and conditions set out in that contract.