1 Battery room ventilators should be fitted with
a means of closing whenever:
-
.1 the battery room does not open directly onto
an exposed deck;
-
.2 the ventilation opening for the battery room
is required to be fitted with a closing device according to the Load Line Convention (i.e. the height of the opening
does not extend to more than 4.5 m (14.8 feet) above the deck for
position 1 or to more than 2.3 m (7.5 feet) above the deck in position
2; or
-
.3 the battery room is fitted with a fixed gas
fire-extinguishing system.
2 Where a battery room ventilator is fitted with
a closing device, then a warning notice stating, for example "This
closing device is to be kept open and only closed in the event of
fire or other emergency – Explosive gas", should be provided
at the closing device to mitigate the possibility of inadvertent closing.