3.1 Each system shall be fitted with a readily
accessible, manually operated isolating valve in the supply pressure
part of the system.
3.2 In multiple cylinder installations, in addition
to each cylinder shutoff valve there should be non-return valves near
the stop valves. Where there is a change over device (automatic or
manual) it should be provided with non-return valves to isolate any
depleted container.
3.3 When more than one container can supply a
system, the system should not be used with a container removed unless
the unattached pipe is fitted with a suitable gas tight plug arrangement.
3.4 Containers not in use or not being fitted
into an installation should have the protecting cap in place over
the container valve.