The test should be terminated, the specimen removed, and
the dummy specimen in its holder reinserted when any one of the following
is applicable:
-
.1 the specimen fails to ignite after a 10 min
exposure;
-
.2 3 min have passed since all flaming from the
specimen ceased;
-
.3 flaming reaches the end of the specimen or
self-extinguishes and thus ceases progress along the specimen. This
criterion should only be used when heat release measurements are not
being made.
8.2.1 Operations 8.1.1 to 8.1.7 should be repeated
for two additional specimens (see 8.3).