Part 1 - Non-combustibility test
Paragraph 2.1
The test exposure need not exceed a 30 minute duration.
Part 3 - Test for “A”, “B” and “F” class divisions
Paragraph 2.2.1
The minimum bulkhead panel height should be a standard height of the manufactured panel with a dimension of 2,400 mm.
Resolution A.754(18), appendix A.II
Paragraph 2.2.4
The distance between the fire damper and the structural core specified in paragraph 2.2.4 means the distance between the fire damper centre and the structural core.
Paragraph 4
If evaluation of insulation is required, it should prevent a temperature rise at any point on the surface not exceeding 180oC above the initial temperature. The average temperature rise is not relevant.