4.2.1 The nominal release temperatures of automatic
glass bulb nozzles should be as indicated in Table 1.
Nominal Release
Temperature
Table 1 - Nominal release temperature
|
GLASS BULB NOZZLES
|
FUSIBLE ELEMENT NOZZLES
|
Nominal release
tempreture (0C)
|
Liquid
color code
|
Nominal
release tempreture (0C)
|
Frame color
code +
|
57
|
orange
|
57 to
77
|
uncolored
|
68
|
red
|
80 to
107
|
white
|
79
|
yellow
|
121 to
149
|
red
|
93–100
|
green
|
163 to
191
|
blue
|
121–141
|
blue
|
204 to
246
|
green
|
163–182
|
mauve
|
260 to
343
|
orange
|
204–343
|
black
|
|
|
4.2.2 The nominal release temperatures of fusible
automatic element nozzles should be specified in advance by the manufacturer
and verified in accordance with 4.3.
Nominal release temperatures should be within the ranges specified
in Table 1.
4.2.3 The nominal release temperature that is
to be marked on the nozzle should be that determined when the nozzle
is tested in accordance with 5.6.1,
taking into account the specifications of 4.3.