The extension of the bulkhead should be made of non-combustible
                                 material and the construction of the extension should correspond to
                                 the fire class of extended bulkhead. If the extended bulkhead is of
                                 B-0 class standard, then the extension may be made of thin steel plates
                                 of 1 mm thickness and tightened (e.g. with mineral wool). Alternatively,
                                 B-0 class extensions may be constructed of a suitably supported mineral
                                 wool (density at least 100 kg/m3, thickness at least 50
                                 mm).