6.2 Daily verification
Clasification Society 2024 - Version 9.40
Statutory Documents - IMO Publications and Documents - Resolutions - Assembly - IMO Resolution A.653(16) – Recommendation on Improved Fire Test Procedures for Surface Flammability of Bulkhead, Ceiling and Deck Finish Materials – (Adopted on 19 October 1989) - Annex - Recommendation on Improved Fire Test Procedures for Surface Flammability of Bulkhead, Ceiling and Deck Finish Materials - 6 Calibration - 6.2 Daily verification

6.2 Daily verification

 As a means of assuring continued proper adjustment of the apparatus, the following tests should be performed on a daily basis, or more frequently if the nature of the specimens makes this necessary.

  6.2.1 Adjustment of the Pilot Burner, the acetylene and air supply should be adjusted to provide a flame length of about 230 mmfootnote. When this has been done, the flame length as viewed in a darkened laboratory will be seen to extend about 40 mm above the upper retaining flange of the specimen holder. The burner spacing from the specimen is adjusted while the radiant source is operating by the use of softwood splines of 3 mm thickness and of 10 mm and 12 mm width. When these splines are moved during a two second exposure along the flame length, between the pilot burner flame and a dummy specimen surface, the 10 mm spline should not be charred but the 12 mm spline should show char. With the specimen in the vertical position, the charring of the 12 mm spline should occur over a vertical distance of at least 40 mm from the upper exposed edge of the specimen (see Figure 9).

Figure 8 Pilot burner details and connections

Figure 9 Position of pilot flame

  6.2.2 The stack gas thermocouples should be cleaned by light brushing at least daily. This cleaning may be required even more frequently, in some instances before each test, when materials producing heavy soot clouds are tested. These thermocouples should also be individually checked for electrical continuity to ensure the existence of a useful thermojunction. Following daily cleaning of the parallel connected stack gas thermocouples, both they and the compensating junction should be checked to verify that the resistance between them and the stack is in excess of 106 ohms.


Copyright 2022 Clasifications Register Group Limited, International Maritime Organization, International Labour Organization or Maritime and Coastguard Agency. All rights reserved. Clasifications Register Group Limited, its affiliates and subsidiaries and their respective officers, employees or agents are, individually and collectively, referred to in this clause as 'Clasifications Register'. Clasifications Register assumes no responsibility and shall not be liable to any person for any loss, damage or expense caused by reliance on the information or advice in this document or howsoever provided, unless that person has signed a contract with the relevant Clasifications Register entity for the provision of this information or advice and in that case any responsibility or liability is exclusively on the terms and conditions set out in that contract.