For all "A" class divisions, including those with doors,
the test should continue for minimum 60 min.
When the specimen is of an "A" class division, with a structural
steel core which is imperforate (e.g. without door), and where insulation
is provided to the exposed face only (i.e. the structural steel core
is the unexposed face of the construction), it is permitted to terminate
the test prior to 60 min once the unexposed-face temperature-rise
limits have been exceeded.