Two-year inspections should be carried out to ensure that
the indicated actions are taken for the specified equipment.
8.1 Fixed gas fire-extinguishing systems
-
.1 all high pressure extinguishing agents cylinders
and pilot cylinders should be weighed or have their contents verified
by other reliable means to confirm that the available charge in each
is above 95 per cent of the nominal charge. Cylinders containing less
than 95 per cent of the nominal charge should be refilled; and
-
.2 blow dry compressed air or nitrogen through
the discharge piping or otherwise confirm the pipe work and nozzles
are clear of any obstructions. This may require the removal of nozzles,
if applicable.
8.2 Fixed dry chemical powder systems
-
.1 blow dry nitrogen through the discharge piping
to confirm that the pipe work and nozzles are clear of any obstructions;
-
.2 operationally test local and remote controls
and section valves;
-
.3 verify the contents of propellant gas cylinders
(including remote operating stations);
-
.4 test a sample of dry chemical powder for moisture
content; and
-
.5 subject the powder containment vessel, safety
valve and discharge hoses to a full working pressure test.