10.4.1 Where a fixed fire-extinguishing system
or alternative fire-extinguishing system situated in a space separate
from the compartment containing the main fire pumps utilizes its own
independent sea suction, this sea suction should be capable of being
cleared of accumulations of slush ice.
10.4.2 Fire pump(s) including emergency fire pump(s)
should, wherever reasonable and practicable, be installed in heated
compartment(s) and in any event should be adequately protected from
freezing for minimum temperature for the intended voyage.
10.4.3 Isolating valves should be located so that
they are accessible. Any isolating valves located in exposed positions
should not be subject to icing from freezing spray. The fire main
should be arranged so that external sections can be isolated and draining
devices should be provided.
10.4.4 Hydrants should be positioned or designed
to remain operable under all anticipated temperatures. Ice accumulation
and freezing should be taken into account.
10.4.5 All hydrants should be equipped with an
efficient two-handed valve handle.