1.1.1 These Guidelines specify the test procedures
for the type approval of fixed high-expansion foam systems. The procedures
consist of the following parts:
-
.1 appendix 1: fire test procedures for evaluating
the fire-extinguishing effectiveness of the foam system;
-
.2 appendix 2: component manufacturing test procedures
intended to ensure the operability of the system components in the
marine environment; and
-
.3 appendix 3: procedures for determining the
discharge capacity of the high-expansion foam generators.
1.1.2 These Guidelines are not intended for testing
the performance of high-expansion foam concentrates.
1.1.3 Appendix 4 to the Guidelines is an optional
small scale test intended to verify the fire-extinguishing effectiveness
of high-expansion foam when made with hot, smoke-laden inside air.
This test is recommended for quality control of foam concentrates,
and may also be used to compare the extinguishing performance of foam
concentrates made with freshwater to those made with seawater.