Part C – Suppression of Fire
Regulation 7 – Detection
and alarm
1 Purpose
The purpose of this regulation is to detect a fire in the
space of origin and to provide for alarm for safe escape and fire-fighting
activity. For this purpose, the following functional requirements
shall be met:
-
.1 fixed fire detection and fire alarm system
installations shall be suitable for the nature of the space, fire
growth potential and potential generation of smoke and gases;
-
.2 manually operated call points shall be placed
effectively to ensure a readily accessible means of notification;
and
-
.3 fire patrols shall provide an effective means
of detecting and locating fires and alerting the navigation bridge
and fire teams.
2 General requirements
2.1 A fixed fire detection and fire alarm system
shall be provided in accordance with the provisions of this regulation.
2.2 A fixed fire detection and fire alarm system
and a sample extraction smoke detection system required in this regulation
and other regulations in this part shall be of an approved type and
comply with the Fire Safety Systems Code.
2.3 Where a fixed fire detection and fire alarm
system is required for the protection of spaces other than those specified
in paragraph 5.1, at least one detector complying with the Fire Safety Systems Code shall be installed in each
such space.
3 Initial and periodical tests
3.1 The function of fixed fire detection and fire
alarm systems required by the relevant regulations of this chapter
shall be tested under varying conditions of ventilation after installation.
3.2 The function of fixed fire detection and fire
alarm systems shall be periodically tested to the satisfaction of
the Administration by means of equipment producing hot air at the
appropriate temperature, or smoke or aerosol particles having the
appropriate range of density or particle size, or other phenomena
associated with incipient fires to which the detector is designed
to respond.
4 Protection of machinery spaces
4.1
Installation
A fixed fire detection and fire alarm system shall be installed
in:
4.2
Design
The fixed fire detection and fire alarm system required
in paragraph 4.1.1 shall be so designed and the detectors so positioned
as to detect rapidly the onset of fire in any part of those spaces
and under any normal conditions of operation of the machinery and
variations of ventilation as required by the possible range of ambient
temperatures. Except in spaces of restricted height and where their
use is specially appropriate, detection systems using only thermal
detectors shall not be permitted. The detection system shall initiate
audible and visual alarms distinct in both respects from the alarms
of any other system not indicating fire, in sufficient places to ensure
that the alarms are heard and observed on the navigating bridge and
by a responsible engineer officer. When the navigating bridge is unmanned
the alarm shall sound in a place where a responsible member of the
crew is on duty.
5 Protection of accommodation and service
spaces and control stations
5.1
Smoke detectors in accommodation spaces
Smoke detectors shall be installed in all stairways, corridors
and escape routes within accommodation spaces as provided in paragraphs
5.2, 5.3 and 5.4. Consideration shall be given to the installation
of special purpose smoke detectors within ventilation ducting.
5.2
Requirements for passenger ships carrying
more than 36 passengers
A fixed fire detection and fire alarm system shall be installed
and arranged as to provide smoke detection in service spaces, control
stations and accommodation spaces, including corridors, stairways
and escape routes within accommodation spaces. Smoke detectors need
not be fitted in private bathrooms and galleys. Spaces having little
or no fire risk such as voids, public toilets, carbon dioxide rooms
and similar spaces need not be fitted with a fixed fire detection
and alarm system.
5.3
Requirements for passenger ships carrying
not more than 36 passengers
There shall be installed throughout each separate zone,
whether vertical or horizontal, in all accommodation and service spaces
and, where it is considered necessary by the Administration, in control
stations, except spaces which afford no substantial fire risk such
as void spaces, sanitary spaces, etc., either:
-
.1 a fixed fire detection and fire alarm system
so installed and arranged as to detect the presence of fire in such
spaces and providing smoke detection in corridors, stairways and escape
routes within accommodation spaces; or
-
.2 an automatic sprinkler, fire detection and
fire alarm system of an approved type complying with the relevant
requirements of the Fire Safety Systems Code and
so installed and arranged as to protect such spaces and, in addition,
a fixed fire detection and fire alarm system and so installed and
arranged as to provide smoke detection in corridors, stairways and
escape routes within accommodation spaces.
5.4
Protection of atriums in passenger ships
The entire main vertical zone containing the atrium shall
be protected throughout with a smoke detection system.
5.5 Cargo ships
Accommodation and service spaces and control stations of
cargo ships shall be protected by a fixed fire detection and fire
alarm system and/or an automatic sprinkler, fire detection and fire
alarm system as follows depending on a protection method adopted in
accordance with regulation 9.2.3.1.
A fixed fire detection and fire alarm system shall be so
installed and arranged as to provide smoke detection in all corridors,
stairways and escape routes within accommodation spaces.
An automatic sprinkler, fire detection and fire alarm system
of an approved type complying with the relevant requirements of the Fire Safety Systems Code shall be so installed and
arranged as to protect accommodation spaces, galleys and other service
spaces, except spaces which afford no substantial fire risk such as
void spaces, sanitary spaces, etc. In addition, a fixed fire detection
and fire alarm system shall be so installed and arranged as to provide
smoke detection in all corridors, stairways and escape routes within
accommodation spaces.
A fixed fire detection and fire alarm system shall be so
installed and arranged as to detect the presence of fire in all accommodation
spaces and service spaces providing smoke detection in corridors,
stairways and escape routes within accommodation spaces, except spaces
which afford no substantial fire risk such as void spaces, sanitary
spaces, etc. In addition, a fixed fire detection and fire alarm system
shall be so installed and arranged as to provide smoke detection in
all corridors, stairways and escape routes within accommodation spaces.
6 Protection of cargo spaces in passenger
ships
A fixed fire detection and fire alarm system or a sample
extraction smoke detection system shall be provided in any cargo space
which, in the opinion of the Administration, is not accessible, except
where it is shown to the satisfaction of the Administration that the
ship is engaged on voyages of such short duration that it would be
unreasonable to apply this requirement.
7 Manually operated call points
Manually operated call points complying with the Fire Safety Systems Code shall be installed throughout
the accommodation spaces, service spaces and control stations. One
manually operated call point shall be located at each exit. Manually
operated call points shall be readily accessible in the corridors
of each deck such that no part of the corridor is more than 20 m from
a manually operated call point.
8 Fire patrols in passenger ships
8.1
Fire patrols
For ships carrying more than 36 passengers an efficient
patrol system shall be maintained so that an outbreak of fire may
be promptly detected. Each member of the fire patrol shall be trained
to be familiar with the arrangements of the ship as well as the location
and operation of any equipment he may be called upon to use.
8.2
Inspection hatches
The construction of ceiling and bulkheads shall be such
that it will be possible, without impairing the efficiency of the
fire protection, for the fire patrols to detect any smoke originating
in concealed and inaccessible places, except where in the opinion
of the Administration there is no risk of fire originating in such
places.
8.3
Two-way portable radiotelephone apparatus
Each member of the fire patrol shall be provided with a
two-way portable radiotelephone apparatus.
9 Fire alarm signalling systems in passenger
ships
footnote
9.1 Passenger ships shall at all times when at
sea, or in port (except when out of service), be so manned or equipped
as to ensure that any initial fire alarm is immediately received by
a responsible member of the crew.
9.2 The control panel of fixed fire detection
and fire alarm systems shall be designed on the fail-safe principle
(e.g. an open detector circuit shall cause an alarm condition).
9.3 Passenger ships carrying more than 36 passengers
shall have the fire detection alarms for the systems required by paragraph
5.2 centralized in a continuously manned central control station.
In addition, controls for remote closing of the fire doors and shutting
down the ventilation fans shall be centralized in the same location.
The ventilation fans shall be capable of reactivation by the crew
at the continuously manned control station. The control panels in
the central control station shall be capable of indicating open or
closed positions of fire doors and closed or off status of the detectors,
alarms and fans. The control panel shall be continuously powered and
shall have an automatic change-over to standby power supply in case
of loss of normal power supply. The control panel shall be powered
from the main source of electrical power and the emergency source
of electrical power defined by regulation
II-1/42 unless other arrangements are permitted by the regulations,
as applicable.
9.4 A special alarm, operated from the navigation
bridge or fire control station, shall be fitted to summon the crew.
This alarm may be part of the ship’s general alarm system and
shall be capable of being sounded independently of the alarm to the
passenger spaces.
Regulation 8 – Control
of smoke spread
1 Purpose
The purpose of this regulation is to control the spread
of smoke in order to minimize the hazards from smoke. For this purpose,
means for controlling smoke in atriums, control stations, machinery
spaces and concealed spaces shall be provided.
2 Protection of control stations outside
machinery spaces
Practicable measures shall be taken for control stations
outside machinery spaces in order to ensure that ventilation, visibility
and freedom from smoke are maintained so that, in the event of fire,
the machinery and equipment contained therein may be supervised and
continue to function effectively. Alternative and separate means of
air supply shall be provided and air inlets of the two sources of
supply shall be so disposed that the risk of both inlets drawing in
smoke simultaneously is minimized. At the discretion of the Administration,
such requirements need not apply to control stations situated on,
and opening on to, an open deck or where local closing arrangements
would be equally effective.
3 Release of smoke from machinery spaces
3.1 The provisions of this paragraph shall apply
to machinery spaces of category A and, where the Administration considers
desirable, to other machinery spaces.
3.2 Suitable arrangements shall be made to permit
the release of smoke, in the event of fire, from the space to be protected,
subject to the provisions of regulation 9.5.2.1 The normal ventilation
systems may be acceptable for this purpose.
3.3 Means of control shall be provided for permitting
the release of smoke and such controls shall be located outside the
space concerned so that, in the event of fire, they will not be cut
off from the space they serve.
3.4 In passenger ships, the controls required
by paragraph 3.3 shall be situated at one control position or grouped
in as few positions as possible to the satisfaction of the Administration.
Such positions shall have a safe access from the open deck.
4 Draught stops
Air spaces enclosed behind ceilings, panelling or linings
shall be divided by close-fitting draught stops spaced not more than
14 m apart. In the vertical direction, such enclosed air spaces, including
those behind linings of stairways, trunks, etc., shall be closed at
each deck.
5 Smoke extraction systems in atriums
of passenger ships
Atriums shall be equipped with a smoke extraction system.
The smoke extraction system shall be activated by the required smoke
detection system and be capable of manual control. The fans shall
be sized such that the entire volume within space can be exhausted
in 10 min or less.
Regulation 9 – Containment
of fire
1 Purpose
The purpose of this regulation is to contain a fire in the
space of origin. For this purpose, the following functional requirements
shall be met:
-
.1 the ship shall be subdivided by thermal and
structural boundaries;
-
.2 thermal insulation of boundaries shall have
due regard to the fire risk of the space and adjacent spaces; and
-
.3 the fire integrity of the divisions shall be
maintained at openings and penetrations.
2 Thermal and structural boundaries
2.1
Thermal and structural subdivision
Ships of all types shall be subdivided into spaces by thermal
and structural divisions having regard to the fire risks of the space.
2.2
Passenger ships
2.2.1
Main vertical zones and horizontal
zones
2.2.1.1.1 In ships carrying more than 36 passengers,
the hull, superstructure and deckhouses shall be subdivided into main
vertical zones by "A-60" class divisions. Steps and recesses shall
be kept to a minimum, but where they are necessary they shall also
be "A-60" class divisions. Where a category (5), (9) or (10) space
defined in paragraph 2.2.3.2.2 is on one side or where fuel oil tanks
are on both sides of the division the standard may be reduced to "A-0".
2.2.1.1.2 In ships carrying not more than 36 passengers,
the hull, superstructure and deckhouses in way of accommodation and
service spaces shall be subdivided into main vertical zones by "A"
class divisions. These divisions shall have insulation values in accordance
with tables in paragraph 2.2.4.
2.2.1.2 As far as practicable, the bulkheads forming
the boundaries of the main vertical zones above the bulkhead deck
shall be in line with watertight subdivision bulkheads situated immediately
below the bulkhead deck. The length and width of main vertical zones
may be extended to a maximum of 48 m in order to bring the ends of
main vertical zones to coincide with watertight subdivision bulkheads
or in order to accommodate a large public space extending for the
whole length of the main vertical zone provided that the total area
of the main vertical zone is not greater than 1,600 m2 on
any deck. The length or width of a main vertical zone is the maximum
distance between the furthermost points of the bulkheads bounding
it.
2.2.1.3 Such bulkheads shall extend from deck
to deck and to the shell or other boundaries.
2.2.1.4 Where a main vertical zone is subdivided
by horizontal "A" class divisions into horizontal zones for the purpose
of providing an appropriate barrier between a zone with sprinklers
and a zone without sprinklers, the divisions shall extend between
adjacent main vertical zone bulkheads and to the shell or exterior
boundaries of the ship and shall be insulated in accordance with the
fire insulation and integrity values given in table 9.4.
2.2.1.5.1 On ships designed for special purposes,
such as automobile or railroad car ferries, where the provision of
main vertical zone bulkheads would defeat the purpose for which the
ship is intended, equivalent means for controlling and limiting a
fire shall be substituted and specifically approved by the Administration.
Service spaces and ship stores shall not be located on ro-ro decks
unless protected in accordance with the applicable regulations.
2.2.1.5.2 However, in a ship with special category
spaces, such spaces shall comply with the applicable provisions of
regulation 20 and where such compliance would be inconsistent with
other requirements for passenger ships specified in this chapter,
the requirements of regulation 20 shall prevail.
2.2.2
Bulkheads within a main vertical zone
2.2.2.1 For ships carrying more than 36 passengers,
bulkheads which are not required to be "A" class divisions shall be
at least "B" class or "C" class divisions as prescribed in the tables
in paragraph 2.2.3.
2.2.2.2 For ships carrying not more than 36 passengers,
bulkheads within accommodation and service spaces which are not required
to be "A" class divisions shall be at least "B" class or "C" class
divisions as prescribed in the tables in paragraph 2.2.4. In addition,
corridor bulkheads, where not required to be "A" class, shall be "B"
class divisions which shall extend from deck to deck except:
-
.1 when continuous "B" class ceilings or linings
are fitted on both sides of the bulkhead, the portion of the bulkhead
behind the continuous ceiling or lining shall be of material which,
in thickness and composition, is acceptable in the construction of
"B" class divisions, but which shall be required to meet "B" class
integrity standards only in so far as is reasonable and practicable
in the opinion of the Administration; and
-
.2 in the case of a ship protected by an automatic
sprinkler system complying with the provisions of the Fire
Safety Systems Code, the corridor bulkheads may terminate at
a ceiling in the corridor provided such bulkheads and ceilings are
of “B” class standard in compliance with paragraph 2.2.4.
All doors and frames in such bulkheads shall be of non-combustible
materials and shall have the same fire integrity as the bulkhead in
which they are fitted.
2.2.2.3 Bulkheads required to be "B" class divisions,
except corridor bulkheads as prescribed in paragraph 2.2.2.2, shall
extend from deck to deck and to the shell or other boundaries. However,
where a continuous "B" class ceiling or lining is fitted on both sides
of a bulkhead which is at least of the same fire resistance as the
adjoining bulkhead, the bulkhead may terminate at the continuous ceiling
or lining.
2.2.3
Fire integrity of bulkheads and decks
in ships carrying more than 36 passengers
2.2.3.1 In addition to complying with the specific
provisions for fire integrity of bulkheads and decks of passenger
ships, the minimum fire integrity of all bulkheads and decks shall
be as prescribed in tables 9.1 and 9.2. Where, due to any particular
structural arrangements in the ship, difficulty is experienced in
determining from the tables the minimum fire integrity value of any
divisions, such values shall be determined to the satisfaction of
the Administration.
2.2.3.2 The following requirements shall govern
application of the tables:
-
.1 Table 9.1 shall apply to bulkheads not bounding
either main vertical zones or horizontal zones. Table 9.2 shall apply
to decks not forming steps in main vertical zones nor bounding horizontal
zones;
-
.2 For determining the appropriate fire integrity
standards to be applied to boundaries between adjacent spaces, such
spaces are classified according to their fire risk as shown in categories
(1) to (14) below. Where the contents and use of a space are such
that there is a doubt as to its classification for the purpose of
this regulation, or where it is possible to assign two or more classifications
to a space, it shall be treated as a space within the relevant category
having the most stringent boundary requirements. Smaller, enclosed
rooms within a space that have less than 30% communicating openings
to that space are considered separate spaces. The fire integrity of
the boundary bulkheads and decks of such smaller rooms shall be as
prescribed in tables 9.1 and 9.2. The title of each category is intended
to be typical rather than restrictive. The number in parentheses preceding
each category refers to the applicable column or row in the tables.
-
(1)
Control stations
Spaces
containing emergency sources of power and lighting. Wheelhouse
and chartroom. Spaces containing the ship’s radio
equipment. Fire control stations Control
room for propulsion machinery when located outside the propulsion
machinery space. Spaces containing centralized fire
alarm equipment. Spaces containing centralized emergency
public address system stations and equipment.
-
(2)
Stairways
Interior
stairways, lifts, totally enclosed emergency escape trunks, and escalators
(other than those wholly contained within the machinery spaces) for
passengers and crew and enclosures thereto. In this
connection a stairway which is enclosed at only one level shall be
regarded as part of the space from which it is not separated by a
fire door.
-
(3)
Corridors
Passenger
and crew corridors and lobbies.
-
(4)
Evacuation stations and external escape
routes
Survival craft stowage area. Open
deck spaces and enclosed promenades forming lifeboat and liferaft
embarkation and lowering stations. Assembly stations,
internal and external. External stairs and open decks
used for escape routes. The ship’s side to the
waterline in the lightest seagoing condition, superstructure and deckhouse
sides situated below and adjacent to the liferaft and evacuation slide
embarkation areas.
-
(5)
Open deck spaces
Open
deck spaces and enclosed promenades clear of lifeboat and liferaft
embarkation and lowering stations. To be considered in this category,
enclosed promenades shall have no significant fire risk, meaning that
furnishings shall be restricted to deck furniture. In addition, such
spaces shall be naturally ventilated by permanent openings. Air
spaces (the space outside superstructures and deckhouses).
-
(6)
Accommodation spaces of minor fire risk
Cabins containing furniture and furnishings of restricted
fire risk. Offices and dispensaries containing furniture
and furnishings of restricted fire risk. Public spaces
containing furniture and furnishings of restricted fire risk and having
a deck area of less than 50 m2.
-
(7)
Accommodation spaces of moderate fire
risk
Spaces as in category (6) above but containing
furniture and furnishings of other than restricted fire risk. Public
spaces containing furniture and furnishings of restricted fire risk
and having a deck area of 50 m2 or more. Isolated
lockers and small store-rooms in accommodation spaces having areas
less than 4 m2 (in which flammable liquids are not stowed). Sale shops. Motion picture projection and film stowage rooms.
Diet kitchens (containing no open flame). Cleaning gear
lockers (in which flammable liquids are not stowed). Laboratories
(in which flammable liquids are not stowed). Pharmacies. Small drying rooms (having a deck area of 4 m2 or
less). Specie rooms. Operating rooms.
-
(8)
Accommodation spaces of greater fire
risk
Public spaces containing furniture and furnishings
of other than restricted fire risk and having a deck area of 50 m2 or
more. Barber shops and beauty parlours. Saunas.
-
(9)
Sanitary and similar spaces
Communal sanitary facilities, showers, baths, water closets,
etc. Small laundry rooms. Indoor swimming
pool area. Isolated pantries containing no cooking appliances
in accommodation spaces. Private sanitary facilities
shall be considered a portion of the space in which they are located.
-
(10)
Tanks, voids and auxiliary machinery
spaces having little or no fire risk
Water tanks
forming part of the ship’s structure. Voids and
cofferdams. Auxiliary machinery spaces which do not
contain machinery having a pressure lubrication system and where storage
of combustibles is prohibited, such as:
-
ventilation and air-conditioning rooms;
-
windlass room;
-
steering gear room;
-
stabilizer equipment room;
-
electrical propulsion motor room; rooms containing
section switchboards and purely electrical equipment other than oil-filled
electrical transformers (above 10 kVA); shaft alleys
and pipe tunnels; spaces for pumps and refrigeration
machinery (not handling or using flammable liquids).
-
Closed trunks serving the spaces listed above. Other
closed trunks such as pipe and cable trunks.
-
(11)
Auxiliary machinery spaces, cargo spaces,
cargo and other oil tanks and other similar spaces of moderate fire
risk
Cargo oil tanks. Cargo holds,
trunkways and hatchways. Refrigerated chambers. Oil
fuel tanks (where installed in a separate space with no machinery). Shaft alleys and pipe tunnels allowing storage of combustibles. Auxiliary machinery spaces as in category (10) which contain
machinery having a pressure lubrication system or where storage of
combustibles is permitted. Oil fuel filling stations. Spaces containing oil-filled electrical transformers (above
10 kVA). Spaces containing turbine and reciprocating
steam engine driven auxiliary generators and small internal combustion
engines of power output up to 110 kW driving generators, sprinkler,
drencher or fire pumps, bilge pumps, etc. Closed trunks
serving the spaces listed above.
-
(12)
Machinery spaces and main galleys
Main propulsion machinery rooms (other than electric propulsion
motor rooms) and boiler rooms. Auxiliary machinery spaces
other than those in categories (10) and (11) which contain internal
combustion machinery or other oil-burning, heating or pumping units. Main galleys and annexes. Trunks and casings
to the spaces listed above.
-
(13)
Store-rooms, workshops, pantries, etc.
Main pantries not annexed to galleys. Main
laundry. Large drying rooms (having a deck area of more
than 4 m2) Miscellaneous stores. Mail
and baggage rooms. Garbage rooms. Workshops
(not part of machinery spaces, galleys, etc.). Lockers
and store-rooms having areas greater than 4 m2, other than
those spaces that have provisions for the storage of flammable liquids.
-
(14)
Other spaces in which flammable liquids
are stowed
Paint lockers. Store-rooms
containing flammable liquids (including dyes, medicines, etc.). Laboratories
(in which flammable liquids are stowed);
-
.3 Where a single value is shown for the fire
integrity of a boundary between two spaces, that value shall apply
in all cases;
-
.4 Notwithstanding the provisions of paragraph
2.2.2 there are no special requirements for material or integrity
of boundaries where only a dash appears in the tables; and
-
.5 The Administration shall determine in respect
of category (5) spaces whether the insulation values in table 9.1
shall apply to ends of deckhouses and superstructures, and whether
the insulation values in table 9.2 shall apply to weather decks. In
no case shall the requirements of category (5) of tables 9.1 or 9.2
necessitate enclosure of spaces which in the opinion of the Administration
need not be enclosed.
Table 9.1 Bulkheads
not bounding either main vertical zones or horizontal zones
Spaces
|
(1)
|
(2)
|
(3)
|
(4)
|
(5)
|
(6)
|
(7)
|
(8)
|
(9)
|
(10)
|
(11)
|
(12)
|
(13)
|
(14)
|
Control stations
|
(1)
|
B-0a
|
A-0
|
A-0
|
A-0
|
A-0
|
A-60
|
A-60
|
A-60
|
A-0
|
A-0
|
A-60
|
A-60
|
A-60
|
A-60
|
Stairways
|
(2)
|
|
A-0a
|
A-0
|
A-0
|
A-0
|
A-0
|
A-15
|
A-15
|
A-0c
|
A-0
|
A-15
|
A-30
|
A-15
|
A-30
|
Corridors
|
(3)
|
|
|
B-15
|
A-60
|
A-0
|
B-15
|
B-15
|
B-15
|
B-15
|
A-0
|
A-15
|
A-30
|
A-0
|
A-30
|
Evacuation stations and external
escape routes
|
(4)
|
|
|
|
|
A-0
|
A-60b,d
|
A-60b,d
|
A-60b,d
|
A-0d
|
A-0
|
A-60b
|
A-60b
|
A-60b
|
A-60b
|
Open deck spaces
|
(5)
|
|
|
|
|
|
|
A-0
|
A-0
|
A-0
|
A-0
|
A-0
|
A-0
|
A-0
|
A-0
|
Accommodation spaces of minor fire risk
|
(6)
|
|
|
|
|
|
|
B-0
|
B-0
|
C
|
A-0
|
A-0
|
A-30
|
A-0
|
A-30
|
Accommodation spaces of moderate fire risk
|
(7)
|
|
|
|
|
|
|
B-0
|
B-0
|
C
|
A-0
|
A-15
|
A-60
|
A-15
|
A-60
|
Accommodation spaces of greater fire risk
|
(8)
|
|
|
|
|
|
|
|
B-0
|
C
|
A-0
|
A-30
|
A-60
|
A-0
|
A-60
|
Sanitary and similar spaces
|
(9)
|
|
|
|
|
|
|
|
|
C
|
A-0
|
A-0
|
A-0
|
A-0
|
A-0
|
Tanks, voids and auxiliary machinery spaces having
little or no fire risk
|
(10)
|
|
|
|
|
|
|
|
|
|
A-0a
|
A-0
|
A-0
|
A-0
|
A-0
|
Auxiliary machinery spaces, cargo spaces, cargo and
other oil tanks and other similar spaces of moderate fire
risk
|
(11)
|
|
|
|
|
|
|
|
|
|
|
A-0a
|
A-0
|
A-0
|
A-15
|
Machinery spaces and main galleys
|
(12)
|
|
|
|
|
|
|
|
|
|
|
|
A-0a
|
A-0
|
A-60
|
Store-rooms, workshops, pantries, etc.
|
(13)
|
|
|
|
|
|
|
|
|
|
|
|
|
A-0a
|
A-0
|
Other spaces in which flammable liquids are
stowed
|
(14)
|
|
|
|
|
|
|
|
|
|
|
|
|
|
A-30
|
See notes following table 9.2
|
Table 9.2 Decks not
forming steps in main vertical zones nor bounding horizontal
zones
Space below?
|
Space above?
|
(1)
|
(2)
|
(3)
|
(4)
|
(5)
|
(6)
|
(7)
|
(8)
|
(9)
|
(10)
|
(11)
|
(12)
|
(13)
|
(14)
|
Control stations
|
(1)
|
A-30
|
A-30
|
A-15
|
A-0
|
A-0
|
A-0
|
A-15
|
A-30
|
A-0
|
A-0
|
A-0
|
A-60
|
A-0
|
A-60
|
Stairways
|
(2)
|
A-0
|
A-0
|
A-0
|
A-0
|
A-0
|
A-0
|
A-0
|
A-0
|
A-0
|
A-0
|
A-0
|
A-30
|
A-0
|
A-30
|
Corridors
|
(3)
|
A-15
|
A-0
|
A-0a
|
A-60
|
A-0
|
A-0
|
A-15
|
A-15
|
A-0
|
A-0
|
A-0
|
A-30
|
A-0
|
A-30
|
Evacuation stations and external escape
routes
|
(4)
|
A-0
|
A-0
|
A-0
|
A-0
|
–
|
A-0
|
A-0
|
A-0
|
A-0
|
A-0
|
A-0
|
A-0
|
A-0
|
A-0
|
Open deck spaces
|
(5)
|
A-0
|
A-0
|
A-0
|
A-0
|
–
|
A-0
|
A-0
|
A-0
|
A-0
|
A-0
|
A-0
|
A-0
|
A-0
|
A-0
|
Accommodation spaces of minor fire risk
|
(6)
|
A-60
|
A-15
|
A-0
|
A-60
|
A-0
|
A-0
|
A-0
|
A-0
|
A-0
|
A-0
|
A-0
|
A-0
|
A-0
|
A-0
|
Accommodation spaces of moderate fire risk
|
(7)
|
A-60
|
A-15
|
A-15
|
A-60
|
A-0
|
A-0
|
A-15
|
A-15
|
A-0
|
A-0
|
A-0
|
A-0
|
A-0
|
A-0
|
Accommodation spaces of greater fire risk
|
(8)
|
A-60
|
A-15
|
A-15
|
A-60
|
A-0
|
A-15
|
A-15
|
A-30
|
A-0
|
A-0
|
A-0
|
A-0
|
A-0
|
A-0
|
Sanitary and similar spaces
|
(9)
|
A-0
|
A-0
|
A-0
|
A-0
|
A-0
|
A-0
|
A-0
|
A-0
|
A-0
|
A-0
|
A-0
|
A-0
|
A-0
|
A-0
|
Tanks, voids and auxiliary machinery spaces having
little or no fire risk
|
(10)
|
A-0
|
A-0
|
A-0
|
A-0
|
A-0
|
A-0
|
A-0
|
A-0
|
A-0
|
A-0a
|
A-0
|
A-0
|
A-0
|
A-0
|
Auxiliary machinery spaces, cargo spaces, cargo and
other oil tanks and other similar spaces of moderate fire
risk
|
(11)
|
A-60
|
A-60
|
A-60
|
A-60
|
A-0
|
A-0
|
A-15
|
A-30
|
A-0
|
A-0
|
A-0a
|
A-0
|
A-0
|
A-30
|
Machinery spaces and main galleys
|
(12)
|
A-60
|
A-60
|
A-60
|
A-60
|
A-0
|
A-60
|
A-60
|
A-60
|
A-0
|
A-0
|
A-30
|
A-30a
|
A-0
|
A-60
|
Store-rooms, workshops, pantries, etc.
|
(13)
|
A-60
|
A-30
|
A-15
|
A-60
|
A-0
|
A-15
|
A-30
|
A-30
|
A-0
|
A-0
|
A-0
|
A-0
|
A-0
|
A-0
|
Other spaces in which flammable liquids are
stowed
|
(14)
|
A-60
|
A-60
|
A-60
|
A-60
|
A-0
|
A-30
|
A-60
|
A-60
|
A-0
|
A-0
|
A-0
|
A-0
|
A-0
|
A-0
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Note: To be applied to tables 9.1 and 9.2
|
a
|
Where adjacent spaces are in the same
numerical category and superscript "a" appears, a bulkhead or
deck between such spaces need not be fitted if deemed
unnecessary by the Administration. For example, in category (12)
a bulkhead need not be required between a galley and its annexed
pantries provided the pantry bulkhead and decks maintain the
integrity of the galley boundaries. A bulkhead is, however,
required between a galley and machinery space even though both
spaces are in category (12).
|
b
|
The ship’s side, to the waterline in the
lightest seagoing condition, superstructure and deckhouse sides
situated below and adjacent to liferafts and evacuation slides
may be reduced to "A-30".
|
c
|
Where public toilets are installed
completely within the stairway enclosure, the public toilet
bulkhead within the stairway enclosure can be of "B" class
integrity.
|
d
|
Where spaces of categories (6), (7), (8)
and (9) are located completely within the outer perimeter of the
assembly station, the bulkheads of these spaces are allowed to
be of "B-0" class integrity. Control positions for audio, video
and light installations may be considered as part of the
assembly station.
|
2.2.3.3 Continuous "B" class ceilings or linings,
in association with the relevant decks or bulkheads, may be accepted
as contributing wholly or in part, to the required insulation and
integrity of a division.
2.2.3.4
Construction and arrangement of saunas
2.2.3.4.1 The perimeter of the sauna shall be
of "A" class boundaries and may include changing rooms, showers and
toilets. The sauna shall be insulated to A-60 standard against other
spaces except those inside of the perimeter and spaces of categories
(5), (9) and (10).
2.2.3.4.2 Bathrooms with direct access to saunas
may be considered as part of them. In such cases, the door between
sauna and the bathroom need not comply with fire safety requirements.
2.2.3.4.3 The traditional wooden lining on the
bulkheads and ceiling are permitted in the sauna. The ceiling above
the oven shall be lined with a non-combustible plate with an air gap
of at least 30 mm. The distance from the hot surfaces to combustible
materials shall be at least 500 mm or the combustible materials shall
be protected (e.g. non-combustible plate with an air gap of at least
30 mm).
2.2.3.4.4 The traditional wooden benches are permitted
to be used in the sauna.
2.2.3.4.5 The sauna door shall open outwards by
pushing.
2.2.3.4.6 Electrically heated ovens shall be provided
with a timer.
2.2.4
Fire integrity of bulkheads and decks
in ships carrying not more than 36 passengers
2.2.4.1 In addition to complying with the specific
provisions for fire integrity of bulkheads and decks of passenger
ships, the minimum fire integrity of bulkheads and decks shall be
as prescribed in tables 9.3 and 9.4.
2.2.4.2 The following requirements govern application
of the tables:
-
.1 Tables 9.3 and 9.4 shall apply respectively
to the bulkheads and decks separating adjacent spaces;
-
.2 For determining the appropriate fire integrity
standards to be applied to divisions between adjacent spaces, such
spaces are classified according to their fire risk as shown in categories
(1) to (11) below. Where the contents and use of a space are such
that there is a doubt as to its classification for the purpose of
this regulation, or where it is possible to assign two or more classifications
to a space, it shall be treated as a space within the relevant category
having the most stringent boundary requirements. Smaller, enclosed
rooms within a space that have less than 30 % communicating openings
to that space are considered separate spaces. The fire integrity of
the boundary bulkheads and decks of such smaller rooms shall be as
prescribed in tables 9.3 and 9.4. The title of each category is intended
to be typical rather than restrictive. The number in parentheses preceding
each category refers to the applicable column or row in the tables.
-
(1)
Control stations
Spaces
containing emergency sources of power and lighting. Wheelhouse
and chartroom. Spaces containing the ship’s radio
equipment. Fire control stations. Control
room for propulsion machinery when located outside the machinery space. Spaces containing centralized fire alarm equipment.
-
(2)
Corridors
Passenger
and crew corridors and lobbies.
-
(3)
Accommodation spaces
Spaces
as defined in regulation 3.1 excluding corridors.
-
(4)
Stairways
Interior
stairways, lifts, totally enclosed emergency escape trunks, and escalators
(other than those wholly contained within the machinery spaces) and
enclosures thereto. In this connection, a stairway which
is enclosed only at one level shall be regarded as part of the space
from which it is not separated by a fire door.
-
(5)
Service spaces (low risk)
Lockers
and store-rooms not having provisions for the storage of flammable
liquids and having areas less than 4 m2 and drying rooms
and laundries.
-
(6)
Machinery spaces of category A
Spaces as defined in regulation 3.31.
-
(7)
Other machinery spaces
Electrical
equipment rooms (auto-telephone exchange, air-conditioning duct spaces). Spaces as defined in regulation 3.30 excluding machinery
spaces of category A.
-
(8)
Cargo spaces
All
spaces used for cargo (including cargo oil tanks) and trunkways and
hatchways to such spaces, other than special category spaces.
-
(9)
Service spaces (high risk)
Galleys,
pantries containing cooking appliances, paint and lamp rooms, lockers
and store-rooms having areas of 4 m2 or more, spaces for
the storage of flammable liquids, saunas and workshops other than
those forming part of the machinery spaces.
-
(10)
Open decks
Open
deck spaces and enclosed promenades having little or no fire risk.
Enclosed promenades should have no significant fire risk, meaning
that furnishing should be restricted to deck furniture. In addition,
such spaces should be naturally ventilated by permanent openings.
Air spaces (the space outside superstructures and deckhouses).
-
(11)
Special category and ro-ro spaces
Spaces as defined in regulations 3.41 and 3.46;
-
.3 In determining the applicable fire integrity
standard of a boundary between two spaces within a main vertical zone
or horizontal zone which is not protected by an automatic sprinkler
system complying with the provisions of the Fire Safety
Systems Code or between such zones neither of which is so protected,
the higher of the two values given in the tables shall apply; and
-
.4 In determining the applicable fire integrity
standard of a boundary between two spaces within a main vertical zone
or horizontal zone which is protected by an automatic sprinkler system
complying with the provisions of the Fire Safety Systems
Code or between such zones both of which are so protected,
the lesser of the two values given in the tables shall apply. Where
a zone with sprinklers and a zone without sprinklers meet within accommodation
and service spaces, the higher of the two values given in the tables
shall apply to the division between the zones.
2.2.4.3 Continuous "B" class ceilings or linings,
in association with the relevant decks or bulkheads, may be accepted
as contributing, wholly or in part, to the required insulation and
integrity of a division.
2.2.4.4 External boundaries which are required
in regulation 11.2 to be of steel or other equivalent material may
be pierced for the fitting of windows and sidescuttles provided that
there is no requirement for such boundaries of passenger ships to
have "A" class integrity. Similarly, in such boundaries which are
not required to have "A" class integrity, doors may be constructed
of materials which are to the satisfaction of the Administration.
2.2.4.5 Saunas shall comply with paragraph 2.2.3.4.
Table 9.3 Fire
integrity of bulkheads separating adjacent spaces
Spaces
|
(1)
|
(2)
|
(3)
|
(4)
|
(5)
|
(6)
|
(7)
|
(8)
|
(9)
|
(10)
|
(11)
|
Control stations
|
(1)
|
A-0c
|
A-0
|
A-60
|
A-0
|
A-15
|
A-60
|
A-15
|
A-60
|
A-60
|
*
|
A-60
|
Corridors
|
(2)
|
|
Ce
|
B-0e
|
A-0a
|
B-0e
|
A-60
|
A-0
|
A-0
|
A-15
|
*
|
A-15
|
B-0e
|
A-0d
|
Accommodation spaces
|
(3)
|
|
|
Ce
|
A-0a
|
B-0e
|
A-60
|
A-0
|
A-0
|
A-15
|
*
|
A-30
|
B-0e
|
A-0d
|
A-0d
|
Stairways
|
(4)
|
|
|
|
A-0a
|
A-0a
|
A-60
|
A-0
|
A-0
|
A-15
|
*
|
A-15
|
B-0e
|
B-0e
|
A-0d
|
Service spaces (low risk)
|
(5)
|
|
|
|
|
Ce
|
A-60
|
A-0
|
A-0
|
A-0
|
*
|
A-0
|
Machinery spaces of category A
|
(6)
|
|
|
|
|
|
*
|
A-0
|
A-0
|
A-60
|
*
|
A-60
|
Other machinery spaces
|
(7)
|
|
|
|
|
|
|
A-0b
|
A-0
|
A-0
|
*
|
A-0
|
Cargo spaces
|
(8)
|
|
|
|
|
|
|
|
*
|
A-0
|
*
|
A-0
|
Service spaces (high risk)
|
(9)
|
|
|
|
|
|
|
|
|
A-0b
|
*
|
A-30
|
Open decks
|
(10)
|
|
|
|
|
|
|
|
|
|
|
A-0
|
Special category and ro-ro spaces
|
(11)
|
|
|
|
|
|
|
|
|
|
|
A-0
|
Table 9.4 Fire
integrity of decks seperating adjacent spaces
Space below
|
Space above
|
(1)
|
(2)
|
(3)
|
(4)
|
(5)
|
(6)
|
(7)
|
(8)
|
(9)
|
(10)
|
(11)
|
Control stations
|
(1)
|
A-0
|
A-0
|
A-0
|
A-0
|
A-0
|
A-60
|
A-0
|
A-0
|
A-0
|
*
|
A-30
|
Corridors
|
(2)
|
A-0
|
*
|
*
|
A-0
|
*
|
A-60
|
A-0
|
A-0
|
A-0
|
*
|
A-30
|
Accommodation spaces
|
(3)
|
A-60
|
A-0
|
*
|
A-0
|
*
|
A-60
|
A-0
|
A-0
|
A-0
|
*
|
A-30
|
A-0d
|
Stairways
|
(4)
|
A-0
|
A-0
|
A-0
|
*
|
A-0
|
A-60
|
A-0
|
A-0
|
A-0
|
*
|
A-0
|
Service spaces (low risk)
|
(5)
|
A-15
|
A-0
|
A-0
|
A-0
|
*
|
A-60
|
A-0
|
A-0
|
A-0
|
*
|
A-0
|
Machinery spaces of category A
|
(6)
|
A-60
|
A-60
|
A-60
|
A-60
|
A-60
|
*
|
A-60f
|
A-30
|
A-60
|
*
|
A-60
|
Other machinery spaces
|
(7)
|
A-15
|
A-0
|
A-0
|
A-0
|
A-0
|
A-0
|
*
|
A-0
|
A-0
|
*
|
A-0
|
Cargo spaces
|
(8)
|
A-60
|
A-0
|
A-0
|
A-0
|
A-0
|
A-0
|
A-0
|
*
|
A-0
|
*
|
A-0
|
Service spaces (high risk)
|
(9)
|
A-60
|
A-30
|
A-30
|
A-30
|
A-0
|
A-60
|
A-0
|
A-0
|
A-0
|
*
|
A-30
|
A-0d
|
A-0d
|
A-0d
|
Open decks
|
(10)
|
*
|
*
|
*
|
*
|
*
|
*
|
*
|
*
|
*
|
–
|
A-0
|
Special category and ro-ro spaces
|
(11)
|
A-60
|
A-15
|
A-30
|
A-15
|
A-0
|
A-30
|
A-0
|
A-0
|
A-30
|
A-0
|
A-0
|
A-0d
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Notes:
|
To be applied to both tables 9.3 and 9.4
as appropriate
|
a
|
For clarification as to which applies, see
paragraphs 2.2.2 and 2.2.5.
|
b
|
Where spaces are of the same numerical
category and superscript b appears, a bulkhead or deck of the
rating shown in the tables is only required when the adjacent
spaces are for a different purpose, (e.g. in category (9)). A
galley next to a galley does not require a bulkhead but a galley
next to a paint room requires an "A-0" bulkhead.
|
c
|
Bulkhead separating the wheelhouse and
chartroom from each other may have a "B-0" rating.
|
d
|
See paragraphs 2.2.4.2.3 and
2.2.4.2.4.
|
e
|
For the application of paragraph
2.2.1.1.2, "B-0" and "C", where appearing in table 9.3, shall be
read as "A-0".
|
f
|
Fire insulation need not be fitted if the
machinery space in category (7), in the opinion of the
Administration, has little or no fire risk.
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
*
|
Where an asterisk appears in the tables,
the division is required to be of steel or other equivalent
material, but is not required to be of "A" class standard.
However, where a deck, except in a category (10) space, is
penetrated for the passage of electric cables, pipes and vent
ducts, such penetrations should be made tight to prevent the
passage of flame and smoke. Divisions between control stations
(emergency generators) and open decks may have air intake
openings without means for closure, unless a fixed gas
fire-fighting system is fitted.
|
|
For the application of paragraph
2.2.1.1.2, an asterisk, where appearing in table 9.4, except for
categories (8) and (10), shall be read as “A-0”.
|
2.2.5
Protection of stairways and
lifts in accommodation area
2.2.5.1 Stairways shall be within enclosures formed
of "A" class divisions, with positive means of closure at all openings,
except that:
-
.1 a stairway connecting only two decks need not
be enclosed, provided the integrity of the deck is maintained by proper
bulkheads or self-closing doors in one 'tween-deck space. When a stairway
is closed in one 'tween-deck space, the stairway enclosure shall be
protected in accordance with the tables for decks in paragraphs 2.2.3
or 2.2.4; and
-
.2 stairways may be fitted in the open in a public
space, provided they lie wholly within the public space.
2.2.5.2 Lift trunks shall be so fitted as to prevent
the passage of smoke and flame from one ‘tween-deck to another
and shall be provided with means of closing so as to permit the control
of draught and smoke. Machinery for lifts located within stairway
enclosures shall be arranged in a separate room, surrounded by steel
boundaries, except that small passages for lift cables are permitted.
Lifts which open into spaces other than corridors, public spaces,
special category spaces, stairways and external areas shall not open
into stairways included in the means of escape.
2.3
Cargo ships except tankers
2.3.1
Methods of protection in accommodation
area
2.3.1.1 One of the following methods of protection
shall be adopted in accommodation and service spaces and control stations:
-
.1
Method IC
The construction
of internal divisional bulkheads of non-combustible "B" or "C" class
divisions generally without the installation of an automatic sprinkler,
fire detection and fire alarm system in the accommodation and service
spaces, except as required by regulation 7.5.5.1; or
-
.2
Method IIC
The fitting
of an automatic sprinkler, fire detection and fire alarm system as
required by regulation 7.5.5.2 for the detection and extinction of
fire in all spaces in which fire might be expected to originate, generally
with no restriction on the type of internal divisional bulkheads;
or
-
.3
Method IIIC
The
fitting of a fixed fire detection and fire alarm system as required
by regulation 7.5.5.3, in spaces in which a fire might be expected
to originate, generally with no restriction on the type of internal
divisional bulkheads, except that in no case must the area of any
accommodation space or spaces bounded by an "A" or "B" class division
exceed 50 m2. Consideration may be given by the Administration
to increasing this area for public spaces.
2.3.1.2 The requirements for the use of non-combustible
materials in the construction and insulation of boundary bulkheads
of machinery spaces, control stations, service spaces, etc., and the
protection of the above stairway enclosures and corridors will be
common to all three methods outlined in paragraph 2.3.1.1.
2.3.2
Bulkheads within accommodation area
2.3.2.1 Bulkheads required to be "B" class divisions
shall extend from deck to deck and to the shell or other boundaries.
However, where a continuous "B" class ceiling or lining is fitted
on both sides of the bulkhead, the bulkhead may terminate at the continuous
ceiling or lining.
Bulkheads not required by this or other regulations for
cargo ships to be "A" or "B" class divisions, shall be of at least
"C" class construction.
There shall be no restriction on the construction of bulkheads
not required by this or other regulations for cargo ships to be "A"
or "B" class divisions except in individual cases where "C" class
bulkheads are required in accordance with table 9.5.
There shall be no restriction on the construction of bulkheads
not required for cargo ships to be "A" or "B" class divisions except
that the area of any accommodation space or spaces bounded by a continuous
"A" or "B" class division must in no case exceed 50 m2,
except in individual cases where "C" class bulkheads are required
in accordance with table 9.5. Consideration may be given by the Administration
to increasing this area for public spaces.
2.3.3
Fire integrity of bulkheads and decks
2.3.3.1 In addition to complying with the specific
provisions for fire integrity of bulkheads and decks of cargo ships,
the minimum fire integrity of bulkheads and decks shall be as prescribed
in tables 9.5 and 9.6.
2.3.3.2 The following requirements shall govern
application of the tables:
-
.1 Tables 9.5 and 9.6 shall apply respectively
to the bulkheads and decks separating adjacent spaces;
-
.2 For determining the appropriate fire integrity
standards to be applied to divisions between adjacent spaces, such
spaces are classified according to their fire risk as shown in categories
(1) to (11) below. Where the contents and use of a space are such
that there is a doubt as to its classification for the purpose of
this regulation, or where it is possible to assign two or more classifications
to a space, it shall be treated as a space within the relevant category
having the most stringent boundary requirements. Smaller, enclosed
rooms within a space that have less than 30% communicating openings
to that space are considered separate spaces. The fire integrity of
the boundary bulkheads and decks of such smaller rooms shall be as
prescribed in tables 9.5 and 9.6. The title of each category is intended
to be typical rather than restrictive. The number in parentheses preceding
each category refers to the applicable column or row in the tables;
-
(1)
Control stations
Spaces
containing emergency sources of power and lighting. Wheelhouse
and chartroom. Spaces containing the ship’s radio
equipment. Fire control stations.
Control
room for propulsion machinery when located outside the machinery space. Spaces containing centralized fire alarm equipment.
-
(2)
Corridors
corridors
and lobbies.
-
(3)
Accommodation spaces
Spaces
as defined in regulation 3.1, excluding corridors.
-
(4)
Stairways
Interior
stairway, lifts, totally enclosed emergency escape trunks, and escalators
(other than those wholly contained within the machinery spaces) and
enclosures thereto. In this connection, a stairway which
is enclosed only at one level shall be regarded as part of the space
from which it is not separated by a fire door.
-
(5)
Service spaces (low risk)
Lockers
and store-rooms not having provisions for the storage of flammable
liquids and having areas less than 4 m2 and drying rooms
and laundries.
-
(6)
Machinery spaces of category A
Spaces as defined in regulation 3.31.
-
(7)
Other machinery spaces
Electrical
equipment rooms (auto-telephone exchange, air-conditioning duct spaces). Spaces as defined in regulation 3.30 excluding machinery
spaces of category A.
-
(8)
Cargo spaces
All
spaces used for cargo (including cargo oil tanks) and trunkways and
hatchways to such spaces.
-
(9)
Service spaces (high risk)
Galleys,
pantries containing cooking appliances, saunas, paint lockers and
store-rooms having areas of 4 m2 or more, spaces for the
storage of flammable liquids, and workshops other than those forming
part of the machinery spaces.
-
(10)
Open decks
Open
deck spaces and enclosed promenades having little or no fire risk.
To be considered in this category, enclosed promenades shall have
no significant fire risk, meaning that furnishings shall be restricted
to deck furniture. In addition, such spaces shall be naturally ventilated
by permanent openings. Air spaces (the space outside
superstructures and deckhouses).
-
(11)
Ro-ro and vehicle spaces
Ro-ro
spaces as defined in regulation 3.41. Vehicle spaces
as defined in regulation 3.49.
Table 9.5 Fire
integrity of bulkheads seperating adjacent spaces
Spaces
|
(1)
|
(2)
|
(3)
|
(4)
|
(5)
|
(6)
|
(7)
|
(8)
|
(9)
|
(10)
|
(11)
|
Control stations
|
(1)
|
A-0e
|
A-0
|
A-60
|
A-0
|
A-15
|
A-60
|
A-15
|
A-60
|
A-60
|
*
|
A-60
|
Corridors
|
(2)
|
|
C
|
B-0
|
B-0
|
B-0
|
A-60
|
A-0
|
A-0
|
A-0
|
*
|
A-30
|
A-0c
|
Accommodation spaces
|
(3)
|
|
|
Ca,b
|
B-0
|
B-0
|
A-60
|
A-0
|
A-0
|
A-0
|
*
|
A-30
|
A-0c
|
Stairways
|
(4)
|
|
|
|
B-0
|
B-0
|
A-60
|
A-0
|
A-0
|
A-0
|
*
|
A-30
|
A-0c
|
A-0c
|
Service spaces (low risk)
|
(5)
|
|
|
|
|
C
|
A-60
|
A-0
|
A-0
|
A-0
|
*
|
A-0
|
Machinery spaces of category A
|
(6)
|
|
|
|
|
|
*
|
A-0
|
A-0g
|
A-60
|
*
|
A-60f
|
Other machinery spaces
|
(7)
|
|
|
|
|
|
|
A-0d
|
A-0
|
A-0
|
*
|
A-0
|
Cargo spaces
|
(8)
|
|
|
|
|
|
|
|
*
|
A-0
|
*
|
A-0
|
Service spaces (high risk)
|
(9)
|
|
|
|
|
|
|
|
|
A-0d
|
*
|
A-30
|
Open decks
|
(10)
|
|
|
|
|
|
|
|
|
|
–
|
A-0
|
Ro-ro and vehicle spaces
|
(11)
|
|
|
|
|
|
|
|
|
|
|
*h
|
Table 9.6 Fire
integrity of decks seperating adjacent spaces
Space below
|
Space above
|
(1)
|
(2)
|
(3)
|
(4)
|
(5)
|
(6)
|
(7)
|
(8)
|
(9)
|
(10)
|
(11)
|
Control stations
|
(1)
|
A-0
|
A-0
|
A-0
|
A-0
|
A-0
|
A-60
|
A-0
|
A-0
|
A-0
|
*
|
A-60
|
Corridors
|
(2)
|
A-0
|
*
|
*
|
A-0
|
*
|
A-60
|
A-0
|
A-0
|
A-0
|
*
|
A-30
|
Accommodation spaces
|
(3)
|
A-60
|
A-0
|
*
|
A-0
|
*
|
A-60
|
A-0
|
A-0
|
A-0
|
*
|
A-30
|
Stairways
|
(4)
|
A-0
|
A-0
|
A-0
|
*
|
A-0
|
A-60
|
A-0
|
A-0
|
A-0
|
*
|
A-30
|
Service spaces (low risk)
|
(5)
|
A-15
|
A-0
|
A-0
|
A-0
|
*
|
A-60
|
A-0
|
A-0
|
A-0
|
*
|
A-0
|
Machinery spaces of category A
|
(6)
|
A-60
|
A-60
|
A-60
|
A-60
|
A-60
|
*
|
A-60i
|
A-30
|
A-60
|
*
|
A-60
|
Other machinery spaces
|
(7)
|
A-15
|
A-0
|
A-0
|
A-0
|
A-0
|
A-0
|
*
|
A-0
|
A-0
|
*
|
A-0
|
Cargo spaces
|
(8)
|
A-60
|
A-0
|
A-0
|
A-0
|
A-0
|
A-0
|
A-0
|
*
|
A-0
|
*
|
A-0
|
Service spaces (high risk)
|
(9)
|
A-60
|
A-0
|
A-0
|
A-0
|
A-0
|
A-60
|
A-0
|
A-0
|
A-0d
|
*
|
A-30
|
Open decks
|
(10)
|
*
|
*
|
*
|
*
|
*
|
*
|
*
|
*
|
*
|
-
|
*
|
Ro-ro and vehicle spaces
|
(11)
|
A-60
|
A-30
|
A-30
|
A-30
|
A-0
|
A-60
|
A-0
|
A-0
|
A-30
|
*
|
*h
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Note:
|
To be applied to tables 9.5 and 9.6 as
appropriate
|
a
|
No special requirements are imposed upon
bulkheads in methods IIC and IIIC fire protection.
|
b
|
In case of method IIIC "B" class bulkheads
of "B-0" rating shall be provided between spaces or groups of
spaces of 50 m2 and over in area.
|
c
|
For clarification as to which applies, see
paragraphs 2.3.2 and 2.3.4.
|
d
|
Where spaces are of the same numerical
category and superscript d appear, a bulkhead or deck of the
rating shown in the tables is only required when the adjacent
spaces are for a different purpose (e.g. in category (9)). A
galley next to a galley does not require a bulkhead but a galley
next to a paint room requires an "A-0" bulkhead.
|
e
|
Bulkheads separating the wheelhouse,
chartroom and radio room from each other may have a "B-0"
rating.
|
f
|
An "A-0" rating may be used if no
dangerous goods are intended to be carried or if such goods are
stowed not less than 3 m horizontally from such a
bulkhead.
|
g
|
For cargo spaces in which dangerous goods
are intended to be carried, regulation 19.3.8 applies.
|
h
|
Bulkheads and decks separating ro-ro
spaces shall be capable of being closed reasonably gastight and
such divisions shall have "A" class integrity in so far as
reasonable and practicable, if in the opinion of the
Administration it has little or no fire risk.
|
I
|
Fire insulation need not be fitted if the
machinery in category (7) if, in the opinion of the
Administration, it has little or no fire risk.
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
*
|
Where an asterisk appears in the tables,
the division is required to be of steel or other equivalent
material but is not required to be of "A" class standard.
However, where a deck, except an open deck, is penetrated for
the passage of electric cables, pipes and vent ducts, such
penetrations should be made tight to prevent the passage of
flame and smoke. Divisions between control stations (emergency
generators) and open decks may have air intake openings without
means for closure, unless a fixed gas fire-fighting system is
fitted.
|
2.3.3.3 Continuous "B" class ceilings or linings,
in association with the relevant decks or bulkheads, may be accepted
as contributing, wholly or in part, to the required insulation and
integrity of a division.
2.3.3.4 External boundaries which are required
in regulation 11.2 to be of steel or other equivalent material may
be pierced for the fitting of windows and sidescuttles provided that
there is no requirement for such boundaries of cargo ships to have
"A" class integrity. Similarly, in such boundaries which are not required
to have "A" class integrity, doors may be constructed of materials
which are to the satisfaction of the Administration.
2.3.3.5 Saunas shall comply with paragraph 2.2.3.4.
2.3.4
Protection of stairways and lift trunks
in accommodation spaces, service spaces and control stations
2.3.4.1 Stairways which penetrate only a single
deck shall be protected, at a minimum, at one level by at least "B-0"
class divisions and self-closing doors. Lifts which penetrate only
a single deck shall be surrounded by "A-0" class divisions with steel
doors at both levels. Stairways and lift trunks which penetrate more
than a single deck shall be surrounded by at least "A-0" class divisions
and be protected by self-closing doors at all levels.
2.3.4.2 On ships having accommodation for 12 persons
or less, where stairways penetrate more than a single deck and where
there are at least two escape routes direct to the open deck at every
accommodation level, the "A-0" requirements of paragraph 2.3.4.1 may
be reduced to "B-0".
2.4
Tankers
2.4.1
Application
For tankers, only method IC as defined in paragraph 2.3.1.1
shall be used.
2.4.2
Fire integrity of bulkheads and decks
2.4.2.1 In lieu of paragraph 2.3 and in addition
to complying with the specific provisions for fire integrity of bulkheads
and decks of tankers, the minimum fire integrity of bulkheads and
decks shall be as prescribed in tables 9.7 and 9.8.
2.4.2.2 The following requirements shall govern
application of the tables:
-
.1 Tables 9.7 and 9.8 shall apply respectively
to the bulkhead and decks separating adjacent spaces;
-
.2 For determining the appropriate fire integrity
standards to be applied to divisions between adjacent spaces, such
spaces are classified according to their fire risk as shown in categories
(1) to (10) below. Where the contents and use of a space are such
that there is a doubt as to its classification for the purpose of
this regulation, or where it is possible to assign two or more classifications
to a space, it shall be treated as a space within the relevant category
having the most stringent boundary requirements. Smaller, enclosed
areas within a space that have less than 30% communicating openings
to that space are considered separate areas. The fire integrity of
the boundary bulkheads and decks of such smaller spaces shall be as
prescribed in tables 9.7 and 9.8. The title of each category is intended
to be typical rather than restrictive. The number in parentheses preceding
each category refers to the applicable column or row in the tables;
-
(1)
Control stations
Spaces
containing emergency sources of power and lighting. Wheelhouse
and chartroom. Spaces containing the ship’s radio
equipment. Fire control stations.
Control
room for propulsion machinery when located outside the machinery space. Spaces containing centralized fire alarm equipment.
-
(2)
Corridors
Corridors
and lobbies.
-
(3)
Accommodation spaces
Spaces
as defined in regulation 3.1, excluding corridors.
-
(4)
Stairways
Interior
stairways, lifts, totally enclosed emergency escape trunks, and escalators
(other than those wholly contained within the machinery spaces) and
enclosures thereto. In this connection, a stairway which
is enclosed only at one level shall be regarded as part of the space
from which it is not separated by a fire door.
-
(5)
Service spaces (low risk)
Lockers
and store-rooms not having provisions for the storage of flammable
liquids and having areas less than 4 m2 and drying rooms
and laundries.
-
(6)
Machinery spaces of category A
Spaces as defined in regulation 3.31.
-
(7)
Other machinery spaces
Electrical
equipment rooms (auto-telephone exchange and airconditioning duct
spaces). Spaces as defined in regulation 3.30 excluding
machinery spaces of category A.
-
(8)
Cargo pump-rooms
Spaces
containing cargo pumps and entrances and trunks to such spaces.
-
(9)
Service spaces (high risk)
Galleys,
pantries containing cooking appliances, saunas, paint lockers and
store-rooms having areas of 4 m2 or more, spaces for the
storage of flammable liquids and workshops other than those forming
part of the machinery spaces.
-
(10)
Open decks
Open
deck spaces and enclosed promenades having little or no fire risk.
To be considered in this category, enclosed promenades shall have
no significant fire risk, meaning that furnishings shall be restricted
to deck furniture. In addition, such spaces shall be naturally ventilated
by permanent openings. Air spaces (the space outside
superstructures and deckhouses).
2.4.2.3 Continuous "B" class ceilings or linings,
in association with the relevant decks or bulkheads, may be accepted
as contributing, wholly or in part, to the required insulation and
integrity of a division.
2.4.2.4 External boundaries which are required
in regulation 11.2 to be of steel or other equivalent material may
be pierced for the fitting of windows and sidescuttles provided that
there is no requirement for such boundarie s of tankers to have "A"
class integrity. Similarly, in such boundaries which are not required
to have "A" class integrity, doors may be constructed of materials
which are to the satisfaction of the Administration.
2.4.2.5 Exterior boundaries of superstructures
and deckhouses enclosing accommodation and including any overhanging
decks which support such accommodation, shall be constructed of steel
and insulated to "A-60" standard for the whole of the portions which
face the cargo area and on the outward sides for a distance of 3 m
from the end boundary facing the cargo area. The distance of 3 m shall
be measured horizontally and parallel to the middle line of the ship
from the boundary which faces the cargo area at each deck level. In
the case of the sides of those superstructures and deckhouses, such
insulation shall be carried up to the underside of the deck of the
navigation bridge.
2.4.2.6 Skylights to cargo pump-rooms shall be
of steel, shall not contain any glass and shall be capable of being
closed from outside the pump-room.
2.4.2.7 Construction and arrangement of saunas
shall comply with paragraph 2.2.3.4.
Table 9.7 Fire
integrity of bulkheads separating adjacent spaces
Spaces
|
(1)
|
(2)
|
(3)
|
(4)
|
(5)
|
(6)
|
(7)
|
(8)
|
(9)
|
(10)
|
Control stations
|
(1)
|
A-0c
|
A-0
|
A-60
|
A-0
|
A-15
|
A-60
|
A-15
|
A-60
|
A-60
|
*
|
Corridors
|
(2)
|
|
C
|
B-0
|
B-0
|
B-0
|
A-60
|
A-0
|
A-60
|
A-0
|
*
|
A-0a
|
Accommodation spaces
|
(3)
|
|
|
C
|
B-0
|
B-0
|
A-60
|
A-0
|
A-60
|
A-0
|
*
|
A-0a
|
Stairways
|
(4)
|
|
|
|
B-0
|
B-0
|
A-60
|
A-0
|
A-60
|
A-0
|
*
|
A-0a
|
A-0a
|
Service spaces (low risk)
|
(5)
|
|
|
|
|
C
|
A-60
|
A-0
|
A-60
|
A-0
|
*
|
Machinery spaces of category A
|
(6)
|
|
|
|
|
|
*
|
A-0
|
A-0d
|
A-60
|
*
|
Other machinery spaces
|
(7)
|
|
|
|
|
|
|
A-0b
|
A-0
|
A-0
|
*
|
Cargo pump-rooms
|
(8)
|
|
|
|
|
|
|
|
*
|
A-60
|
*
|
Service spaces (high risk)
|
(9)
|
|
|
|
|
|
|
|
|
A-0b
|
*
|
Open decks
|
(10)
|
|
|
|
|
|
|
|
|
|
–
|
Table 9.8 Fire
integrity of decks seperating adjacent spaces
Space below
|
Space above
|
(1)
|
(2)
|
(3)
|
(4)
|
(5)
|
(6)
|
(7)
|
(8)
|
(9)
|
(10)
|
Control stations
|
(1)
|
A-0
|
A-0
|
A-0
|
A-0
|
A-0
|
A-60
|
A-0
|
–
|
A-0
|
*
|
Corridors
|
(2)
|
A-0
|
*
|
*
|
A-0
|
*
|
A-60
|
A-0
|
–
|
A-0
|
*
|
Accommodation spaces
|
(3)
|
A-60
|
A-0
|
*
|
A-0
|
*
|
A-60
|
A-0
|
–
|
A-0
|
*
|
Stairways
|
(4)
|
A-0
|
A-0
|
A-0
|
*
|
A-0
|
A-60
|
A-0
|
–
|
A-0
|
*
|
Service spaces (low risk)
|
(5)
|
A-15
|
A-0
|
A-0
|
A-0
|
*
|
A-60
|
A-0
|
–
|
A-0
|
*
|
Machinery spaces of category A
|
(6)
|
A-60
|
A-60
|
A-60
|
A-60
|
A-60
|
*
|
A-60e
|
A-0
|
A-60
|
*
|
Other machinery spaces
|
(7)
|
A-15
|
A-0
|
A-0
|
A-0
|
A-0
|
A-0
|
*
|
A-0
|
A-0
|
*
|
Cargo pump-rooms
|
(8)
|
–
|
–
|
–
|
–
|
–
|
A-0d
|
A-0
|
*
|
–
|
*
|
Service spaces (high risk)
|
(9)
|
A-60
|
A-0
|
A-0
|
A-0
|
A-0
|
A-60
|
A-0
|
–
|
A-0b
|
*
|
Open decks
|
(10)
|
*
|
*
|
*
|
*
|
*
|
*
|
*
|
*
|
*
|
–
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Notes:
|
To be applied to tables 9.7 and 9.8 as
appropriate.
|
a
|
For clarification as to which applies, see
paragraphs 2.3.2 and 2.3.4.
|
b
|
Where spaces are of the same numerical
category and superscript b appears, a bulkhead or deck of the
rating shown in the tables is only required when the adjacent
spaces are for a different purpose (e.g. in category (9)). A
galley next to a galley does not require a bulkhead but a galley
next to a paint room requires an "A-0" bulkhead.
|
c
|
Bulkheads separating the wheelhouse,
chartroom and radio room from each other may have a "B-0"
rating.
|
d
|
Bulkheads and decks between cargo
pump-rooms and machinery spaces of category A may be penetrated
by cargo pump shaft glands and similar gland penetrations,
provided that gas tight seals with efficient lubrication or
other means of ensuring the permanence of the gas seal are
fitted in way of the bulkheads or deck.
|
e
|
Fire insulation need not be fitted if the
machinery space in category (7) if, in the opinion of the
Administration, it has little or no fire risk.
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
*
|
Where an asterisk appears in the table,
the division is required to be of steel or other equivalent
material, but is not required to be of "A" class standard.
However, where a deck, except an open deck, is penetrated for
the passage of electric cables, pipes and vent ducts, such
penetrations should be made tight to prevent the passage of
flame and smoke. Divisions between control stations (emergency
generators) and open decks may have air intake openings without
means for closure, unless a fixed gas fire-fighting system is
fitted.
|
3 Penetration in fire -resisting divisions
and prevention of heat transmission
3.1 Where "A" class divisions are penetrated,
such penetrations shall be tested in accordance with the Fire Test Procedures Code, subject to the provisions of paragraph
4.1.1.5. In the case of ventilation ducts, paragraphs 7.1.2 and 7.3.1
apply. However, where a pipe penetration is made of steel or equivalent
material having a thickness of 3mm or greater and a length of not
less than 900 mm (preferably 450 mm on each side of the division),
and no openings, testing is not required. Such penetrations shall
be suitably insulated by extension of the insulation at the same level
of the division.
3.2 Where "B" class divisions are penetrated for
the passage of electric cables, pipes, trunks, ducts, etc., or for
the fitting of ventilation terminals, lighting fixtures and similar
devices, arrangements shall be made to ensure that the fire resistance
is not impaired, subject to the provisions of paragraph 7.3.2. Pipes
other than steel or copper that penetrate "B" class divisions shall
be protected by either:
-
.1 a fire tested penetration device, suitable
for the fire resistance of the division pierced and the type of pipe
used; or
-
.2 a steel sleeve, having a thickness of not less
than 1.8 mm and a length of not less than 900 mm for pipe diameters
of 150 mm or more and not less than 600 mm for pipe diameters of less
than 150 mm (preferably equally divided to each side of the division).
The pipe shall be connected to the ends of the sleeve by flanges or
couplings; or the clearance between the sleeve and the pipe shall
not exceed 2.5 mm; or any clearance between pipe and sleeve shall
be made tight by means of non-combustible or other suitable material.
3.3 Uninsulated metallic pipes penetrating "A"
or "B" class divisions shall be of materials having a melting temperature
which exceeds 950°C for “A-0” and 850°C for “B-0”
class divisions.
3.4 In approving structural fire protection details,
the Administration shall have regard to the risk of heat transmission
at intersections and terminal points of required thermal barriers.
The insulation of a deck or bulkhead shall be carried past the penetration,
intersection or terminal point for a distance of at least 450 mm in
the case of steel and aluminium structures. If a space is divided
with a deck or a bulkhead of "A" class standard having insulation
of different values, the insulation with the higher value shall continue
on the deck or bulkhead with the insulation of the lesser value for
a distance of at least 450 mm.
4 Protection of openings in fire resisting
divisions
4.1
Openings in bulkheads and decks in passenger
ships
4.1.1
Openings in "A" class divisions
4.1.1.1 Except for hatches between cargo, special
category, store, and baggage spaces, and between such spaces and the
weather decks, openings shall be provided with permanently attached
means of closing which shall be at least as effective for resisting
fires as the divisions in which they are fitted.
4.1.1.2 The construction of doors and door frames
in "A" class divisions, with the means of securing them when closed,
shall provide resistance to fire as well as to the passage of smoke
and flame equivalent to that of the bulkheads in which the doors are
situated, this being determined in accordance with the Fire
Test Procedures Code. Such doors and door frames shall be constructed
of steel or other equivalent material. Watertight doors need not be
insulated.
4.1.1.3 It shall be possible for each door to
be opened and closed from each side of the bulkhead by one person
only.
4.1.1.4 Fire doors in main vertical zone bulkheads,
galley boundaries and stairway enclosures other than power-operated
watertight doors and those which are normally locked, shall satisfy
the following requirements:
-
.1 the doors shall be self-closing and be capable
of closing with an angle of inclination of up to 3.5°opposing
closure;
-
.2 the approximate time of closure for hinged
fire doors shall be no more than 40 s and no less than 10 s from the
beginning of their movement with the ship in upright position. The
approximate uniform rate of closure for sliding doors shall be of
no more than 0.2 m/s and no less than 0.1 m/s with the ship in upright
position;
-
.3 the doors, except those for emergency escape
trunks, shall be capable of remote release from the continuously manned
central control station, either simultaneously or in groups and shall
be capable of release also individually from a position at both sides
of the door. Release switches shall have an on-off function to prevent
automatic resetting of the system;
-
.4 hold-back hooks not subject to central control
station release are prohibited;
-
.5 a door closed remotely from the central control
station shall be capable of being re-opened from both sides of the
door by local control. After such local opening, the door shall automatically
close again;
-
.6 indication must be provided at the fire door
indicator panel in the continuously manned central control station
whether each door is closed;
-
.7 the release mechanism shall be so designed
that the door will automatically close in the event of disruption
of the control system or central power supply;
-
.8 local power accumulators for power-operated
doors shall be provided in the immediate vicinity of the doors to
enable the doors to be operated after disruption of the control system
or central power supply at least ten times (fully opened and closed)
using the local controls;
-
.9 disruption of the control system or central
power supply at one door shall not impair the safe functioning of
the other doors;
-
.10 remote-released sliding or power-operated
doors shall be equipped with an alarm that sounds at least 5 s but
no more than 10 s after the door being released from the central control
station and before the door begins to move and continues sounding
until the door is completely closed;
-
.11 a door designed to re-open upon contacting
an object in its path shall re-open not more than 1 m from the point
of contact;
-
.12 double-leaf doors equipped with a latch necessary
for their fire integrity shall have a latch that is automatically
activated by the operation of the doors when released by the system;
-
.13 doors giving direct access to special category
spaces which are power-operated and automatically closed need not
be equipped with the alarms and remote-release mechanisms required
in paragraphs 4.1.1.4.3 and 4.1.1.4.10;
-
.14 the components of the local control system
shall be accessible for maintenance and adjusting;
-
.15 power-operated doors shall be provided with
a control system of an approved type which shall be able to operate
in case of fire and be in accordance with the Fire
Test Procedures Code. This system shall satisfy the following
requirements:
-
.15.1 the control system shall be able to operate
the door at the temperature of at least 200°C for at least 60
min, served by the power supply;
-
.15.2 the power supply for all other doors not
subject to fire shall not be impaired; and
-
.15.3 at temperatures exceeding 200°C the
control system shall be automatically isolated from the power supply
and shall be capable of keeping the door closed up to at least 945°C.
4.1.1.5 In ships carrying not more than 36 passengers,
where a space is protected by an automatic sprinkler fire detection
and alarm system complying with the provisions the Fire
Safety Systems Code or fitted with a continuous "B" class ceiling,
openings in decks not forming steps in main vertical zones nor bounding
horizontal zones shall be closed reasonably tight and such decks shall
meet the "A" class integrity requirements in so far as is reasonable
and practicable in the opinion of the Administration.
4.1.1.6 The requirements for "A" class integrity
of the outer boundaries of a ship shall not apply to glass partitions,
windows and sidescuttles, provided that there is no requirement for
such boundaries to have "A" class integrity in paragraph 4.1.3.3.
The requirements for "A" class integrity of the outer boundaries of
the ship shall not apply to exterior doors, except for those in superstructures
and deckhouses facing lifesaving appliances, embarkation and external
assembly station areas, external stairs and open decks used for escape
routes. Stairway enclosure doors need not meet this requirement.
4.1.1.7 Except for watertight doors, weathertight
doors (semi-watertight doors), doors leading to the open deck and
doors which need to be reasonably gastight, all "A" class doors located
in stairways, public spaces and main vertical zone bulkheads in escape
routes shall be equipped with a self-closing hose port of material,
construction and fire resistance which is equivalent to the door into
which it is fitted, and shall be a 150 mm square clear opening with
the door closed and shall be inset into the lower edge of the door,
opposite the door hinges or, in the case of sliding doors, nearest
the opening.
4.1.1.8 Where it is necessary that a ventilation
duct passes through a main vertical zone division, a fail-safe automatic
closing fire damper shall be fitted adjacent to the division. The
damper shall also be capable of being manually closed from each side
of the division. The operating position shall be readily accessible
and be marked in red light-reflecting colour. The duct between the
division and the damper shall be of steel or other equivalent material
and, if necessary, insulated to comply with the requirements of paragraph
3.1. The damper shall be fitted on at least one side of the division
with a visible indicator showing whether the damper is in the open
position.
4.1.2
Openings in "B" class divisions
4.1.2.1 Doors and door frames in "B" class divisions
and means of securing them shall provide a method of closure which
shall have resistance to fire equivalent to that of the divisions,
this being determined in accordance with the Fire
Test Procedure Code except that ventilation openings may be
permitted in the lower portion of such doors. Where such opening is
in or under a door the total net area of any such opening or openings
shall not exceed 0.05 m2. Alternatively, a non-combustible
air balance duct routed between the cabin and the corridor, and located
below the sanitary unit is permitted where the cross-sectional area
of the duct does not exceed 0.05 m2. All ventilation openings
shall be fitted with a grill made of non-combustible material. Doors
shall be non-combustible.
4.1.2.2 Cabin doors in "B" class divisions shall
be of a self-closing type. Hold-back hooks are not permitted.
4.1.2.3 The requirements for "B" class integrity
of the outer boundaries of a ship shall not apply to glass partitions,
windows and sidescuttles. Similarly, the requirements for "B" class
integrity shall not apply to exterior doors in superstructures and
deckhouses. For ships carrying not more than 36 passengers, the Administration
may permit the use of combustible materials in doors separating cabins
from the individual interior sanitary spaces such as showers.
4.1.2.4 In ships carrying not more than 36 passengers,
where an automatic sprinkler system complying with the provisions
of the Fire Safety Systems Code is fitted:
-
.1 openings in decks not forming steps in main
vertical zones nor bounding horizontal zones shall be closed reasonably
tight and such decks shall meet the "B" class integrity requirements
in so far as is reasonable and practicable in the opinion of the Administration;
and
-
.2 openings in corridor bulkheads of "B" class
materials shall be protected in accordance with the provisions of
paragraph 2.2.2.
4.1.3
Windows and sidescuttles
4.1.3.1 Windows and sidescuttles in bulkheads
within accommodation and service spaces and control stations other
than those to which the provisions of paragraph 4.1.1.6 and of paragraph
4.1.2.3 apply, shall be so constructed as to preserve the integrity
requirements of the type of bulkheads in which they are fitted, this
being determined in accordance with the Fire Test
Procedures Code.
4.1.3.2 Notwithstanding the requirements of tables
9.1 to 9.4, windows and sidescuttles in bulkheads separating accommodation
and service spaces and control stations from weather shall be constructed
with frames of steel or other suitable material. The glass shall be
retained by a metal glazing bead or angle.
4.1.3.3 Windows facing life-saving appliances,
embarkation and assembly stations, external stairs and open decks
used for escape routes, and windows situated below liferaft and escape
slide embarkation areas shall have fire integrity as required in table
9.1. Where automatic dedicated sprinkler heads are provided for windows,
"A-0" windows may be accepted as equivalent. To be considered under
this paragraph, the sprinkler heads must either be:
-
.1 dedicated heads located above the windows,
and installed in addition to the conventional ceiling sprinklers;
or
-
.2 conventional ceiling sprinkler heads arranged
such that the window is protected by an average application rate of
at least 5 ⋉/m2 and the additional window area is
included in the calculation of the area of coverage.
Windows located in the ship’s side below the lifeboat
embarkation area shall have fire integrity at least equal to "A-0"
class.
4.2
Doors in fire-resisting divisions in
cargo ships
4.2.1 The fire resistance of doors shall be equivalent
to that of the division in which they are fitted, this being determined
in accordance with the Fire Test Procedures Code.
Doors and door frames in "A" class divisions shall be constructed
of steel. Doors in "B" class divisions shall be non-combustible. Doors
fitted in boundary bulkheads of machinery spaces of category A shall
be reasonably gastight and self-closing. In ships constructed according
to method IC, the Administration may permit the use of combustible
materials in doors separating cabins from individual interior sanitary
accommodation such as showers.
4.2.2 Doors required to be self-closing shall
not be fitted with hold-back hooks. However, hold-back arrangements
fitted with remote release devices of the fail-safe type may be utilized.
4.2.3 In corridor bulkheads ventilation openings
may be permitted in and under the doors of cabins and public spaces.
Ventilation openings are also permitted in "B" class doors leading
to lavatories, offices, pantries, lockers and store rooms. Except
as permitted below, the openings shall be provided only in the lower
half of a door. Where such an opening is in or under a door the total
net area of any such opening or openings shall not exceed 0.05 m2.
Alternatively, a non-combustible air balance duct routed between the
cabin and the corridor, and located below the sanitary unit is permitted
where the cross-sectional area of the duct does not exceed 0.05 m2.
Ventilation openings, except those under the door, shall be fitted
with a grille made of non-combustible material.
4.2.4 Watertight doors need not be insulated.
5 Protection of openings in machinery
spaces boundaries
5.1
Application
5.1.1 The provision of this paragraph shall apply
to machinery spaces of category A and, where the Administration considers
it desirable, to other machinery spaces.
5.2
Protection of openings in machinery
space boundaries
5.2.1 The number of skylights, doors, ventilators,
openings in funnels to permit exhaust ventilation and other openings
to machinery spaces shall be reduced to a minimum consistent with
the needs of ventilation and the proper and safe working of the ship.
5.2.2 Skylights shall be of steel and shall not
contain glass panels.
5.2.3 Means of control shall be provided for closing
power-operated doors or actuating release mechanisms on doors other
than power-operated watertight doors. The control shall be located
outside the space concerned, where they will not be cut off in the
event of fire in the space it serves.
5.2.4 In passenger ships, the means of control
required in paragraph 5.2.3 shall be situated at one control position
or grouped in as few positions as possible to the satisfaction of
the Administration. Such positions shall have safe access from the
open deck.
5.2.5 In passenger ships, doors, other than power-operated
watertight doors shall be so arranged that positive closure is assured
in case of fire in the space by power-operated closing arrangements
or by the provision of self-closing doors capable of closing against
an inclination of 3.5° opposing closure, and having a fail-safe
hold-back arrangement, provided with a remotely operated release device.
Doors for emergency escape trunks need not be fitted with a fail-safe
hold-back facility and a remotely operated release device.
5.2.6 Windows shall not be fitted in machinery
space boundaries. However, this does not preclude the use of glass
in control rooms within the machinery spaces.
6 Protection of cargo space boundaries
6.1 In passenger ships carrying more than 36 passengers,
the boundary bulkheads and decks of special category and ro-ro spaces
shall be insulated to "A-60" class standard. However, where a category
(5), (9) and (10) space, as defined in paragraph 2.2.3, is on one
side of the division the standard may be reduced to "A-0". Where fuel
oil tanks are below a special category space, the integrity of the
deck between such spaces may be reduced to "A-0" standard.
6.2 In passenger ships carrying not more than
36 passengers, the boundary bulkheads of special category spaces shall
be insulated as required for category (11) spaces in table 9.3 and
the horizontal boundaries as required for category (11) spaces in
table 9.4.
6.3 In passenger ships carrying not more than
36 passengers the boundary bulkheads and decks of closed and open
ro-ro spaces shall have a fire integrity as required for category
(8) spaces in table 9.3 and the horizontal boundaries as required
for category (8) spaces in table 9.4.
6.4 In passenger ships, indicators shall be provided
on the navigating bridge which shall indicate when any fire door leading
to or from the special category spaces is closed.
6.5 In tankers, for the protection of cargo tanks
carrying crude oil and petroleum products having a flashpoint not
exceeding 60°C, materials readily rendered ineffective by heat
shall not be used for valves, fittings, tank opening covers, cargo
vent piping, and cargo piping so as to prevent the spread of fire
to the cargo.
7 Ventilation systems
7.1
Duct and dampers
7.1.1 Ventilation ducts shall be of non-combustible
material. However, short ducts, not generally exceeding 2 m in length
and with a free cross-sectional areafootnote not
exceeding 0.02 m2, need not be non-combustible subject
to the following conditions:
-
.1 the ducts are made of a material which has
low flame spread characteristics;
-
.2 the ducts are only used at the end of the ventilation
device; and
-
.3 the ducts are not situated less than 600 mm,
measured along the duct, from an opening in an "A" or "B" class division
including continuous "B" class ceiling.
7.1.2 The following arrangements shall be tested
in accordance with the Fire Test Procedures Code:
-
.1 fire dampers, including their relevant means
of operation; and
-
.2 duct penetrations through "A" class divisions.
However, the test is not required where steel sleeves are directly
joined to ventilation ducts by means of riveted or screwed flanges
or by welding.
7.2
Arrangement of ducts
7.2.1 The ventilation systems for machinery spaces
of category A, vehicle spaces, ro-ro spaces, galleys, special category
spaces and cargo spaces shall, in general, be separated from each
other and from the ventilation systems serving other spaces. Except
that the galley ventilation systems on cargo ships of less than 4,000
gross tonnage and in passenger ships carrying not more than 36 passengers,
need not be completely separated, but may be served by separate ducts
from a ventilation unit serving other spaces. In any case, an automatic
fire damper shall be fitted in the galley ventilation duct near the
ventilation unit. Ducts provided for the ventilation of machinery
spaces of category A, galleys, vehicle spaces, ro-ro spaces or special
category spaces shall not pass through accommodation spaces, service
spaces or control stations unless they comply with the conditions
specified in paragraphs 7.2.1.1.1 to 7.2.1.1.4 or 7.2.1.2.1 and 7.2.1.2.2
below:
-
.1.1 the ducts are constructed of steel having
a thickness of at least 3 mm and 5 mm for ducts the widths or diameters
of which are up to and including 300 mm and 760 mm and over respectively
and, in the case of such ducts, the widths or diameters of which are
between 300 mm and 760 mm having a thickness obtained by interpolation;
-
.1.2 the ducts are suitably supported and stiffened;
-
.1.3 the ducts are fitted with automatic fire
dampers close to the boundaries penetrated; and
-
.1.4 the ducts are insulated to "A-60" class standard
from the machinery spaces, galleys, vehicle spaces, ro-ro spaces or
special category spaces to a point at least 5 m beyond each fire damper;
or
-
.2.1 the ducts are constructed of steel in accordance
with paragraphs 7.2.1.1.1 and 7.2.1.1.2; and
-
.2.2 the ducts are insulated to "A-60" class standard
throughout the accommodation spaces, service spaces or control stations;
except that penetrations of main zone divisions shall also
comply with the requirements of paragraph 4.1.1.8.
7.2.2 Ducts provided for ventilation to accommodation
spaces, service spaces or control stations shall not pass through
machinery spaces of category A, galleys, vehicle spaces, ro-ro spaces
or special category spaces unless they comply with the conditions
specified in paragraphs 7.2.2.1.1 to 7.2.2.1.3 or 7.2.2.2.1 and 7.2.2.2.2
below:
-
.1.1 the ducts where they pass through a machinery
space of category A, galley, vehicle space, ro-ro space or special
category space are constructed of steel in accordance with paragraphs
7.2.1.1.1 and 7.2.1.1.2;
-
.1.2 automatic fire dampers are fitted close to
the boundaries penetrated; and
-
.1.3 the integrity of the machinery space, galley,
vehicle space, ro-ro space or special category space boundaries is
maintained at the penetrations;
or
-
.2.1 the ducts where they pass through a machinery
space of category A, galley, vehicle space, ro-ro space or special
category space are constructed of steel in accordance with paragraphs
7.2.1.1.1 and 7.2.1.1.2; and
-
.2.2 the ducts are insulated to "A-60" standard
within the machinery space, galley, vehicle space, ro-ro space or
special category space;
except that penetrations of main zone divisions shall also
comply with the requirements of paragraph 4.1.1.8.
7.3
Details of duct penetrations
7.3.1 Where a thin plated duct with a free cross-sectional
area equal to, or less than, 0.02 m2 passes through "A"
class bulkheads or decks, the opening shall be lined with a steel
sheet sleeve having a thickness of at least 3 mm and a length of at
least 200 mm, divided preferably into 100 mm on each side of the bulkhead
or, in the case of the deck, wholly laid on the lower side of the
decks pierced. Where ventilation ducts with a free cross-sectional
area exceeding 0.02 m2 pass through "A" class bulkheads
or decks, the opening shall be lined with a steel sheet sleeve. However,
where such ducts are of steel construction and pass through a deck
or bulkhead, the ducts and sleeves shall comply with the following:
-
.1 The sleeves shall have a thickness of at least
3 mm and a length of at least 900 mm. When passing through bulkheads,
this length shall be divided preferably into 450 mm on each side of
the bulkhead. These ducts, or sleeves lining such ducts, shall be
provided with fire insulation. The insulation shall have at least
the same fire integrity as the bulkhead or deck through which the
duct passes; and
-
.2 Ducts with a free cross-sectional area exceeding
0.075 m2 shall be fitted with fire dampers in addition
to the requirements of paragraph 7.3.1.1. The fire damper shall operate
automatically, but shall also be capable of being closed manually
from both sides of the bulkhead or deck. The damper shall be provided
with an indicator which shows whether the damper is open or closed.
Fire dampers are not required, however, where ducts pass through spaces
surrounded by "A" class divisions, without serving those spaces, provided
those ducts have the same fire integrity as the divisions which they
pierce. Fire dampers shall be easily accessible. Where they are placed
behind ceilings or linings, these ceilings or linings shall be provided
with an inspection door on which a plate reporting the identification
number of the fire damper is provided. The fire damper identification
number shall also be placed on any remote controls required.
7.3.2 Ventilation ducts with a free cross-sectional
area exceeding 0.02 m2 passing through "B" class bulkheads
shall be lined with steel sheet sleeves of 900 mm in length divided
preferably into 450 mm on each side of the bulkheads unless the duct
is of steel for this length.
7.4
Ventilation systems for passenger ships
carrying more than 36 passengers
7.4.1 The ventilation system of a passenger ship
carrying more than 36 passengers shall be in compliance with the following
additional requirements.
7.4.2 In general, the ventilation fans shall be
so disposed that the ducts reaching the various spaces remain within
the main vertical zone.
7.4.3 Where ventilation systems penetrate decks,
precautions shall be taken, in addition to those relating to the fire
integrity of the deck required by paragraphs 3.1 and 4.1.1.5, to reduce
the likelihood of smoke and hot gases passing from one 'tween-deck
space to another through the system. In addition to insulation requirements
contained in paragraph 7.4, vertical ducts shall, if necessary, be
insulated as required by the appropriate tables 9.1 and 9.2.
7.4.4 Except in cargo spaces, ventilation ducts
shall be constructed of the following materials:
-
.1 ducts not less than 0.075 m2 in
free cross-sectional area and all vertical ducts serving more than
a single 'tween-deck space shall be constructed of steel or other
equivalent material;
-
.2 ducts less than 0.075 m2 in free
cross-sectional area other than the vertical ducts referred to in
paragraph 7.4.4.1, shall be constructed of non-combustible materials.
Where such ducts penetrate "A" or "B" class division due regard shall
be given to ensuring the fire integrity of the division; and
-
.3 short length of duct, not in general exceeding
0.02m2 in free cross-sectional area nor 2 m in length,
need not be non-combustible provided that all of the following conditions
are met:
-
.3.1 the duct is constructed of a material which
has low flame spread characteristics;
-
.3.2 the duct is used only at the terminal end
of the ventilation system; and
-
3.3 the duct is not located closer than 600mm
measured along its length to a penetration of an "A" or "B" class
division, including continuous "B" class ceilings.
7.4.5 Stairway enclosures shall be ventilated
and served by an independent fan and duct system which shall not serve
any other spaces in the ventilation systems.
7.4.6 Exhaust ducts shall be provided with hatches
for inspection and cleaning. The hatches shall be located near the
fire dampers.
7.5
Exhaust ducts from galley ranges
7.5.1
Requirements for passenger ships carrying
more than 36 passengers
Exhaust ducts from galley ranges shall meet the requirements
of paragraphs 7.2.1.2.1 and 7.2.1.2.2 and shall be fitted with:
-
.1 a grease trap readily removable for cleaning
unless an alternative approved grease removal system is fitted;
-
.2 a fire damper located in the lower end of the
duct which is automatically and remotely operated, and in addition
a remotely operated fire damper located in the upper end of the duct;
-
.3 a fixed means for extinguishing a fire within
the duct;
-
.4 remote-control arrangements for shutting off
the exhaust fans and supply fans, for operating the fire dampers mentioned
in paragraph 7.5.1.2 and for operating the fire-extinguishing system,
which shall be placed in a position close to the entrance to the galley.
Where a multi-branch system is installed, a remote means located with
the above controls shall be provided to close all branches exhausting
through the same main duct before an extinguishing medium is released
into the system; and
-
.5 suitably located hatches for inspection and
cleaning.
7.5.2
Requirements for cargo ships and passenger
ships carrying not more than 36 passenger ships
7.5.2.1 Where they pass through accommodation
spaces or spaces containing combustible materials, the exhaust ducts
from galley ranges shall be constructed of "A" class divisions. Each
exhaust duct shall be fitted with:
-
.1 a grease trap readily removable for cleaning;
-
.2 a fire damper located in the lower end of the
duct;
-
.3 arrangements, operable from within the galley,
for shutting off the exhaust fans; and
-
.4 fixed means for extinguishing a fire within
the duct.
Regulation 10 – Fire fighting
1 Purpose
The purpose of this regulation is to suppress and swiftly
extinguish a fire in the space of origin. For this purpose, the following
functional requirements shall be met:
2 Water supply systems
Ships shall be provided with fire pumps, fire mains, hydrants
and hoses complying with the applicable requirements of this regulation.
2.1
Fire mains and hydrants
2.1.1
General
Materials readily rendered ineffective by heat shall not
be used for fire mains and hydrants unless adequately protected. The
pipes and hydrants shall be so placed that the fire hoses may be easily
coupled to them. The arrangement of pipes and hydrants shall be such
as to avoid the possibility of freezing. Suitable drainage provisions
shall be provided for fire main piping. Isolation valves shall be
installed for all open deck fire main branches used for purposes other
than fire fighting. In ships where deck cargo may be carried, the
positions of the hydrants shall be such that they are always readily
accessible and the pipes shall be arranged as far as practicable to
avoid risk of damage by such cargo.
2.1.2
Ready availability of water supply
The arrangements for the ready availability of water supply
shall be:
-
.1 in passenger ships:
-
.1.1 of 1,000 gross tonnage and upwards such that
at least one effective jet of water is immediately available from
any hydrant in an interior location and so as to ensure the continuation
of the output of water by the automatic starting of one required fire
pump;
-
.1.2 of less than 1,000 gross tonnage by automatic
start of at least one fire pump or by remote starting from the navigation
bridge of at least one fire pump. If the pump starts automatically
or if the bottom valve cannot be opened from where the pump is remotely
started, the bottom valve shall always be kept open; and
-
.1.3 if fitted with periodically unattended machinery
spaces in accordance with regulation
II-1/54, the Administration shall determine provisions for
fixed water fire-extinguishing arrangement for such spaces equivalent
to those required for normally attended machinery spaces;
-
.2 in cargo ships:
-
.2.1 to the satisfaction of the Administration;
and
-
.2.2 with a periodically unattended machinery
space or when only one person is required on watch, there shall be
immediate water delivery from the fire main system at a suitable pressure,
either by remote starting of one of the main fire pumps with remote
starting from the navigating bridge and fire control station, if any,
or permanent pressurization of the fire main system by one of the
main fire pumps, except that the Administration may waive this requirement
for cargo ships of less than 1,600 gross tonnage if the fire pump
starting arrangement in the machinery space is in an easily accessible
position.
2.1.3
Diameter of fire mains
The diameter of the fire main and water service pipes shall
be sufficient for the effective distribution of the maximum required
discharge from two fire pumps operating simultaneously, except that
in the case of cargo ships the diameter need only be sufficient for
the discharge of 140 m3/h.
2.1.4
Isolating valves and relief valves
2.1.4.1 Isolating valves to separate the section
of the fire main within the machinery space containing the main fire
pump or pumps from the rest of the fire main shall be fitted in an
easily accessible and tenable position outside the machinery spaces.
The fire main shall be so arranged that when the isolating valves
are shut all the hydrants on the ship, except those in the machinery
space referred to above, can be supplied with water by another fire
pump or an emergency fire pump. The emergency fire pump, its seawater
inlet, and suction and delivery pipes and isolating valves shall be
located outside the machinery space. If this arrangement cannot be
made, the sea-chest may be fitted in the machinery space if the valve
is remotely controlled from a position in the same compartment as
the emergency fire pump and the suction pipe is as short as practicable.
Short lengths of suction or discharge piping may penetrate the machinery
space, provided they are enclosed in a substantial steel casing, or
are insulated to A-60 class standards. The pipes shall have substantial
wall thickness, but in no case less than 11 mm, and shall be welded
except for the flanged connection to the sea inlet valve.
2.1.4.2 A valve shall be fitted to serve each
fire hydrant so that any fire hose may be removed while the fire pumps
are in operation.
2.1.4.3 Relief valves shall be provided in conjunction
with fire pumps if the pumps are capable of developing a pressure
exceeding the design pressure of the water service pipes, hydrants
and hoses. These valves shall be so placed and adjusted as to prevent
excessive pressure in any part of the fire main system.
2.1.4.4 In tankers, isolation valves shall be
fitted in the fire main at poop front in a protected position and
on the tank deck at intervals of not more than 40 m to preserve the
integrity of the fire main system in case of fire or explosion.
2.1.5
Number and position of hydrants
2.1.5.1 The number and position of hydrants shall
be such that at least two jets of water not emanating from the same
hydrant, one of which shall be from a single length of hose, may reach
any part of the ship normally accessible to the passengers or crew
while the ship is being navigated and any part of any cargo space
when empty, any ro-ro space or any vehicle space in which latter case
the two jets shall reach any part of the space, each from a single
length of hose. Furthermore, such hydrants shall be positioned near
the accesses to the protected spaces.
2.1.5.2 In addition to the requirements in the
paragraph 2.1.5.1, passenger ships shall comply with the following:
-
.1 in the accommodation, service and machinery
spaces the number and position of hydrants shall be such that the
requirements of paragraph 2.1.5.1 may be complied with when all watertight
doors and all doors in main vertical zone bulkheads are closed; and
-
.2 where access is provided to a machinery space
of category A at a low level from an adjacent shaft tunnel, two hydrants
shall be provided external to, but near the entrance to that machinery
space. Where such access is provided from other spaces, in one of
those spaces two hydrants shall be provided near the entrance to the
machinery space of category A. Such provision need not be made where
the tunnel or adjacent spaces are not part of the escape route.
2.1.6
Pressure at hydrants
With the two pumps simultaneously delivering water through
the nozzles specified in paragraph 2.3.3, with the quantity of water
as specified in paragraph 2.1.3, through any adjacent hydrants, the
following minimum pressures shall be maintained at all hydrants:
.1
|
for passenger
ships:
|
|
|
4,000 gross
tonnage and upwards
|
0.40
N/mm2
|
|
less than
4,000 gross tonnage
|
0.30
N/mm2;
|
|
|
|
.2
|
for cargo
ships,
|
|
|
6,000 gross
tonnage and upwards
|
0.27
N/mm2
|
|
less than
6,000 gross tonnage;
|
0.25
N/mm2;
|
|
and
|
|
|
|
|
.3
|
the maximum pressure at any hydrant shall
not exceed that at which the effective control of a fire hose
can be demonstrated.
|
2.1.7
International shore connection
2.1.7.1 Ships of 500 gross tonnage and upwards
shall be provided with at least one international shore connection
complying with the Fire Safety Systems Code.
2.1.7.2 Facilities shall be available enabling
such a connection to be used on either side of the ship.
2.2
Fire pumps
2.2.1
Pumps accepted as fire pumps
Sanitary, ballast, bilge or general service pumps may be
accepted as fire pumps, provided that they are not normally used for
pumping oil and that if they are subject to occasional duty for the
transfer or pumping of oil fuel, suitable change-over arrangements
are fitted.
2.2.2
Number of fire pumps
Ships shall be provided with independently driven fire pumps
as follows:
.1
|
in passenger
ships of:
|
|
|
4,000 gross
tonnage and upwards
|
at least
three
|
|
less than
4,000 gross tonnage
|
at least
two
|
|
|
|
.2
|
in cargo
ships of:
|
|
|
1,000 gross
tonnage and upwards
|
at least
two
|
|
less than
1,000 gross tonnage
|
at least two
power driven pumps, one of which shall be independently
driven.
|
2.2.3
Arrangement of fire pumps and fire
mains
2.2.3.1
Fire pumps
The arrangement of sea connections, fire pumps and their
sources of power shall be as to ensure that:
-
.1 in passenger ships of l,000 gross tonnage and
upwards, in the event of a fire in any one compartment all the fire
pumps will not be put out of action; and
-
.2 in passenger ships of less than 1,000 gross
tonnage and in cargo ships, if a fire in any one compartment could
put all the pumps out of action, there shall be an alternative means
consisting of an emergency fire pump complying with the provisions
of the Fire Safety Systems Code with its source
of power and sea connection located outside the space where the main
fire pumps or their sources of power are located.
2.2.3.2
Requirements for the space containing
the emergency fire pump
2.2.3.2.1
Location of the space
The space containing the fire pump shall not be contiguous
to the boundaries of machinery spaces of category A or those spaces
containing main fire pumps. Where this is not practicable, the common
bulkhead between the two spaces shall be insulated to a standard of
structural fire protection equivalent to that required for a control
station in regulation 9.2.3.3.
2.2.3.2.2
Access to the emergency fire pump
No direct access shall be permitted between the machinery
space and the space containing the emergency fire pump and its source
of power. When this is impracticable, the Administration may accept
an arrangement where the access is by means of an airlock with the
door of the machinery space being of A-60 class standard, and the
other door being at least steel, both reasonably gastight, self-closing
and without any hold back arrangements. Alternatively, the access
may be through a watertight door capable of being operated from a
space remote from the machinery space and the space containing the
emergency fire pump and unlikely to be cut off in the event of fire
in those spaces. In such cases, a second means of access to the space
containing the emergency fire pump and its source of power shall be
provided.
2.2.3.2.3
Ventilation of the emergency fire
pump space
Ventilation arrangements to the space containing the independent
source of power for the emergency fire pump shall be such as to preclude,
as far as practicable, the possibility of smoke from a machinery space
fire entering or being drawn into that space.
2.2.3.3
Additional pumps for cargo ships
In addition, in cargo ships where other pumps, such as general
service, bilge and ballast, etc., are fitted in a machinery space,
arrangements shall be made to ensure that at least one of these pumps,
having the capacity and pressure required by paragraphs 2.1.6.2 and
2.2.4.2, is capable of providing water to the fire main.
2.2.4
Capacity of fire pumps
2.2.4.1
Total capacity of required fire pumps
The required fire pumps shall be capable of delivering for
fire-fighting purposes a quantity of water, at the pressure specified
in paragraph 2.1.6, as follows:
-
.1 pumps in passenger ships, the quantity of water
is not less than two thirds of the quantity required to be dealt with
by the bilge pumps when employed for bilge pumping; and
-
.2 pumps in cargo ships, other than any emergency
pump, the quantity of water is not less than four thirds of the quantity
required under regulation II-1/21 to
be dealt with by each of the independent bilge pumps in a passenger
ship of the same dimension when employed in bilge pumping, provided
that in no cargo ship need the total required capacity of the fire
pumps exceed 180 m3/h.
2.2.4.2
Capacity of each fire pump
Each of the required fire pumps (other than any emergency
pump required in paragraph 2.2.3.1.2 for cargo ships) shall have a
capacity not less than 80% of the total required capacity divided
by the minimum number of required fire pumps but in any case not less
than 25 m3/h and each such pump shall in any event be capable
of delivering at least the two required jets of water. These fire
pumps shall be capable of supplying the fire main system under the
required conditions. Where more pumps than the minimum of required
pumps are installed such additional pumps shall have a capacity of
at least 25 m3/h and shall be capable of delivering at
least the two jets of water required in paragraph 2.1.5.1.
2.3
Fire hoses and nozzles
2.3.1
General specifications
2.3.1.1 Fire hoses shall be of non-perishable
material approved by the Administration and shall be sufficient in
length to project a jet of water to any of the spaces in which they
may be required to be used. Each hose shall be provided with a nozzle
and the necessary couplings. Hoses specified in this chapter as "fire
hoses" shall, together with any necessary fittings and tools, be kept
ready for use in conspicuous positions near the water service hydrants
or connections. Additionally, in interior locations in passenger ships
carrying more than 36 passengers fire hoses shall be connected to
the hydrants at all times. Fire hoses shall have a length of at least
10 m, but not more than:
-
.1 15 m in machinery spaces;
-
.2 20 m in other spaces and open decks; and
-
.3 25 m for open decks on ships with a maximum
breadth in excess of 30 m.
2.3.1.2 Unless one hose and nozzle is provided
for each hydrant in the ship, there shall be complete interchangeability
of hose couplings and nozzles.
2.3.2
Number and diameter of fire hoses
2.3.2.1 Ships shall be provided with fire hoses
the number and diameter of which shall be to the satisfaction of the
Administration.
2.3.2.2 In passenger ships, there shall be at
least one fire hose for each of the hydrants required by paragraph
2.1.5 and these hoses shall be used only for the purposes of extinguishing
fires or testing the fire-extinguishing apparatus at fire drills and
surveys.
2.3.2.3 In cargo ships:
-
.1 of 1,000 gross tonnage and upwards, the number
of fire hoses to be provided shall be one for each 30 m length of
the ship and one spare but in no case less than five in all. This
number does not include any hoses required in any engine or boiler
room. The Administration may increase the number of hoses required
so as to ensure that hoses in sufficient number are available and
accessible at all times, having regard to the type of ship and the
nature of trade in which the ship is employed. Ships carrying dangerous
goods in accordance with regulation 19 shall be provided with 3 hoses
and nozzles, in addition to those required above; and
-
.2 of less than 1,000 gross tonnage, the number
of fire hoses to be provided shall be calculated in accordance with
the provisions of paragraph 2.3.2.3.1. However, the number of hoses
shall in no case be less than three.
2.3.3
Size and types of nozzles
2.3.3.1 For the purposes of this chapter, standard
nozzle sizes shall be 12 mm, 16 mm and 19 mm or as near thereto as
possible. Larger diameter nozzles may be permitted at the discretion
of the Administration.
2.3.3.2 For accommodation and service spaces,
a nozzle size greater than 12 mm need not be used.
2.3.3.3 For machinery spaces and exterior locations,
the nozzle size shall be such as to obtain the maximum discharge possible
from two jets at the pressure mentioned in paragraph 2.1.6 from the
smallest pump, provided that a nozzle size greater than 19 mm need
not be used.
2.3.3.4 Nozzles shall be of an approved dual-purpose
type (i.e., spray/jet type) incorporating a shutoff.
3 Portable fire extinguishers
3.1
Type and design
3.2
Arrangement of fire extinguishers
3.2.1 Accommodation spaces, service spaces and
control stations shall be provided with portable fire extinguishers
of appropriate types and in sufficient number to the satisfaction
of the Administration. Ships of 1,000 gross tonnage and upwards shall
carry at least five portable fire extinguishers.
3.2.2 One of the portable fire extinguishers intended
for use in any space shall be stowed near the entrance to that space.
3.2.3 Carbon dioxide fire extinguishers shall
not be placed in accommodation spaces. In control stations and other
spaces containing electrical or electronic equipment or appliances
necessary for the safety of the ship, fire extinguishers should be
provided whose extinguishing media are neither electrically conductive
nor harmful to the equipment and appliances.
3.2.4 Fire extinguishers shall be situated ready
for use at easily visible places, which can be reached quickly and
easily at any time in the event of a fire, and in such a way that
their serviceability is not impaired by the weather, vibration or
other external factors. Portable fire extinguishers shall be provided
with devices which indicate whether they have been used.
3.3
Spare charges
3.3.1 Spare charges shall be provided for 100%
of the first 10 extinguishers and 50% of the remaining fire extinguishers
capable of being recharged on board. Not more than 60 total spare
charges are required. Instructions for recharging shall be carried
on board.
3.3.2 For fire extinguishers which cannot be recharged
onboard, additional portable fire extinguishers of the same quantity,
type, capacity and number as determined in paragraph 3.3.1 above shall
be provided in lieu of spare charges.
4 Fixed fire-extinguishing systems
4.1
Types of fixed fire extinguishing systems
4.1.1 A fixed fire extinguishing system required
by paragraph 5 below may be any of the following systems:
4.1.2 Where a fixed fire-extinguishing system
not required by this chapter is installed, it shall meet the requirements
of the relevant regulations of this chapter and the Fire
Safety Systems Code.
4.1.3 Fire-extinguishing systems using Halon 1211,
1301, and 2402 and perfluorocarbons shall be prohibited.
4.1.4 In general, the Administration shall not
permit the use of steam as a fire-extinguishing medium in fixed fire-extinguishing
systems. Where the use of steam is permitted by the Administration,
it shall be used only in restricted areas as an addition to the required
fire-extinguishing system and shall comply with the requirements of
the Fire Safety System Code.
4.2
Closing appliances for fixed gas fire-extinguishing
systems
Where a fixed gas fire-extinguishing system is used, openings
which may admit air to, or allow gas to escape from, a protected space
shall be capable of being closed from outside the protected space.
4.3
Storage rooms of fire-extinguishing medium
When the fire-extinguishing medium is stored outside a protected
space, it shall be stored in a room which is located behind the forward
collision bulkhead, and is used for no other purposes. Any entrance
to such a storage room shall preferably be from the open deck and
shall be independent of the protected space. If the storage space
is located below deck, it shall be located no more than one deck below
the open deck and shall be directly accessible by a stairway or ladder
from the open deck. Spaces which are located below deck or spaces
where access from the open deck is not provided, shall be fitted with
a mechanical ventilation system designed to take exhaust air from
the bottom of the space and shall be sized to provide at least 6 air
changes per hour. Access doors shall open outwards, and bulkheads
and decks including doors and other means of closing any opening therein,
which form the boundaries between such rooms and adjacent enclosed
spaces shall be gastight. For the purpose of the application of tables
9.1 to 9.8, such storage rooms shall be treated as fire control stations.
4.4
Water pumps for other fire-extinguishing
systems
Pumps, other than those serving the fire main, required
for the provision of water for fire-extinguishing systems required
by this chapter, their sources of power and their controls shall be
installed outside the space or spaces protected by such systems and
shall be so arranged that a fire in the space or spaces protected
will not put any such system out of action.
5 Fire extinguishing arrangements in
machinery spaces
5.1
Machinery spaces containing oil-fired
boilers or oil fuel units
5.1.1
Fixed fire-extinguishing systems
Machinery spaces of category A containing oil-fired boilers
or oil fuel units shall be provided with any one of the fixed fire-extinguishing
systems in paragraph 4.1. In each case, if the engine and boiler rooms
are not entirely separate, or if fuel oil can drain from the boiler
room into the engine-room, the combined engine and boiler rooms shall
be considered as one compartment.
5.1.2
Additional fire-extinguishing arrangements
5.1.2.1 There shall be in each boiler room or
at an entrance outside of the boiler room at least one portable foam
applicator unit complying with the provisions of the Fire
Safety Systems Code.
5.1.2.2 There shall be at least two portable foam
extinguishers or equivalent in each firing space in each boiler room
and in each space in which a part of the oil fuel installation is
situated. There shall be not less than one approved foam-type extinguisher
of at least 135 l capacity or equivalent in each boiler
room. These extinguishers shall be provided with hoses on reels suitable
for reaching any part of the boiler room. In the case of domestic
boilers of less than 175 kW an approved foam-type extinguisher of
at least 135 l capacity is not required.
5.1.2.3 In each firing space there shall be a
receptacle containing at least 0.1 m3 sand, sawdust impregnated
with soda, or other approved dry material, along with a suitable shovel
for spreading the material. An approved portable extinguisher may
be substituted as an alternative.
5.2
Machinery spaces containing internal
combustion machinery
5.2.1
Fixed fire-extinguishing systems
Machinery spaces of category A containing internal combustion
machinery shall be provided with one of the fixed fire-extinguishing
systems in paragraph 4.1.
5.2.2
Additional fire-extinguishing arrangements
5.2.2.1 There shall be at least one portable foam
applicator unit complying with the provisions of the Fire
Safety Systems Code.
5.2.2.2 There shall be in each such space approved
foam-type fire extinguishers, each of at least 45 l capacity
or equivalent, sufficient in number to enable foam or its equivalent
to be directed on to any part of the fuel and lubricating oil pressure
systems, gearing and other fire hazards. In addition, there shall
be provided a sufficient number of portable foam extinguishers or
equivalent which shall be so located that no point in the space is
more than 10 m walking distance from an extinguisher and that there
are at least two such extinguishers in each such space. For smaller
spaces of cargo ships the Administration may consider relaxing this
requirement.
5.3
Machinery spaces containing steam turbines
or enclosed steam engines
5.3.1
Fixed fire-extinguishing systems
In spaces containing steam turbines or enclosed steam engines
used for main propulsion or other purposes having in the aggregate
a total output of not less than 375 kW, one of the fire-extinguishing
systems specified in paragraph 4.1 shall be provided if such spaces
are periodically unattended.
5.3.2
Additional fire-extinguishing arrangements
5.3.2.1 There shall be approved foam fire extinguishers
each of at least 45 l capacity or equivalent sufficient in number
to enable foam or its equivalent to be directed on to any part of
the pressure lubrication system, on to any part of the casings enclosing
pressure lubricated parts of the turbines, engines or associated gearing,
and any other fire hazards. However, such extinguishers shall not
be required if protection, at least equivalent to that required by
this subparagraph, is provided in such spaces by a fixed fire-extinguishing
system fitted in compliance with paragraph 4.1.
5.3.2.2 There shall be a sufficient number of
portable foam extinguishers or equivalent which shall be so located
that no point in the space is more than 10 m walking distance from
an extinguisher and that there are at least two such extinguishers
in each such space, except that such extinguishers shall not be required
in addition to any provided in compliance with paragraph 5.1.2.2.
5.4
Other machinery spaces
Where, in the opinion of the Administration, a fire hazard
exists in any machinery space for which no specific provisions for
fire-extinguishing appliances are prescribed in paragraphs 5.1, 5.2
and 5.3, there shall be provided in, or adjacent to, that space such
a number of approved portable fire extinguishers or other means of
fire extinction as the Administration may deem sufficient.
5.5
Additional requirements for passenger
ships
In passenger ships carrying more than 36 passengers, each
machinery space of category A shall be provided with at least two
suitable water fog applicators.footnote
5.6
Fixed local application fire-fighting
systems
5.6.1 Paragraph 5.6 shall apply to passenger ships
of 500 gross tonnage and above and cargo ships of 2000 gross tonnage
and above.
5.6.2 Machinery spaces of category A above 500
m3 in volume shall, in addition to the fixed fire-extinguishing
system required in paragraph 5.1.1, be protected by an approved type
of fixed water-based or equivalent local application fire-fighting
system, based on the guidelines developed by the Organizationfootnote In the case of periodically unattended machinery
spaces, the fire fighting system shall have both automatic and manual
release capabilities. In the case of continuously manned machinery
spaces, the fire-fighting system is only required to have a manual
release capability.
5.6.3 Fixed local application fire-fighting systems
are to protect areas such as the following without the necessity of
engine shutdown, personnel evacuation, or sealing of the spaces:
-
.1 the fire hazard portions of internal combustion
machinery used for the ship’s main propulsion and power generation;
-
.2 boiler fronts;
-
.3 the fire hazard portions of incinerators; and
-
.4 purifiers for heated fuel oil.
5.6.4 Activation of any local application system
shall give a visual and distinct audible alarm in the protected space
and at continuously manned stations. The alarm shall indicate the
specific system activated. The system alarm requirements described
within this paragraph are in addition to, and not a substitute for,
the detection and fire alarm system required elsewhere in this chapter.
6 Fire -extinguishing arrangements in control stations,
accommodation and service spaces
6.1
Sprinkler systems in passenger ships
6.1.1 Passenger ships carrying more than 36 passengers
shall be equipped with an automatic sprinkler, fire detection and
fire alarm system of an approved type complying with the requirements
of the Fire Safety Systems Code in all control
stations, accommodation and service spaces, including corridors and
stairways. Alternatively, control stations, where water may cause
damage to essential equipment, may be fitted with an approved fixed
fire-extinguishing system of another type. Spaces having little or
no fire risk such as voids, public toilets, carbon dioxide rooms and
similar spaces need not be fitted with an automatic sprinkler system.
6.1.2 In passenger ships carrying not more than
36 passengers, when a fixed smoke detection and fire alarm system
complying with the provisions of the Fire Safety Systems
Code is provided only in corridors, stairways and escape routes
within accommodation spaces, an automatic sprinkler system shall be
installed in accordance with regulation 7.5.3.2.
6.2
Sprinkler systems for cargo ships
In cargo ships in which method IIC specified in regulation
9.2.3.1.1.2 is adopted, an automatic sprinkler, fire detection and
fire alarm system shall be fitted in accordance with the requirements
in regulation 7.5.5.2.
6.3
Spaces containing flammable liquid
6.3.1 Paint lockers shall be protected by:
-
.1 a carbon dioxide system, designed to give a
minimum volume of free gas equal to 40% of the gross volume of the
protected space;
-
.2 a dry powder system, designed for at least
0.5 kg powder/m3;
-
.3 a water spraying or sprinkler system, designed
for 5 ⋉/m2 min. Water spraying systems may be connected
to the fire main of the ship; or
-
.4 a system providing equivalent protection, as
determined by the Administration.
In any case, the system shall be operable from outside the
protected space.
6.3.2 Flammable liquid lockers shall be protected
by an appropriate fire-extinguishing arrangement approved by the Administration.
6.3.3 For lockers of a deck area of less than
4 m2, which do not give access to accommodation spaces,
a carbon dioxide portable fire extinguisher sized to provide a minimum
volume of free gas equal to 40% of the gross volume of the space may
be accepted in lieu of a fixed system. A discharge port shall be arranged
in the locker to allow the discharge of the extinguisher without having
to enter into the protected space. The required portable fire extinguisher
shall be stowed adjacent to the port. Alternatively, a port or hose
connection may be provided to facilitate the use of fire main water.
6.4
Deep-fat cooking equipment
Deep-fat cooking equipment shall be fitted with the following:
-
.1 an automatic or manual extinguishing system
tested to an international standard acceptable to the Organization;footnote
-
.2 a primary and backup thermostat with an alarm
to alert the operator in the event of failure of either thermostat;
-
.3 arrangements for automatically shutting off
the electrical power upon activation of the extinguishing system;
-
.4 an alarm for indicating operation of the extinguishing
system in the galley where the equipment is installed; and
-
.5 controls for manual operation of the extinguishing
system which are clearly labelled for ready use by the crew.
7 Fire-extinguishing arrangements in cargo spaces
7.1
Fixed gas fire-extinguishing systems
for general cargo
7.1.1 Except as provided for in paragraph 7.2,
the cargo spaces of passenger ships of 1,000 gross tonnage and upwards
shall be protected by a fixed carbon dioxide or inert gas fire-extinguishing
system complying with the provisions of the Fire Safety
Systems Code or by a fixed high expansion foam fire-extinguishing
system which gives equivalent protection.
7.1.2 Where it is shown to the satisfaction of
the Administration that a passenger ship is engaged on voyages of
such short duration that it would be unreasonable to apply the requirements
of paragraph 7.1.1 and also in ships of less than 1,000 gross tonnage,
the arrangements in cargo spaces shall be to the satisfaction of the
Administration, provided that the ship is fitted with steel hatch
covers and effective means of closing all ventilators and other openings
leading to the cargo spaces.
7.1.3 Except for ro-ro and vehicle spaces, cargo
spaces on cargo ships of 2,000 gross tonnage and upwards shall be
protected by a fixed carbon dioxide or inert gas fire-extinguishing
system complying with the provisions of the Fire Safety
Systems Code, or by a fire-extinguishing system which gives
equivalent protection.
7.1.4 The Administration may exempt from the requirements
of paragraphs 7.1.3 and 7.2, cargo spaces of any cargo ship if constructed,
and solely intended for, the carriage of ore, coal, grain, unseasoned
timber, non-combustible cargoes or cargoes which, in the opinion of
the Administration, constitute a low fire risk.footnote Such exemptions may be granted only if the
ship is fitted with steel hatch covers and effective means of closing
ventilators and other openings leading to the cargo spaces. When such
exemptions are granted, the Administration shall issue an Exemption
Certificate, irrespective of the date of construction of the ship
concerned, in accordance with regulation
I/12(a)(vi), and shall ensure that the list of cargoes the
ship is permitted to carry is attached to the Exemption Certificate.
7.2
Fixed gas fire-extinguishing systems
for dangerous goods
A ship engaged in the carriage of dangerous goods in any
cargo spaces shall be provided with a fixed carbon dioxide or inert
gas fire-extinguishing system complying with the provisions of the Fire Safety Systems Code or with a fire-extinguishing
system which, in the opinion of the Administration, gives equivalent
protection for the cargoes carried.
8 Cargo tank protection
8.1
Fixed deck foam systems
8.1.1 For tankers of 20,000 tonnes deadweight
and upwards, a fixed deck foam system shall be provided in accordance
with the requirements of the Fire Safety Systems Code,
except that, in lieu of the above, the Administration, after having
given consideration to the ship’s arrangement and equipment,
may accept other fixed installations if they afford protection equivalent
to the above, in accordance with regulation
I/5. The requirements for alternative fixed installations shall
comply with the requirements in paragraph 8.1.2.
8.1.2 In accordance with paragraph 8.1.1, where
the Administration accepts an equivalent fixed installation in lieu
of the fixed deck foam system, the installation shall:
8.1.3 Tankers of less than 20,000 tonnes deadweight
shall be provided with a deck foam system complying with the requirements
of the Fire Safety Systems Code.
9 Protection of cargo pump rooms in tankers
9.1
Fixed fire-extinguishing systems
Each cargo pump-room shall be provided with one of the following
fixed fire-extinguishing systems operated from a readily accessible
position outside the pump-room. Cargo pump-rooms shall be provided
with a system suitable for machinery spaces of category A.
9.1.1 A carbon dioxide system complying with the
provisions the Fire Safety Systems Code and
with the following:
-
.1 the alarms giving audible warning of the release
of fire-extinguishing medium shall be safe for use in a flammable
cargo vapour/air mixture; and
-
.2 a notice shall be exhibited at the controls
stating that due to the electrostatic ignition hazard, the system
is to be used only for fire extinguishing and not for inerting purposes.
9.1.2 A high-expansion foam system complying with
the provisions of the Fire Safety Systems Code,
provided that the foam concentrate supply is suitable for extinguishing
fires involving the cargoes carried.
9.2
Quantity of fire-extinguishing medium
Where the extinguishing medium used in the cargo pump-room
system is also used in systems serving other spaces, the quantity
of medium provided or its delivery rate need not be more than the
maximum required for the largest compartment.
10 Fire -fighter’s outfits
10.1
Types of fire-fighter’s outfits
10.2
Number of fire-fighter’s outfits
10.2.1 Ships shall carry at least two fire-fighter’s
outfits.
10.2.2 In addition, in passenger ships there shall
be provided:
-
.1 for every 80 m, or part thereof, of the aggregate
of the lengths of all passenger spaces and service spaces on the deck
which carries such spaces or, if there is more than one such deck,
on the deck which has the largest aggregate of such lengths, two fire-fighter’s
outfits and, in addition, two sets of personal equipment, each set
comprising the items stipulated in the Fire Safety
Systems Code. In passenger ships carrying more than 36 passengers,
two additional fire-fighter’s outfits shall be provided for
each main vertical zone. However, for stairway enclosures which constitute
individual main vertical zones and for the main vertical zones in
the fore or aft end of a ship which do not contain spaces of categories
(6), (7), (8) or (12) defined in regulation 9.2.2.3, no additional
fire-fighter’s outfits are required; and
-
.2 ships carrying more than 36 passengers, for
each pair of breathing apparatus there shall be provided one water
fog applicator which shall be stored adjacent to such apparatus.
10.2.3 In addition, in tankers, two fire-fighter’s
outfits shall be provided.
10.2.4 The Administration may require additional
sets of personal equipment and breathing apparatus, having due regard
to the size and type of the ship.
10.2.5 Two spare charges shall be provided for
each required breathing apparatus. Passenger ships carrying not more
than 36 passengers and cargo ships that are equipped with suitably
located means for fully recharging the air cylinders free from contamination,
need carry only one spare charge for each required apparatus. In passenger
ships carrying more than 36 passengers, at least two spare charges
for each breathing apparatus shall be provided.
10.3
Storage of fire-fighter's outfits
10.3.1 The fire-fighter’s outfits or sets
of personal equipment shall be kept ready for use in an easily accessible
location that is permanently and clearly marked and, where more than
one fire-fighter’s outfit or more than one set of personal equipment
is carried, they shall be stored in widely separated positions.
10.3.2 In passenger ships, at least two fire-fighter’s
outfits and, in addition, one set of personal equipment shall be available
at any one position. At least two fire-fighter’s outfits shall
be stored in each main vertical zone.
Regulation 11 –
Structural integrity
1 Purpose
The purpose of this regulation is to maintain structural
integrity of the ship preventing partial or whole collapse of the
ship structures due to strength deterioration by heat. For this purpose,
materials used in the ships’ structure shall ensure that the
structural integrity is not degraded due to fire.
2 Material of hull, superstructures,
structural bulkheads, decks and deckhouses
The hull, superstructures, structural bulkheads, decks and
deckhouses shall be constructed of steel or other equivalent material.
For the purpose of applying the definition of steel or other equivalent
material as given in regulation 3.43 the "applicable fire exposure"
shall be according to the integrity and insulation standards given
in tables 9.1 to 9.4. For example, where divisions such as decks or
sides and ends of deckhouses are permitted to have "B-0" fire integrity,
the "applicable fire exposure" shall be half an hour.
3 Structure of aluminium alloy
Unless otherwise specified in paragraph 2, in cases where
any part of the structure is of aluminium alloy, the following shall
apply:
-
.1 the insulation of aluminium alloy components
of "A" or "B" class divisions, except structure which, in the opinion
of the Administration, is non-load-bearing, shall be such that the
temperature of the structural core does not rise more than 200°C
above the ambient temperature at any time during the applicable fire
exposure to the standard fire test; and
-
.2 special attention shall be given to the insulation
of aluminium alloy components of columns, stanchions and other structural
members required to support lifeboat and liferaft stowage, launching
and embarkation areas, and "A" and "B" class divisions to ensure:
-
.2.1 that for such members supporting lifeboat
and liferaft areas and "A" class divisions, the temperature rise limitation
specified in paragraph 3.1 shall apply at the end of one hour; and
-
.2.2 that for such members required to support
"B" class divisions, the temperature rise limitation specified in
paragraph 3.1 shall apply at the end of half an hour.
4 Machinery spaces of category A
4.1
Crowns and casings
Crowns and casings of machinery spaces of category A shall
be of steel construction and shall be insulated as required by tables
9.5 and 9.7, as appropriate.
4.2
Floor plating
The floor plating of normal passageways in machinery spaces
of category A shall be made of steel.
5 Materials of overboard fittings
Materials readily rendered ineffective by heat shall not
be used for overboard scuppers, sanitary discharges, and other outlets
which are close to the waterline and where the failure of the material
in the event of fire would give rise to danger of flooding.
6 Protection of cargo tank structure against pressure
or vacuum in tankers
6.1
General
The venting arrangements shall be so designed and operated
as to ensure that neither pressure nor vacuum in cargo tanks shall
exceed design parameters and be such as to provide for:
-
.1 the flow of the small volumes of vapour, air
or inert gas mixtures caused by thermal variations in a cargo tank
in all cases through pressure/vacuum valves; and
-
.2 the passage of large volumes of vapour, air
or inert gas mixtures during cargo loading and ballasting, or during
discharging.
6.2
Openings for small flow by thermal variations
Openings for pressure release required by paragraph 6.1.1
shall:
-
.1 have as great a height as is practicable above
the cargo tank deck to obtain maximum dispersal of flammable vapours,
but in no case less than 2 m above the cargo tank deck; and
-
.2 be arranged at the furthest distance practicable
but not less than 5 m from the nearest air intakes and openings to
enclosed spaces containing a source of ignition and from deck machinery
and equipment which may constitute an ignition hazard. Anchor windlass
and chain locker openings constitute an ignition hazard.
6.3
Safety measures in cargo tanks
6.3.1
Preventive measures against liquid
rising in the venting system
Provisions shall be made to guard against liquid rising
in the venting system to a height which would exceed the design head
of cargo tanks. This shall be accomplished by high-level alarms or
overflow control systems or other equivalent means, together with
independent gauging devices and cargo tank filling procedures. For
the purposes of this regulation, spill valves are not considered equivalent
to an overflow system.
6.3.2
Secondary means for pressure/vacuum
relief
A secondary means of allowing full flow relief of vapour,
air or inert gas mixtures to prevent over-pressure or under-pressure
in the event of failure of the arrangements in paragraph 6.1.2. Alternatively,
pressure sensors may be fitted in each tank protected by the arrangement
required in paragraph 6.1.2, with a monitoring system in the ship’s
cargo control room or the position from which cargo operations are
normally carried out. Such monitoring equipment shall also provide
an alarm facility which is activated by detection of over-pressure
or under-pressure conditions within a tank.
6.3.3
Bypasses in vent mains
Pressure/vacuum valves required by paragraph 6.1.1 may be
provided with a bypass arrangement when they are located in a vent
main or masthead riser. Where such an arrangement is provided there
shall be suitable indicators to show whether the bypass is open or
closed.
6.3.4
Pressure/vacuum-breaking devices
One or more pressure/vacuum-breaking devices shall be provided
to prevent the cargo tanks from being subject to:
-
.1 a positive pressure, in excess of the test
pressure of the cargo tank, if the cargo were to be loaded at the
maximum rated capacity and all other outlets are left shut; and
-
.2 a negative pressure in excess of 700 mm water
gauge if cargo were to be discharged at the maximum rated capacity
of the cargo pumps and the inert gas blowers were to fail.
Such devices shall be installed on the inert gas main unless
they are installed in the venting system required by regulation 4.5.3.1
or on individual cargo tanks. The location and design of the devices
shall be in accordance with regulation 4.5.3 and paragraph 6.
6.4
Size of vent outlets
Vent outlets for cargo loading, discharging and ballasting
required by paragraph 6.1.2 shall be designed on the basis of the
maximum designed loading rate multiplied by a factor of at least 1.25
to take account of gas evolution, in order to prevent the pressure
in any cargo tank from exceeding the design pressure. The master shall
be provided with information regarding the maximum permissible loading
rate for each cargo tank and in the case of combined venting systems,
for each group of cargo tanks.
|