1.1 This test method is intended for evaluating
the effectiveness of fixed water-based fire-fighting systems installed
in ro-ro spaces and special category spaces with deck heights up to
and including 5 m and/or up to and including 2.5 m.
1.2 The test programme has two objectives:
-
.1 establishing nozzle location, nozzle characteristics,
minimum water delivery rate and minimum water pressure for systems
which will provide the required level of system response time, suppression
and control; and
-
.2 establishing the minimum area of operation
of the system for the purpose of determining hydraulic design requirements
for wet pipe, dry pipe and preaction systems.