Quarterly inspections should be carried out to ensure that
the indicated actions are taken for the specified equipment:
6.1 Fire mains, fire pumps, hydrants, hoses and
nozzles
Verify international shore connection(s) is in serviceable
condition.
6.2 Foam fire-extinguishing systems
Verify the proper quantity of foam concentrate is provided
in the foam system storage tank.
6.3 Ventilation systems and fire dampers
Test all fire dampers for local operation.
Test all fire doors located in main vertical zone bulkheads
for local operation.
6.5 Water mist, water spray and sprinkler systems
Assess system water quality in the header tank and pump unit against the manufacturer's
water quality guidelines.