The fire test report should identify the critical parameters
to be incorporated into the design, installation and operating instruction
manual. The instruction manual should reference the limitations of
each device and should include at least the following items:
-
.1 description and operating details of each device
and all accessory equipment, including identification of extinguishing
system components or accessory equipment by part or model number;
-
.2 nozzle design recommendation and limitations
for each fire type;
-
.3 type and pressure rating of pipe, tubing and
fittings to be used;
-
.4 equivalent length values of all fittings and
all system components through which water flows;
-
.5 discharge nozzle limitations, including maximum
dimensional and area coverage, minimum and maximum installation height
limitations, and nozzle permitted location in the protected volume;
-
.6 range of filling capacities for each size storage
container;
-
.7 details for the proper installation of each
device, including all component equipment;
-
.8 reference to the specific types of detection
and control panels (if applicable) to be connected to the equipment;
-
.9 operating pressure ranges of the system;
-
.10 method of sizing pipe or tubing;
-
.11 recommended orientation of tee fittings and
the splitting of flows through tees; and
-
.12 maximum difference in operating (flowing)
pressure between the hydraulically closest and most remote nozzle.