4.1 For rigid pipework systems solid drawn copper
alloy or stainless steel tube should be used. Steel tubing, aluminium,
or any materials having a low melting point should not be used.
4.2 Connection between rigid pipe sections should
be made with, hard solder (minimum melting point 450°C). Appropriate
compression or screwed fittings are recommended for general use for
pipework in LPG installations.
4.3 Lengths of flexible piping (if required for
flexible connections) should conform to an appropriate standard, be
kept as short as possible, and be protected from inadvertent damage.
Such hose should be installed in such a manner to allow access for
inspection along its length.
Proposals for a more extensive use of flexible piping (which
conforms to an internationally recognised standard for its application)
should be submitted to the Administration for approval on an individual
basis.