14A.2.5.1 Arrangements for the storage, distribution
and utilisation of oil fuel are to be such as to minimise the risk
of fire or explosion.
14A.2.5.2 Oil fuel tanks situated within, or adjacent
to, the boundaries of Category 'A' machinery spaces are not to contain
oil fuel having a flashpoint of less than 60°C.
14A.2.5.3 Oil fuel, lubricating oil and other
flammable oils are not to be carried in fore-peak tanks.
14A.2.5.4 Every oil fuel pipe, which, if damaged,
would allow oil to escape from a storage, settling or daily service
tank situated above the double bottom, shall be fitted with a cock
or valve directly on the tank capable of being closed from a safe
position outside the space concerned in the event of a fire occurring
in the space in which such tanks are situated.
14A.2.5.5 Means are to be provided to stop fuel
transfer pumps, oil fired boilers and separators from outside the
machinery space.
14A.2.5.6 Fuel filter bowls should be of metal
construction.