3.2.1 Audible and visual alarms in accordance
with the Code on Alerts and Indicators should be initiated on the
navigation bridge, at the control panel, and at all indicating units
under the following conditions:
-
.1 upon detection of gas concentrations above
the alarm setpoint in any monitored space;
-
.2 in a fault condition, such as power failure
or short-circuit;
-
.3 low or no flow in any sampling pipe;
-
.4 tampering with the alarm setpoint; or
-
.5 failure of any self-test functions described
in paragraph 4.1.4.
3.2.2 A visual alarm should remain in effect while
an alarm condition is present. The audible alarm may be silenced manually.
3.2.3 The gas concentration inside the control
panel enclosure should be monitored. Upon detection of gas concentrations
above the alarm setpoint within the enclosure, in addition to the
alarm, the gas analysis unit should be automatically isolated from
all sampling pipes and shut down. Appropriate measures should be taken
to vent flammable gas inside the enclosure to an open space away from
ignition sources.