Section 7.8.7.2 Degree of protection for electrical equipment in exhaust ventilation ducts and exhaust fans
Clasification Society 2024 - Version 9.40
Statutory Documents - IMO Publications and Documents - Circulars - Maritime Safety Committee - MSC/Circular.1102 – Interpretations of the 2000 HSC Code and SOLAS Chapter X – (15 September 2003) - Annex 1 - Interpretations of Provisions of the 2000 HSC Code - Section 7.8.7.2 Degree of protection for electrical equipment in exhaust ventilation ducts and exhaust fans

Section 7.8.7.2 Degree of protection for electrical equipment in exhaust ventilation ducts and exhaust fans

  1 The electrical equipment referred to in these regulations should be certified "safe type" and wiring, if fitted, and should be suitable for use in zone 1 areas as defined in IEC Publication 79 - Electrical apparatus for explosive gas atmospheres (gas group II A and temperature class T 3).

  2 Exhaust fans should be of a non-sparking type in accordance with IACS Unified Requirement F 29, as revised.


Copyright 2022 Clasifications Register Group Limited, International Maritime Organization, International Labour Organization or Maritime and Coastguard Agency. All rights reserved. Clasifications Register Group Limited, its affiliates and subsidiaries and their respective officers, employees or agents are, individually and collectively, referred to in this clause as 'Clasifications Register'. Clasifications Register assumes no responsibility and shall not be liable to any person for any loss, damage or expense caused by reliance on the information or advice in this document or howsoever provided, unless that person has signed a contract with the relevant Clasifications Register entity for the provision of this information or advice and in that case any responsibility or liability is exclusively on the terms and conditions set out in that contract.