6.3.1 Start and normal stop should be on oil fuel
only. Gas injection should not be possible without a corresponding
pilot oil injection. The amount of pilot fuel fed to each cylinder
should be sufficient to ensure a positive ignition of the gas mixture.
6.3.2 In case of shut-off of the gas fuel supply,
the engines should be capable of continuous operation by oil fuel
only.
6.3.3 Changeover to and from gas fuel operation
should only be possible at a power level and under conditions where
it can be done with acceptable reliability as demonstrated through
testing. On power reduction the changeover to oil fuel is to be automatic.
The changeover process itself from and to gas operation should be
automatic. Manual interruption should be possible in all cases.
6.3.4 On normal stop as well as emergency shutdown,
gas fuel supply should be shut off not later than simultaneously with
the oil fuel. It should not be possible to shut off the supply pilot
fuel without first or simultaneously closing the gas supply to each
cylinder or to the complete engine.