1.1 These Guidelines and fire tests are intended
for the design and approval of fixed water-based fire-fighting systems
for open and closed ro-ro spaces and special category spaces defined
in SOLAS regulations II-2/3.12, II-2/3.13,
II-2/3.35, II-2/3.36, II-2/3.46 and II-2/3.49. Deluge systems
can be applied on open ro-ro spaces when the actual wind condition
is taken into consideration, for example through the use of high velocity
nozzles. Systems using automatic sprinklers or nozzles are only permitted
for closed ro-ro and special category spaces or other spaces where
wind conditions are not likely to affect system performance.
1.2 These Guidelines are intended to replace both
the prescriptive requirements of resolution
A.123(V) for conventional water spray systems and the performance-based
requirements of circular MSC.1/Circ.1272 for
automatic sprinkler and deluge systems. All systems should comply
with sections 1, 2 and 3. In addition, prescriptive-based systems
should comply with section 4, and performance-based systems should
comply with section 5.