Statutory Documents - IMO Publications and Documents - Resolutions - Assembly - IMO Resolution A.754(18) – Recommendation on Fire Resistance Tests for “A”, “B” and “F” Class Divisions – (Adopted on 4 November 1993) - Annex - Recommendation on Fire Resistance Tests for “A”, “B” and “F” Class Divisions1 - 8 Method of Test - 8.2 Commencement of Test

8.2 Commencement of Test

 Not more than 5 min before the commencement of the test, the initial temperatures recorded by all thermocouples should be checked to ensure consistency and the datum values should be noted. Similar datum values should be obtained for deformation, and the initial condition of the test specimen should be noted.

 At the time of the test, the initial average internal temperature and unexposed surface temperature of the specimen should be 20 ± 10°C and should be within 5°C of the initial ambient temperature.


Copyright 2022 Clasifications Register Group Limited, International Maritime Organization, International Labour Organization or Maritime and Coastguard Agency. All rights reserved. Clasifications Register Group Limited, its affiliates and subsidiaries and their respective officers, employees or agents are, individually and collectively, referred to in this clause as 'Clasifications Register'. Clasifications Register assumes no responsibility and shall not be liable to any person for any loss, damage or expense caused by reliance on the information or advice in this document or howsoever provided, unless that person has signed a contract with the relevant Clasifications Register entity for the provision of this information or advice and in that case any responsibility or liability is exclusively on the terms and conditions set out in that contract.