Part A - General
12.1 General
12.1.1 Electrical installations footnoteshould be such that:
-
.1 all electrical auxiliary services necessary
for maintaining the craft in normal operation and habitable conditions
will be ensured without recourse to the emergency source of electrical
power;
-
.2 electrical services essential for safety will
be ensured under various emergency conditions, and
-
.3 the safety of passengers, crew and craft from
electrical hazards will be ensured.
The FMEA should include the electrical system, taking into account
the effects of electrical failure on the systems being supplied. In
cases where faults can occur without being detected during routine
checks on the installations, the analysis should take into account
the possibility of faults occurring simultaneously or consecutively.
12.1.2 The electrical system should be designed
and installed so that the probability of the craft being at risk of
failure of a service is extremely remote.
12.1.3 Where loss of particular essential service
would cause serious risk to the craft, the service should be fed by
at least two independent circuits fed in such a way that no single
failure in the electrical supply or distribution systems would effect
both supplies.
12.1.4 The securing arrangements for heavy items,
i.e. accumulator batteries, should, as far as practicable, prevent
excessive movement during the accelerations due to grounding or collision.
12.1.5 Precautions should be taken to minimize
risk of supplies to essential and emergency services being interrupted
by the inadvertent or accidental opening of switches or circuit breakers.
12.2 Main source of electrical
power
12.2.1 A main source of electrical power of sufficient
capacity to supply all those services mentioned in 12.1.1 should be provided. The main source of electrical power
should consist of at least two generating sets.
12.2.2 The capacity of these generating sets should
be such that in the event of any one generating set being stopped
or failing it will still be possible to supply those services necessary
to provide the normal operational conditions of propulsion and safety.
Minimum comfortable conditions of habitability should also be ensured
which include at least adequate services for cooking, heating, domestic
refrigeration, mechanical ventilation, sanitary and fresh water.
12.2.3 The arrangements of the craft's main source
of electrical power should be such that the services referred to in 12.1.1.1 can be maintained regardless of the
speed and direction of the propulsion machinery or shafting.
12.2.4 In addition, the generating sets should
be such as to ensure that with any one generator or its primary source
of power out of operation, the remaining generating set should be
capable of providing the electrical services necessary to start the
main propulsion plant from dead craft condition. The emergency source
of electrical power may be used for the purpose of starting from a
dead craft condition if its capability either alone or combined with
that of any other source of electrical power is sufficient to provide
at the same time those services required to be provided by 12.7.3.1 to 12.7.3.3 or 12.7.4.1 to 12.7.4.4 or 12.8.2.1 to 12.8.2.4.1, as appropriate.
12.2.5 Where transformers constitute an essential
part of the electrical supply system required by this section, the
system should be so arranged as to ensure the same continuity of supply
as is stated in 12.2.
12.2.6 A main electric lighting system which should
provide illumination throughout those parts of the craft normally
accessible to and used by passengers and crew should be supplied from
the main source of electrical power.
12.2.7 The arrangement of the main electric lighting
system should be such that a fire or other casualty in spaces containing
the emergency source of electrical power, associated transforming
equipment, if any, the emergency switchboard and the emergency lighting
switchboard will not render inoperative the main electric lighting
system required by 12.2.6.
12.2.8 The main switchboard should be so placed
relative to one main generating station that, as far as practicable,
the integrity of the normal electrical supply may be affected only
by a fire or other casualty in one space. An environmental enclosure
for the main switchboard, such as may be provided by a machinery control
room situated within the main boundaries of the space, should not
be considered as separating the switchboards from the generators.
12.2.9 The main busbars should normally be subdivided
into at least two parts which should be connected by a circuit-breaker
or other approved means. So far as is practicable, the connection
of generating sets and any other duplicated equipment should be equally
divided between the parts. Equivalent arrangements may be permitted
to the satisfaction of the Administration.
12.3 Emergency source of electrical
power
12.3.1 A self-contained emergency source of electrical
power should be provided.
12.3.2 The emergency source of electrical power,
associated transforming equipment, if any, transitional source of
electrical power, emergency switchboard and emergency lighting switchboard
should be located above the waterline in the final condition of damage
as referred to in chapter 2, operable in
that condition and readily accessible.
12.3.3 The location of the emergency source of
electrical power and associated transforming equipment, if any, the
transitional source of emergency power, the emergency switchboard
and the emergency electrical lighting switchboards in relation to
the main source of electrical power, associated transforming equipment,
if any, and the main switchboard should be such as to ensure that
a fire or other casualty in spaces containing the main source of electrical
power, associated transforming equipment, if any, and the main switchboard
or in any machinery space will not interfere with the supply, control
and distribution of emergency electrical power. As far as practicable,
the space containing the emergency source of electrical power, associated
transforming equipment, if any, the transitional source of emergency
electrical power and the emergency switchboard should not be contiguous
to the boundaries of main machinery spaces or those spaces containing
the main source of electrical power, associated transforming equipment,
if any, or the main switchboard.
12.3.4 Provided that suitable measures are taken
for safeguarding independent emergency operation under all circumstances,
the emergency generator, if provided, may be used exceptionally, and
for short periods, to supply non-emergency circuits.
12.3.5 Distribution systems should be so arranged
that the feeders from the main and emergency sources are separated
both vertically and horizontally as widely as practicable.
12.3.6 The emergency source of electrical power
may be either a generator or an accumulator battery, which should
comply with the following:
-
.1 Where the emergency source of electrical power
is a generator, it should be:
-
.1.1 driven by a suitable prime mover with an
independent supply of fuel having a flashpoint which meets the requirements
of 7.1.2.2;
-
.1.2 started automatically upon failure of the
electrical supply from the main source of electrical power and should
be automatically connected to the emergency switchboard. Those services
referred to in 12.7.5 or 12.8.3 should then be transferred to the emergency
generating set. The automatic starting system and the characteristic
of the prime mover should be such as to permit the emergency generator
to carry its full rated load as quickly as is safe and practicable,
subject to a maximum of 45 s; and
-
.1.3 provided with a transitional source of emergency
electrical power according to 12.7.5 or 12.8.3.
-
.2 Where the emergency source of electrical power
is an accumulator battery, it should be capable of:
-
.2.1 carrying the emergency electrical load without
recharging while maintaining the voltage of the battery throughout
the discharge period within 12% above or below its nominal voltage;
-
.2.2 automatically connecting to the emergency
switchboard in the event of failure of the main source of electrical
power; and
-
.2.3 immediately supplying at least those services
specified in 12.7.5 or 12.8.3.
12.3.7 The emergency switchboard should be installed
as near as is practicable to the emergency source of electrical power.
12.3.8 Where the emergency source of electrical
power is a generator, the emergency switchboard should be located
in the same space unless the operation of the emergency switchboard
would thereby be impaired.
12.3.9 No accumulator battery fitted in accordance
with this section should be installed in the same space as the emergency
switchboard. An indicator should be mounted in a suitable space at
the craft's operating compartment to indicate when the batteries constituting
either the emergency source of electrical power or the transitional
source of emergency electrical power referred to in 12.3.6.1.3 are
being discharged.
12.3.10 The emergency switchboard should be supplied
during normal operation from the main switchboard by an interconnector
feeder which should be adequately protected at the main switchboard
against overload and short circuit and which should be disconnected
automatically at the emergency switchboard upon failure of the main
source of electrical power. Where the system is arranged for feedback
operation, the interconnector feeder should also be protected at the
emergency switchboard at least against short circuit. Failure of the
emergency switchboard, when being used in other than an emergency,
should not put at risk the operation of the craft.
12.3.11 In order to ensure ready availability
of the emergency source of electrical power, arrangements should be
made, where necessary, to disconnect automatically non-emergency circuits
from the emergency switchboard to ensure that power should be available
to the emergency circuits.
12.3.12 The emergency generator and its prime
mover and any emergency accumulator battery should be so designed
and arranged as to ensure that they will function at full rated power
when the craft is upright and when the craft has a list or trimming
accordance with 9.1.12 including any
damage cases considered in chapter 2, or
is in any combination of angles within those limits.
12.3.13 Where accumulator batteries are installed
to supply emergency services, provisions should be made to charge
them in situ from a reliable on-board supply. Charging facilities
should be designed to permit the supply of services, regardless of
whether battery is on charge or not. Means should be provided to minimize
the risk of overcharging or overheating the batteries. Means for efficient
air ventilation should be provided.
12.4 Starting arrangements for
emergency generating sets
12.4.1 Emergency generating sets should be capable
of being readily started in their cold condition at a temperature
of 0°C. If this is impracticable, or if lower temperatures are
likely to be encountered, provisions should be made for heating arrangements
to ensure ready starting of the generating sets.
12.4.2 Each emergency generating set should be
equipped with starting devices with a stored energy capability of
at least three consecutive starts. The source of stored energy should
be protected to preclude critical depletion by the automatic starting
system, unless a second independent means of starting is provided.
A second source of energy should be provided for an additional three
starts within 30 min, unless manual starting can be demonstrated to
be effective.
12.4.3 The stored energy should be maintained
at all times, as follows:
-
.1 electrical and hydraulic starting systems should
be maintained from the emergency switchboard;
-
.2 compressed air starting systems may be maintained
by the main or auxiliary compressed air receivers through a suitable
nonreturn valve or by an emergency air compressor which, if electrically
driven, is supplied from the emergency switchboard:
-
.3 all of these starting, charging and energy
storing devices should be located in the emergency generator space.
These devices should not be used for any purpose other than the operation
of the emergency generating set. This does not preclude the supply
to the air receiver of the emergency generating set from the main
or auxiliary compressed air system through the nonreturn valve fitted
in the emergency generator space.
12.5 Steering and stabilization
12.5.1 Where steering and/or stabilization of
a craft is essentially dependent on one device as with a single rudder
or pylon, which is itself dependent on the continuous availability
of electric power, it should be served by at least two independent
circuits one of which should be fed either from the emergency source
of electric power or from an independent power source located in such
a position as to be unaffected by fire or flooding affecting the main
source of power. Failure of either supply should not cause any risk
to the craft or passengers during switching to the alternative supply
and such switching arrangements should meet the requirements in 5.2.5. These circuits should be provided with
short circuit protection and an overload alarm.
12.5.2 Protection against excess current may be
provided, in which case it should be for not less than twice the full
load current of the motor or circuit so protected, and should be arranged
to accept the appropriate starting current with a reasonable margin.
Where three-phase supply is used, an alarm should be provided in a
readily observed position in the craft's operating compartment that
will indicate failure of any one of the phases.
12.5.3 Where such systems are not essentially
dependent on the continuous availability of electric power but at
least one alternative system, not dependent on the electric supply
is installed, then the electrically powered or controlled system may
be fed by a single circuit protected in accordance with 12.5.2.
12.5.4 The requirements of chapters
5 and 16 for power supply of the
directional control system and stabilization system of the craft should
be met.
12.6 Precautions against shock,
fire and other hazards of electrical origin
12.6.1.1 Exposed metal parts of electrical machines
or equipment which are not intended to be live but which are liable
under fault conditions to become live should be earthed unless the
machines or equipment are:
-
.1 supplied at a voltage not exceeding 55 V direct
current or 55 V root mean square between conductors; auto-transformers
should not be used for the purpose of achieving this voltage; or
-
.2 supplied at a voltage not exceeding 250 V by
safety isolating transformers supplying only one consuming device;
or
-
.3 constructed in accordance with the principle
of double insulation.
12.6.1.2 The Administration may require additional
precautions for portable electrical equipment for use in confined
or exceptionally damp spaces where particular risks due to conductivity
may exist.
12.6.1.3 All electrical apparatus should be so
constructed and so installed as not to cause injury when handled or
touched in the normal manner.
12.6.2 Main and emergency switchboards should
be so arranged as to give easy access, as may be needed, to apparatus
and equipment, without danger to personnel. The sides and the rear
and, where necessary, the front of switchboards should be suitably
guarded. Exposed live parts having voltages to earth exceeding a voltage
to be specified by the Administration should not be installed on the
front of such switchboards. Where necessary, nonconducting mats or
gratings should be provided at the front and rear of the switchboard.
12.6.3 When a distribution system, whether primary
or secondary, for power, heating or lighting, with no connection to
earth is used, a device capable of continuously monitoring the insulation
level to earth and of giving an audible or visual indication of abnormally
low insulation values should be provided. For limited secondary distribution
systems the Administration may accept a device for manual checking
of the insulation level.
12.6.5.1 Each separate circuit should be protected
against short circuit and against overload, except as permitted in 12.5, or where the Administration may exceptionally
otherwise permit.
12.6.5.2 The rating or appropriate setting of
the overload protective device for each-circuit should be permanently
indicated at the location of the protective device.
12.6.5.3 When the protective device is a fuse
it should be placed on the load side of the disconnect switch serving
the protected circuit.
12.6.6 Lighting fittings should be so arranged
as to prevent temperature rises which could damage the cables and
wiring, and to prevent surrounding material from becoming excessively
hot.
12.6.7 All lighting and power circuits terminating
in a bunker or cargo space should be provided with a multiple-pole
switch outside the space for disconnecting such circuits.
12.6.8.1 Accumulator batteries should be suitably
housed, and compartments used primarily for their accommodation should
be properly constructed and efficiently ventilated.
12.6.8.2 Electrical or other equipment which may
constitute a source of ignition of flammable vapours should not be
permitted in these compartments except as permitted in 12.6.9.
12.6.8.3 Accumulator batteries should not be located
in crew accommodation.
12.6.9 No electrical equipment should be installed
in any space where flammable mixtures are liable to collect including
those in compartments assigned principally to accumulator batteries,
in paint lockers, acetylene stores or similar spaces, unless the Administration
is satisfied that such equipment is:
-
.1 essential for operational purposes;
-
.2 of a type which will not ignite the mixture
concerned;
-
.3 appropriate to the space concerned; and
-
.4 appropriately certified for safe usage in the
dusts, vapours or gases likely to be encountered.
12.6.10 The following additional requirements
from .1 to .7 should be met, and requirements from .8 to .13 should
be met also for non-metallic craft:
-
.1 The electrical distribution voltages throughout
the craft may be either direct current or alternating current and
should not exceed:
-
.1.1 500 V for power, cooking, heating and other
permanently connected equipment; and
-
.1.2 250 V for lighting, internal communications
and receptacle outlets.
The Administration may accept
higher voltage for propulsion purposes.
-
.2 For electrical power distribution, two-wire,
three-wire or four-wire insulated systems should be used. Where applicable,
the requirements of 7.5.6.4 or 7.5.6.5 should
also be met.
-
.3 Effective means should be provided so that
voltage may be cut off from each and every circuit and sub-circuit
and from all apparatus as may be necessary to prevent danger.
-
.4 Electrical equipment should be so designed
that the possibility of accidentally touching live parts, rotating
or moving parts as well as heated surfaces which might cause burns
or initiate fire is minimized.
-
.5 Electrical equipment should be adequately secured.
The probability of fire or dangerous consequences arising from damage
to electrical equipment should be reduced to an acceptable minimum.
-
.6 The rating or appropriate setting of the overload
protective device for each circuit should be permanently indicated
at the location of the protection device.
-
.7 Where it is impracticable to provide electrical
protective devices for certain cables supplied from batteries, e.g.
within battery compartments and in engine starting circuits, unprotected
cable runs should be kept as short as possible and special precautions
should be taken to minimize risk of faults, e.g. use of single core
cables with additional sleeve over the insulation of each core, with
shrouded terminals.
-
.8 In order to minimize the risk of fire, structural
damage, electrical shock and radio interference due to lightning strike
or electrostatic discharge, all metal parts of the craft should be
bonded together, in so far as possible in consideration of galvanic
corrosion between dissimilar metals, to form a continuous electrical
system, suitable for the earth return of electrical equipment and
to connect the craft to the water when water-born. The bonding of
isolated components inside the structure is not generally necessary,
except in fuel tanks.
-
.9 Each pressure refuelling point should be provided
with a means of bonding the fuelling equipment to the craft.
-
.10 Metallic pipes capable of generating electrostatic
discharges, due to the flow of liquids and gases should be bonded
so as to be electrically continuous throughout their length and should
be adequately earthed.
-
.11 Primary conductors provided for lightning
discharge currents should have a minimum cross section of 50 mm2 in
copper or equivalent surge carrying capacity in aluminium.
-
.12 Secondary conductors provided for the equalization
of static discharges, bonding of equipment, etc., but not for carrying
lightning discharges should have a minimum cross section of 5 mm2 copper
or equivalent surge current carrying capacity in aluminium.
-
.13 The electrical resistance between bonded objects
and the basic structure should not exceed 0.05 Ohms except where it
can be demonstrated that a higher resistance will not cause a hazard.
The bonding path should have sufficient cross-sectional area to carry
the maximum current likely to be imposed on it without excessive voltage
drop.
12.6.4 Cables and wiring
12.6.4.1 Except as permitted by the Administration
in exceptional circumstances, all metal sheaths and armour of cables
should be electrically continuous and should be earthed.
12.6.4.2 All electric cables and wiring external
to equipment should be at least of a flame-retardant type and should
be so installed as not to impair their original flame-retarding properties.
Where necessary for particular applications, the Administration may
permit the use of special types of cables such as radio frequency
cables, which do not comply with the foregoing.
12.6.4.3 Cables and wiring serving essential or
emergency power, lighting, internal communications or signals should
so far as practicable be routed clear of machinery spaces and their
casings and other high fire risk areas. Where practicable all such
cables should be run in such a manner as to preclude their being rendered
unserviceable by heating of the bulkheads that may be caused by a
fire in an adjacent space.
12.6.4.4 Where cables which are installed in hazardous
areas introduce the risk of fire or explosion in the event of an electrical
fault in such areas, special precautions against such risks should
be taken to the satisfaction of the Administration.
12.6.4.5 Cables and wiring should be installed
and supported in such manner as to avoid chafing or other damage.
12.6.4.6 Terminations and joints in all conductors
should be so made as to retain the original electrical, mechanical,
flame-retarding and, where necessary, fire-resisting properties of
the cable.
|