9.7 Testing of other units and alarms

  9.7.1 A method should be devised to test the correct functioning of all units and alarms and it may be necessary to simulate certain conditions to carry out an effective testing programme.

  9.7.2 Such a programme should include checking:

  • .1 all alarm and safety functions;

  • .2 the functioning of the flue gas isolating valves;

  • .3 the operation of all remotely or automatically controlled valves;

  • .4 the functioning of the water seal and nonreturn valve (with a backflow pressure test);

  • .5 the vibration level of the inert gas blowers;

  • .6 for leakages: in systems four years old or more, deck lines should be examined for gas leakage;

  • .7 the interlocking of the soot blowers;

  • .8 oxygen measuring equipment, both portable and fixed, for accuracy by means of both air and a suitable calibration gas.


Copyright 2020 Lloyd's Register Group Limited, International Maritime Organization, International Labour Organization or Maritime and Coastguard Agency. All rights reserved. Lloyd's Register Group Limited, its affiliates and subsidiaries and their respective officers, employees or agents are, individually and collectively, referred to in this clause as 'Lloyd's Register'. Lloyd's Register assumes no responsibility and shall not be liable to any person for any loss, damage or expense caused by reliance on the information or advice in this document or howsoever provided, unless that person has signed a contract with the relevant Lloyd's Register entity for the provision of this information or advice and in that case any responsibility or liability is exclusively on the terms and conditions set out in that contract.