3.1 Each system shall be fitted with a readily
accessible, manually operated isolating valve in the supply pressure
part of the system.
3.2 In multiple container installations, a non-return
valve should be placed in the supply line near to the stop valve on
each container. If a change-over device is used (automatic or manual),
it should be provided with non-return valves to isolate any depleted
container.
3.3 Where more than one container can supply a
system, the system should not be used with a container removed, unless
the unattached pipe is fitted with a suitable gas tight plug arrangement.
3.4 Containers not in use or not being fitted
into an installation should have the protecting cap in place over
the container valve.