The gas temperature inside the test compartment should be
continuously measured and recorded during the tests. The individual
thermocouples should be positioned as follows:
-
.1 one thermocouple 150 mm behind the foam generator;
and
-
.2 five thermocouples, respectively, at vertical
distances of 100 mm, 200 mm, 300 mm, 600 mm and 1,200 mm from the
ceiling. The thermocouple tree should be positioned 500 mm from the
front side wall (for informative reasons only).
All thermocouples should be of type K (chromel-alumel) and
made from 0.5 mm wire welded together.