3.1 The system may be automatically activated,
manually activated or automatically activated with manual release
capabilities. Automatic activation should be approved by the Administration,
taking into account the implications of such activations.
3.2 The system should be capable of fire suppression
and control and be tested to the satisfaction of the Administration
in accordance with the appendix to these Guidelines.
3.3 The capacity of the system water supply should
be sufficient for the total simultaneous coverage of the hydraulically
most demanding area defined by the minimum coverage area of table
3-1 and the vertically applicable area as defined in paragraph 3.5,
and the requirements of paragraph 3.4 below.
Type of system (Definition number)
|
Minimum coverage area
|
A. |
= |
Wet pipe, automatic sprinkler heads (2.9)
|
|
280 m2 or area of
operation as defined in the fire tests – whichever is larger
|
B. |
= |
Deluge system, automatic1 and manual
release (2.2)
|
|
280 m2 (as per paragraph
3.6) and the overlapping or adjacent section as defined by paragraph 3.4
2
|
C. |
= |
Deluge system, manual release (2.3)
|
|
2 sections each of min 20 m x w
2,3
|
D. |
= |
Other systems (2.4, 2.7)
|
|
Equivalent to the above systems and to
the satisfaction of the Administration
|
Notes:
|
|
1 |
= |
The automatic release should comply with the
requirements of paragraphs 4.1 to 4.5.
|
|
2 |
= |
The pump should be sized to cover the largest
sections for type B systems and the two largest horizontally
adjacent sections for type C systems.
|
|
3 |
= |
Width of cargo space (measured as distance between
tight steel divisions).
|
|
3.4 The section arrangement for a deluge system
with automatic and manual release (system B) should be such that a
fire in any location of the border zone between two or more sections
would be completely surrounded by activated spray heads, either by
activating more than one section or by overlapping sections (whereby
two or more sections cover the same area in the vicinity of the border
between sections). In case of overlapping sections, such overlap should
be a minimum of two times the required spray head spacing of the section
in question or five metres, whichever is larger. These overlapping
sections need not comply with the minimum width and length requirements
of paragraph 3.6 below.
3.5 Vertically the applicable area of all decks,
including hoistable decks or other intermediate decks, between reasonably
gas-tight steel decks (or equivalent materials), should be included
for simultaneous coverage (example: with one hoistable deck, both
the layer above and below this deck with a dimensioning area complying
with table 3-1 should be included in the water supply calculations).
Decks with ramps are accepted as reasonably gas-tight decks, assuming
that the ramps are always in their closed position at sea and the
ramps and the decks which these ramps are part of are reasonably gas-tight.
3.6 The system should be divided into sections,
each with its own section valve. The length of a section (along the
lanes) should not be less than 20 m and the width of the section should
not be less than 14 m. Further, the sections need not be longer or
wider than the distance between reasonably gas-tight steel bulkheads
(or equivalent materials). The maximum size of a section on any single
deck should be 48 m multiplied with width of cargo space (measured
as distance between tight steel divisions). Vertically one section
can cover up to three decks.
3.7 Each section should be capable of being isolated
by one section control valve. The section control valves should be
located outside the protected space, be readily accessible, independent
of the protected spaces and their locations should be clearly and
permanently indicated. It should be possible to manually open and
close the section control valves either directly on the valve or via
a control system routed outside the structural fire protection of
the protected spaces. Means should be provided to prevent the operation
of the section control valves by an unauthorized person.
3.8 The piping system should be sized in accordance
with a hydraulic calculation technique such as the Hazen-Williams
hydraulic calculation techniquefootnote and
the Darcy-Weisbach hydraulic calculation technique, to ensure availability
of flows and pressures required for correct performance of the system.
The design of the system should ensure that full system pressure is
available at the most remote nozzle in each section within 60 s of
activation.
3.9 The system supply equipment should be located
outside the protected spaces and all power supply components (including
cables) should be installed outside of the protected space. The electrical
components of the pressure source for the system should have a minimum
rating of IP 54.
3.10 The system should be provided with a redundant
means of pumping or otherwise supplying a water-based extinguishing
medium to the system. The capacity of the redundant means should be
sufficient to compensate for the loss of any single supply pump or
alternative source. Failure of any one component in the power and
control system should not result in a reduction of the automatic release
capability or reduction of required pump capacity by more than 50%
in case of automatic sprinklers and 100% in case of open head systems.
However, systems requiring an external power source need only be supplied
by the main power source. Hydraulic calculations should be conducted
to assure that sufficient flow and pressure are delivered to the hydraulically
most demanding section both in normal operation and in the event of
the failure of any one component.
3.11 The system should be fitted with a permanent
sea inlet and be capable of continuous operation during a fire using
seawater.
3.12 The system and its components should be designed
to withstand ambient temperatures, vibration, humidity, shock, impact,
clogging and corrosion normally encountered.
3.13 The system and its components should be designed
and installed based on international standards acceptable to the Organizationfootnote. The nozzles should be manufactured and
tested based on the relevant sections of appendix A to MSC/Circ.1165.
3.14 The nozzle location, type of nozzle and nozzle
characteristics should be within the limits tested to provide fire
suppression and control as referred to in paragraph 3.2. In addition,
nozzles should be located to protect spaces above and below intermediate
decks, hoistable decks and ramps. Nozzles below hoistable decks should
be capable of protecting all applicable heights.
3.15 System designs should be limited to the use
of the maximum and minimum temperature ratings of the thermally sensitive
fire detection devices tested to provide fire suppression and control
as referred to in paragraph 3.2.
3.16 Activation of the system should give a visual
and audible alarm at a continuously manned station. The visual and
audible alarms should be activated when for instance an automatic
sprinkler operates or when a section valve is opened. The alarm in
the continuously manned station should indicate the specific section
of the system that is activated. The system alarm requirements described
within this paragraph are in addition to, and not a substitute for,
the detection and fire alarm system required by SOLAS regulation II-2/20.4.
3.17 A means for testing the automatic operation
of the system and, in addition, assuring the required pressure and
flow should be provided.
3.18 If the system is pre-primed with water containing
a fire suppression enhancing additive and/or an antifreeze agent,
periodic inspection and testing, as specified by the manufacturer,
should be undertaken to assure that their effectiveness is being maintained.
Fire suppression enhancing additives should be approved for fire protection
service by an independent authority. The approval should consider
possible adverse health effects to exposed personnel, including inhalation
toxicity.
3.19 Wet pipe systems on board vessels that can
operate in areas where temperatures below 0oC can be expected,
shall be protected from freezing either by having temperature control
of the ro-ro space, heating coils on pipes, antifreeze agents or other
equivalent measures.
3.20 Operating instructions for the system should
be displayed at each operating position.
3.21 Installation plans and operating manuals
should be supplied to the ship and be readily available on board.
A list or plan should be displayed showing spaces covered and the
location of the zone in respect of each section. Instructions for
testing and maintenance should be available on board.
3.22 Spare parts and operating and maintenance
instructions should be provided as recommended by the manufacturer.
In the case of automatic sprinkler systems, the total number of spare
sprinkler heads for each type of sprinklers should be 6 for the first
300, 12 for the first 1,000.
3.23 Where automatically operated fire-fighting
systems are installed, a warning notice should be displayed outside
each entry point stating the type of medium used and the possibility
of automatic release.
3.24 All installation, operation and maintenance
instruction/plans for the system should be in the working language
of the ship. If the working language of the ship is not English, French,
nor Spanish, a translation into one of these languages should be included.