General – Steps in the bulkhead deck
For the treatment of steps in the bulkhead deck of passenger ships see explanatory notes
for regulation 13.
Regulation 17.1
This explanatory note only applies to passenger ships for which the building contract
is placed on or after 1 January 2020 and which are constructed before 1 January
2024.
1 Sliding watertight doors with a reduced pressure head that are located above the
bulkhead deck and which are immersed in the final or during any intermediate stage of
flooding should comply fully with the requirements of regulation 13. These types of
sliding watertight doors tested with reduced pressure head must not be immersed at any
stage of flooding by a head of water higher than the tested pressure head. See figure 1
below. These sliding watertight doors shall be kept closed during navigation in
compliance with the requirements of regulation 22 and this should be clearly indicated
in the damage control information required by regulation 19.
2 If watertight doors are located above the worst final and above the worst
intermediate waterline in damage cases contributing to the attained subdivision index
A, but within the area where the door becomes intermittently immersed (fully
or partly) at angles of heel in the required range of positive stability beyond the
equilibrium position, such doors are to be power-operated and remotely controlled
sliding semi-watertight doors complying with the requirements of regulation 13, except
that the scantlings and sealing requirements could be reduced to the maximum head of
water caused by the waterline being intermittently immersed (see figure 1 below). These
doors should be closed in case of damage and this should be clearly indicated in the
damage control information required by regulation 19.

3 The use of sliding watertight doors above the bulkhead deck affects the
escape provisions of regulation II-2/13. When such doors are used above the bulkhead
deck, there should be at least two means of escape from each main vertical zone or
similarly restricted space or group of spaces, at least one of which should be
independent of watertight doors and at least one of which should give access to a
stairway forming a vertical escape. Sliding watertight doors that will be used
frequently by passengers must not create a tripping hazard.
4 Doors fitted above the bulkhead deck which are required to meet both fire
protection and watertight requirements should comply with the fire requirements in
regulation II-2/9.4.1.1 and the watertight requirements in paragraphs 1 and 2 above.
Notwithstanding regulation II-2/9.4.1.1.3, watertight doors fitted above the bulkhead
deck should be insulated to the standard required by table 9.1 and regulation
II-2/9.2.2.1.1.1 or by table 9.3 and regulation II-2/9.2.2.1.1.2 as appropriate. The
door must be capable of operation using both the remote fire door control circuit and
the remote watertight door control circuit. If two doors are fitted, they must be
capable of independent operation. The operation of either door separately must not
preclude closing of the other door. Both doors must be capable of being operated from
either side of the bulkhead.
Regulation 17.2
This explanatory note only applies to passenger ships constructed on or after 1
January 2024.
1 Doors fitted in internal watertight subdivision boundaries located above the bulkhead
deck that are immersed at either the final equilibrium or worst intermediate stage of
flooding waterlines should be sliding watertight doors that comply fully with the
requirements of regulation 13. They should not be immersed at any stage of flooding by a
head of water higher than their design scantlings or their tested pressure head. These
sliding watertight doors should be kept closed during navigation in accordance with the
requirements of regulation 22 and this should be clearly indicated in the damage control
information required by regulation 19.
2 The use of sliding watertight doors above the bulkhead deck affects the escape
provisions of regulation II-2/13. When such doors are used above the bulkhead deck,
there should be at least two means of escape from each main vertical zone or similarly
restricted space or group of spaces, at least one of which should be independent of
watertight doors and at least one of which should give access to a stairway forming a
vertical escape. Sliding watertight doors that will be used frequently by passengers
must not create a tripping hazard.
3 Doors fitted above the bulkhead deck which are required to meet both fire protection
and watertight requirements should comply with the fire requirements in regulation
II-2/9.4.1.1 and the watertight requirements in paragraph 1 above. Notwithstanding
regulation II-2/9.4.1.1.3, watertight doors fitted above the bulkhead deck should be
insulated to the standard required by table 9.1 and regulation II-2/9.2.2.1.1.1 or by
table 9.3 and regulation II-2/9.2.2.1.1.2 as appropriate. The door must be capable of
operation using both the remote fire door control circuit and the remote watertight door
control circuit. If two doors are fitted, they must be capable of independent operation.
The operation of either door separately must not preclude closing of the other door.
Both doors must be capable of being operated from either side of the bulkhead.
Regulation 17.3
This explanatory note only applies to passenger ships constructed on or after 1 January
2024.
1 To be considered capable of preventing the passage of water when intermittently
immersed in the required range of positive stability, these doors should meet a
watertight standard for a minimum 1 m head of water. These doors may be hinged or
sliding, provided they comply with the design requirements applied from both sides of
the door. Consideration should be given to the opening direction for hinged doors, so
that they do not open against the intended direction of escape. These doors should be
closed in case of damage and this should be clearly indicated in the damage control
information required by regulation 19.
2 These doors are required to meet the fire protection requirements in chapter II-2.
Because these doors are not watertight doors that comply with the requirements in
regulation 13, the exclusions for watertight doors in chapter II-2 do not apply. In
addition to operation using the fire door control circuit, these doors should be
provided with a separate remote closure control circuit located on the navigation bridge
with the central operating console for the power-operated sliding watertight doors that
is required by regulation 13.7.1. A diagram showing the location of each door, with
visual indicators to show whether each door is open or closed, should also be at the
central operating console. A red light should indicate a door is fully open and a green
light should indicate a door is fully closed. When the door is closed remotely, the red
light should indicate the intermediate position by flashing. The indicating circuit
should be independent of the control circuit for each door. Indication should also be
provided to the onboard stability computer, if installed in accordance with regulation
8-1.3.1.
3 These doors should also be capable of being remotely closed with the ship listed 15
degrees either way.

|
Situation/waterlines
|
Type
|
Structural and functional
scantling
|
Use at sea
|
Watertight door according to regulations
17.2 and 13
|
Immersed at the final equilibrium stage of
flooding waterline or the worst intermediate stage of flooding
waterline
|
Sliding
|
According to
Revised MSC.1/Circ.1572
|
Closed during
navigation
|
Door according to regulation 17.3
|
Above the worst intermediate and final
equilibrium waterlines but within the area where the door becomes
intermittently immersed (fully or partially) at angles of heel in
the required range of positive stability beyond the equilibrium
position
|
Hinged or Sliding
|
Doors that are remotely
operated should be closed in case of damage
|
Regulation 17.5
For passenger ships for which the building contract is placed on or after 1 January
2020 and which are constructed before 1 January 2024, this is regulation
17.3.
This paragraph is intended to ensure that progressive flooding through air
pipes of volumes located above a horizontal division in the superstructure, which is
considered as a watertight boundary when applying regulation 7-2.6.1.1, will be taken
into consideration if a side or bottom damage would cause flooding via tanks or spaces
located below the waterline.