3.7.1 The drainage time should be determined,
after having determined the expansion ratio, according to paragraph 3.6.2(b.3).
3.7.2 The test should be carried out with sea
water at about 20°C. Simulated sea water with the characteristics
stated in 3.6.3 may be used.
3.7.3 Drainage time obtained with the foam generators
used on board should be consistent with the drainage time obtained
with the foam generators during the fire test.