4.1.1 The provisions of this chapter should be
applied in conjunction with applicable electrical requirements of part D of SOLAS chapter II-1.
4.1.2 Hazardous areas on open deck and other spaces
not defined in this chapter should be decided based on a recognized
standardfootnote. The electrical equipment
fitted within hazardous areas should be according to the same standard.
4.1.3 Electrical equipment and wiring should in
general not be installed in hazardous areas unless essential for operational
purposes based on a recognized standardfootnote.
4.1.4 Electrical equipment fitted in an ESD-protected
machinery space should fulfil the following:
-
.1 In addition to fire and hydrocarbon detectors
and fire and gas alarms, lighting and ventilation fans should be certified
safe for hazardous area zone 1.
-
.2 All electrical equipment in a machinery space
containing gas-fuelled engines, and not certified for zone 1 should
be automatically disconnected, if gas concentrations above 20% LEL
is detected on two detectors in the space containing gas-fuelled engines.
4.1.5 There should be an equalization connection
between the bunker supplier and the bunkering station on the ship
when a flammable gas/liquid is transferred.
4.1.6 Cable penetrations should satisfy the requirements
regulating the dispersion of gas.