9.2 Inert gas scrubber

  9.2.1 Inspection may be made through the manholes. Checks should be made for corrosion attacks, fouling and damage to:

  • .1 scrubber shell and bottom;

  • .2 cooling water pipes and spray nozzles (fouling);

  • .3 float switches and temperature sensors;

  • .4 other internals such as trays and demister filters.

  9.2.2 Checks should be made for damage to non-metallic parts such as:

  • .1 internal linings;

  • .2 demisters;

  • .3 packed beds.


Copyright 2020 Lloyd's Register Group Limited, International Maritime Organization, International Labour Organization or Maritime and Coastguard Agency. All rights reserved. Lloyd's Register Group Limited, its affiliates and subsidiaries and their respective officers, employees or agents are, individually and collectively, referred to in this clause as 'Lloyd's Register'. Lloyd's Register assumes no responsibility and shall not be liable to any person for any loss, damage or expense caused by reliance on the information or advice in this document or howsoever provided, unless that person has signed a contract with the relevant Lloyd's Register entity for the provision of this information or advice and in that case any responsibility or liability is exclusively on the terms and conditions set out in that contract.