At least once every 10 years, the following inspections
should be carried out for the specified equipment:
10.1 Fixed gas fire-extinguishing systems
-
.1 perform a hydrostatic test and internal examination
of 10 per cent of the system's extinguishing agent and pilot cylinders.
If one or more cylinders fail, a total of 50 per cent of the onboard
cylinders should be tested. If further cylinders fail, all cylinders
should be tested;
-
.2 flexible hoses should be replaced at the intervals
recommended by the manufacturer and not exceeding every 10 years;
and
-
.3 if permitted by the Administration, visual
inspection and NDT (non-destructive testing) of halon cylinders may
be performed in lieu of hydrostatic testing.
10.2 Water mist, water spray and sprinkler systems
Perform a hydrostatic test and internal examination for
gas and water pressure cylinders according to flag Administration
guidelines or, where these do not exist, EN 1968:2002 + A1.
10.3 Fixed dry chemical powder systems
Subject all powder containment vessels to hydrostatic or
non-destructive testing carried out by an accredited service agent.
10.4 Fixed aerosol extinguishing systems
Condensed or dispersed aerosol generators to be renewed
in accordance with manufacturer's recommendations.
10.5 Wheeled (mobile) fire extinguishers
All extinguishers together with propellant cartridges should
be hydrostatically tested by specially trained persons in accordance
with recognized standards or the manufacturer's instructions.