15A.2.3.1 A fire main, water service pipes and
fire hydrants should be fitted.
15A.2.3.2 The fire main and water service pipe
connections to the hydrants should be sized for the maximum discharge
rate of the pump(s) connected to the main.
15A.2.3.3 The fire main, water service pipes and
fire hydrants should be constructed such that they will:
-
.1 not be rendered ineffective by heat;
-
.2 not readily corrode; and
-
.3 be protected against freezing.
15A.2.3.4 When a fire main is supplied by 2 pumps,
1 in the machinery space and 1 elsewhere, provision should be made
for isolation of the fire main within the machinery space and for
the second pump to supply the fire main and hydrants external to the
machinery space. Isolation valve(s) should be manually operated
valves fitted outside the machinery space in a position easily accessible
in the event of a fire.
15A.2.3.5 The fire main should have no connections
other than those necessary for fire fighting or washing down.
15A.2.3.6 Fire hydrants should be located for
easy attachment of fire hoses, protected from damage and distributed
so that a single length of the fire hoses provided can reach any part
of the vessel.
15A.2.3.7 Fire hydrants should be fitted with
valves that allow a fire hose to be isolated and removed when a fire
pump is operating.