4.1 Class B fires must be extinguished within
30 s of the end of agent discharge. At the end of the soak period
there should be no re-ignition upon opening the enclosure.
4.2 The fuel spray should be shut off 15 s after
extinguishment. At the end of the soak time, the fuel spray should
be restarted for 15 s prior to reopening the door and there should
be no re-ignition.
4.3 At the end of the test fuel trays must contain
sufficient fuel to cover the bottom of the tray.
4.4 Wood crib weight loss must be no more than
60%.