Part 2 – Test and Performance Specifications for Approval
of Ballast Water Management Systems
The Administration decides the sequence of land-based and
shipboard testing.
2.1 Quality Assurance and Quality Control Procedures
2.1.1 The testing body performing the tests should
have implemented appropriate quality control measures in accordance
with recognized international standards acceptable to the Administration.
2.1.2 The approval testing process should contain
a rigorous quality control/quality assurance program, consisting of:
-
.1 Both a Quality Management Plan (QMP) and a
Quality Assurance Project Plan (QAPP). Guidance on preparation of
these plans, along with other guidance documents and other general
quality control information are available from appropriate international
organizationsfootnote.
-
.2 The QMP addresses the quality control management
structure and policies of the testing body (including subcontractors
and outside laboratories).
-
.3 The QAPP is a project specific technical document
reflecting the specifics of the BWMS to be tested, the test facility,
and other conditions affecting the actual design and implementation
of the required experiments.
2.2 Shipboard tests
2.2.1 A shipboard test cycle includes:
-
.1 the uptake of ballast water of the ship;
-
.2 the storage of ballast water on the ship;
-
.3 treatment of the ballast water in accordance
with paragraph 2.2.2.3 by the BWMS, except in control tanks; and
-
.4 the discharge of ballast water from the ship.
Success criteria for shipboard testing
2.2.2 In evaluating the performance of BWMS installation(s)
on a ship or ships, the following information and results should be
supplied to the satisfaction of the Administration:
-
.1 Test plan to be provided prior to testing.
-
.2 Documentation that the BWMS is of a capacity
within the range of the treatment rated capacity for which it is intended.
-
.3 The amount of ballast water tested in the test
cycle on board should be consistent with the normal ballast operations
of the ship and the BWMS should be operated at the treatment rated
capacity for which it is intended to be approved.
-
.4 Documentation of the results of three consecutive,
valid test cycles showing discharge of treated ballast water in compliance
with regulation D-2.
-
.5 Valid tests are indicated by uptake water,
for both the control tank and ballast water to be treated, with viable
organism concentration exceeding 10 times the maximum permitted values
in regulation D-2.1 and control tank viable organism concentration
exceeding the values of regulation D-2.1 on discharge.
-
.6 Sampling regime:
-
.7 The test cycles including invalid and unsuccessful
test cycles are to span a trial period of not less than six months.
-
.8 The applicant is requested to perform three
consecutive test cycles that comply with regulation D-2 and which
are valid in accordance with paragraph 2.2.2.5. Any invalid test cycle
does not affect the consecutive sequence.
-
.9 The source water for test cycles shall be characterized
by measurement of salinity, temperature, particulate organic carbon
and total suspended solids.
-
.10 For system operation throughout the trial
period, the following information should also be provided:
-
.1 documentation of all ballast water operations
including volumes and locations of uptake and discharge, and if heavy
weather was encountered and where;
-
.2 the possible reasons for the occurrence of
an unsuccessful test cycle, or a test cycle discharge failing the
D-2 standard should be investigated and reported to the Administration;
-
.3 documentation of scheduled maintenance performed
on the system;
-
.4 documentation of unscheduled maintenance and
repair performed on the system;
-
.5 documentation of engineering parameters monitored
as appropriate to the specific system; and
-
.6 documentation of functioning of the control
and monitoring equipment.
2.3 Land-based testing
2.3.1 The test set-up including the ballast water
treatment equipment should operate as described in the provided documentation
during at least 5 valid replicate test cycles. Each test cycle should
take place over a period of at least 5 days.
2.3.2 A land-based test cycle should include:
-
.1 the uptake of ballast water by pumping;
-
.2 the storage of ballast water for at least 5
days;
-
.3 treatment of ballast water within the BWMS,
except in control tanks; and
-
.4 the discharge of ballast water by pumping.
2.3.3 Testing should occur using different water
conditions sequentially as provided for in paragraphs 2.3.17 and 2.3.18.
2.3.4 The BWMS should be tested at its rated capacity
or as given in paragraphs 2.3.13 to 2.3.15 for each test cycle. The
equipment should function to specifications during this test.
2.3.5 The analysis of treated water discharge
from each test cycle should be used to determine that the average
of discharge samples does not exceed the concentrations of regulation
D-2 of the Convention.
2.3.6 The analysis of treated water discharge
from the relevant test cycle(s) should also be used to evaluate the
toxicity of the discharged water for BWMS that make use of Active
Substances and also for those BWMS that do not make use of Active
Substances or Preparations but which could reasonably be expected
to result in changes to the chemical composition of the treated water
such that adverse impacts to receiving waters might occur upon discharge.
Toxicity tests of the treated water discharge should be conducted
in accordance with paragraphs 5.2.3 to 5.2.7 of the Procedure for
approval of ballast water management systems that make use of Active
Substances, as revised (resolution MEPC.169(57)).
Land-based testing objectives, limitations and criteria for
evaluation
2.3.7 The land-based testing serves to determine
the biological efficacy and environmental acceptability of the BWMS
under consideration for Type Approval. The approval testing aims to
ensure replicability and comparability to other treatment equipment.
2.3.8 Any limitations imposed by the ballast water
management system on the testing procedure described here should be
duly noted and evaluated by the Administration.
Land-based set-up
2.3.9 The test set-up for approval tests should
be representative of the characteristics and arrangements of the types
of ships in which the equipment is intended to be installed. The test
set-up should therefore include at least the following:
-
.1 the complete BWMS to be tested;
-
.2 piping and pumping arrangements; and
-
.3 the storage tank that simulates a ballast tank,
constructed such that the water in the tank should be completely shielded
from light.
2.3.10 The control and treated simulated ballast
tanks should each include:
-
.1 a minimum capacity of 200 m3;
-
.2 normal internal structures, including lightening
and drainage holes;
-
.3 standard industry practices for design, construction
and surface coatings for ships; and
-
.4 the minimum modifications required for structural
integrity on land.
2.3.11 The test set-up should be pressure-washed
with tap water, dried and swept to remove loose debris, organisms
and other matter before starting testing procedures, and between test
cycles.
2.3.12 The test set-up will include facilities
to allow sampling as described in paragraphs 2.3.26 and 2.3.27 and
provisions to supply influents to the system, as specified in paragraph
2.3.19 and/or 2.3.20. The installation arrangements should conform
in each case with those specified and approved under the procedure
outlined in section 7 of the main body to these Guidelines.
Ballast water treatment equipment scaling
2.3.13 In-line treatment equipment may be downsized
for land-based testing, but only when the following criteria are taken
into account:
-
.1 equipment with a TRC equal to or smaller than
200 m3/h should not be downscaled;
-
.2 equipment with a TRC larger than 200 m3/h
but smaller than 1,000 m3/h may be downscaled to a maximum
of 1:5 scale, but may not be smaller than 200 m3/h; and
-
.3 equipment with a TRC equal to, or larger than,
1,000 m3/h may be downscaled to a maximum of 1:100 scale,
but may not be smaller than 200 m3/h.
2.3.14 The manufacturer of the equipment should
demonstrate by using mathematical modelling and/or calculations, that
any downscaling will not affect the ultimate functioning and effectiveness
on board a ship of the type and size for which the equipment will
be certified.
2.3.15 In-tank treatment equipment should be tested
on a scale that allows verification of full-scale effectiveness. The
suitability of the test set-up should be evaluated by the manufacturer
and approved by the Administration.
2.3.16 Larger scaling may be applied and lower
flow rates used than provided for in 2.3.13, if the manufacturer can
provide evidence from full-scale shipboard testing and in accordance
with 2.3.14 that scaling and flow rates will not adversely affect
the ability of the results to predict full-scale compliance with the
standard.
Land-based test design – inlet and outlet criteria
2.3.17 For any given set of test cycles (5 replicates
is considered a set) a salinity range should be chosen. Given the
salinity, the test water used in the test set up described above should
have dissolved and particulate content in one of the following combinations:
|
|
Salinity
|
| > 32
PSU
|
3 – 32
PSU
|
< 3
PSU
|
| Dissolved
Organic Carbon (DOC)
|
> 1
mg/l
|
> 5
mg/l
|
> 5
mg/l
|
| Particulate
Organic Carbon (POC)
|
> 1
mg/l
|
> 5
mg/l
|
> 5
mg/l
|
| Total Suspended
Solids (TSS)
|
> 1
mg/l
|
> 50
mg/l
|
> 50
mg/l
|
2.3.18 At least two sets of tests cycles should
be conducted, each with a different salinity range and associated
dissolved and particulate content as prescribed in paragraph 2.3.17.
Tests under adjacent salinity ranges in the above table should be
separated by at least 10 PSUfootnote.
2.3.19 Test organisms may be either naturally
occurring in the test water, or cultured species that may be added
to the test water. The organism concentration should comply with paragraph
2.3.20 below.
2.3.20 The influent water should include:
-
.1 test organisms of greater than or equal to
50 micrometres or more in minimum dimension should be present in a
total density of preferably 106 but not less than 105 individuals
per cubic metre, and should consist of at least 5 species from at
least 3 different phyla/divisions;
-
.2 test organisms greater than or equal to 10
micrometres and less than 50 micrometres in minimum dimension should
be present in a total density of preferably 104 but not
less than 103 individuals per millilitre, and should consist
of at least 5 species from at least 3 different phyla/divisions;
-
.3 heterotrophic bacteria should be present in
a density of at least 104 living bacteria per millilitre;
and
-
.4 the variety of organisms in the test water
should be documented according to the size classes mentioned above
regardless if natural organism assemblages or cultured organisms were
used to meet the density and organism variety requirements.
2.3.21 The following bacteria do not need to be
added to the influent water, but should be measured at the influent
and at the time of discharge:
2.3.22 If cultured test organisms are used, then
it should be ensured that local applicable quarantine regulations
are taken into account during culturing and discharge.
Land-based monitoring and sampling
2.3.23 Change of numbers of test organisms by
treatment and during storage in the simulated ballast tank should
be measured using methods described in Part 4 of the annex, paragraphs
4.5 to 4.7.
2.3.24 It should be verified that the treatment
equipment performs within its specified parameters, such as power
consumption and flow rate, during the test cycle.
2.3.25 Environmental parameters such as pH, temperature,
salinity, dissolved oxygen, TSS, DOC, POC and turbidity (NTU)footnote should be measured at the same time that
the samples described are taken.
2.3.26 Samples during the test should be taken
at the following times and locations: immediately before the treatment
equipment, immediately after the treatment equipment and upon discharge.
2.3.27 The control and treatment cycles may be
run simultaneously or sequentially. Control samples are to be taken
in the same manner as the equipment test as prescribed in paragraph
2.3.26 and upon influent and discharge. A series of examples are included
in figure 1.
2.3.28 Facilities or arrangements for sampling
should be provided to ensure representative samples of treated and
control water can be taken that introduce as little adverse effects
as possible on the organisms.
2.3.29 Samples described in paragraphs 2.3.26
and 2.3.27 should be collected in triplicate on each occasion.
2.3.30 Separate samples should be collected for:
-
.1 organisms of greater than or equal to 50 micrometres
or more in minimum dimension;
-
.2 organisms greater than or equal to 10 micrometres
and less than 50 micrometres in minimum dimension;
-
.3 for coliform, enterococcus group, Vibrio
cholerae and heterotrophic bacteria; and
-
.4 toxicity testing of treated water, from the
discharge, for BWMS that make use of Active Substances and also for
those BWMS that do not make use of Active Substances or Preparations
but which could reasonably be expected to result in changes to the
chemical composition of the treated water such that adverse impacts
to receiving waters might occur upon discharge.
2.3.31 For the comparison of organisms of greater
than or equal to 50 micrometres or more in minimum dimension against
the D-2 standard, at least 20 litres of influent water and l cubic
metre of treated water, in triplicate respectively, should be collected.
If samples are concentrated for enumeration, the samples should be
concentrated using a sieve no greater than 50 micrometres mesh in
the diagonal dimension.
2.3.32 For the evaluation of organisms greater
than or equal to 10 micrometres and less than 50 micrometres in minimum
dimension, at least 1 litre of influent water and at least 10 litres
of treated water should be collected. If samples are concentrated
for enumeration, the samples should be concentrated using a sieve
no greater than 10 micrometres mesh in the diagonal dimension.
2.3.33 For the evaluation of bacteria, at least
500 millilitres of influent and treated water should be collected
in sterile bottles.
2.3.34 The samples should be analysed as soon
as possible after sampling, and analysed live within 6 hours or treated
in such a way so as to ensure that proper analysis can be performed.
2.3.35 The efficacy of a proposed system should
be tested by means of standard scientific methodology in the form
of controlled experimentation, i.e. “experiments”. Specifically,
the effect of the BWMS on organism concentration in ballast water
should be tested by comparing treated ballast water, i.e. “treated
groups”, to untreated “control groups”, such that:
-
.1 one experiment should consist of a comparison
between control water and treated water. Multiple samples, but at
a minimum of three, of control and treated water within a single test
cycle should be taken to obtain a good statistical estimate of the
conditions within the water during that experiment. Multiple samples
taken during a single test cycle should not be treated as independent
measures in the statistical evaluation of treatment effect, to avoid
“pseudo-replication”.
2.3.36 If in any test cycle the average discharge
results from the control water is a concentration less than or equal
to 10 times the values in regulation D-2.1, the test cycle is invalid.
2.3.37 Statistical analysis of BWMS performance
should consist of t-tests, or similar statistical tests, comparing
control and treated water. The comparison between control and treated
water will provide a test of unexpected mortality in the control water,
indicating the effect of an uncontrolled source of mortality in the
testing arrangement.
2.4 Reporting of test results
2.4.1 After approval tests have been completed,
a report should be submitted to the Administration. This report should
include information regarding the test design, methods of analysis
and the results of these analyses.
2.4.2 The results of biological efficacy testing
of the BWMS should be accepted if during the land-based and shipboard
testing conducted as specified in sections 2.2 and 2.3 of this annex
it is shown that the system has met the standard in regulation D-2
in all test cycles as provided in paragraph 4.7 below.
|