Chapter 14A - Structural Fire Protection
Vessels of Less than 500GT
| Objective: The purpose of this Chapter is to ensure a consistent
level of structural fire protection. This Chapter is primarily
concerned with protecting high risk spaces such as the engine room
and galley. It also makes provision for restricting the quantity of
combustible materials and sets out the principles for detection of
fire and effective escape.
|
14A.1 General
(1) Terms used in this section shall have the same meaning as defined in SOLAS.
(2) Table 14A.1 is a guide to the major requirements of this Chapter. The Table is
intended as a quick reference to the requirements and is not to be used in isolation
when designing the fire safety arrangements.
Table 14A.1
| Passive fire protection (see
14A.2).
|
Category ‘A’ machinery spaces: ‘A-30’, (“B-15” for short range
yachts);
Galleys: “B-15” (for yachts not being Short Range
Yachts)’.
|
| Means of escape (see 14A.3):
|
|
| Category ‘A’ machinery spaces.
|
Two (2).
|
| Accommodation and other spaces
|
Two (2).
|
| Fixed fire detection system (see
14A.7).
|
Fitted in machinery spaces.
|
|
|
Fitted in service spaces, control stations and accommodation
spaces.
|
| Automatic sprinkler system or
equivalent
|
Fitted in yachts that do not meet restrictions on combustible
materials (See 14A.2(4)(f) and 14A.2(4)(h).
|
14A.2 Structure
(1) Purpose:
(2) Forms of construction - Fire divisions:
-
(a) Fire divisions required by 14A.2(3) shall be constructed in accordance
with the remaining paragraphs of this Section.
-
(b) Fire divisions using steel equivalent, or alternative forms of
construction may be accepted if it can be demonstrated that the material by
itself, or due to non-combustible insulation provided, has the fire
resistance properties equivalent to those divisions required by 14A.2(3)(a)
and 14A.2(3)(b).
-
(c) Insulation required by 14A.2(2)(b) shall be such that the temperature of
the structural core does not rise above the point at which the structure
would begin to lose its strength at anytime during the applicable exposure
to the standard fire test as referenced in the Fire Test Procedures Code.
For 'A' Class divisions, the applicable exposure is 60 minutes, and for 'B'
Class divisions, the applicable exposure is 30 minutes.
-
(d) For aluminium alloy structures, the insulation shall be such that the
temperature of the structural core does not rise more than 200°C above the
ambient temperature at any time during the applicable fire exposure.
-
(e) For composite structures, the insulation shall be such that the
temperature of the laminate does not rise more than the minimum temperature
of deflection under load of the resin at any time during the applicable fire
exposure. The temperature of deflection under load shall be determined in
accordance with a recognised international standard.
-
(f) Insulation need only be applied on the side that is exposed to the
greatest fire risk (for example inside the engine room), a division between
two such spaces shall however be insulated on both sides unless it is a
steel division.
-
(g) Special attention shall be given to the fixing of fire door frames in
bulkheads constructed of materials other than steel. Measures shall be taken
to ensure that the temperature of the fixings when exposed to fire does not
exceed the temperature at which the bulkhead itself loses strength.
(3) Structural Fire Protection:
-
(a) Machinery spaces of category ‘A’, shall be totally enclosed by ‘A-30’
Class boundaries (bulkheads, side shell and deck heads). For Short Range
Yachts, such machinery spaces shall be totally enclosed by “B-15” Class
boundaries (bulkheads, side shell and deck heads).
-
(b) Yachts which are not Short Range Yachts are to have galleys totally
enclosed by “B-15” Boundaries (bulkheads, side shell and deck heads).
Windows within the exterior hull or superstructure within this boundary are
not expected to meet “B-15” standards.
-
(c) Openings in 'A' and 'B' Class divisions shall be provided with
permanently attached means of closing that shall be at least as effective
for resisting fires as the divisions in which they are fitted. Generally,
windows shall not be fitted in machinery space boundaries.
-
(d) Where 'A' Class divisions are penetrated for the passage of electric
cables, pipes, trunks, ducts, etc., or for girders, beams or other
structural members, arrangements shall be made to ensure that the fire
resistance is not impaired.
-
(e) Where 'B' Class divisions are penetrated for the passage of electric
cables, pipes, trunks, ducts, etc., or for the fitting of ventilation
terminals, lighting fixtures and similar devices, arrangements shall be made
to ensure that the fire resistance is not impaired.
-
(f) Where 'A' Class divisions are required to be insulated, it shall be
ensured that the heat from a fire is not transmitted through the
intersections and terminal points of the divisions or penetrations to
uninsulated boundaries. Where the insulation installed does not achieve
this, arrangements shall be made to prevent this heat transmission by
insulating the horizontal and vertical boundaries or penetrations for a
distance of 450 millimetres.
(4) Materials:
-
(a) Except in refrigerated compartments of service spaces, all insulation
(e.g. thermal and acoustic) shall be of not readily-ignitable materials.
-
(b) Pipes penetrating 'A' or 'B' Class divisions shall be of approved
materials having regard to the temperature such divisions are required to
withstand.
-
(c) Pipes conveying oil or other combustible liquids through accommodation
and service spaces shall be of approved materials having regard to the fire
risk.
-
(d) Materials readily rendered ineffective by heat are not to be used for
overboard scuppers, sanitary discharges, and other outlets which are close
to the waterline and where the failure of the material in the event of fire
would give rise to danger of flooding. Due regard shall be paid to the Fire
Test Procedures Code.
-
(e) Vapour barriers and adhesives used in conjunction with insulation, as
well as insulation of pipe fittings for cold service system need not be
non-combustible, but they shall be kept to the minimum quantity practicable
and their exposed surfaces are to have low flame spread characteristics.
-
(f) Upholstery composites (fabric in association with any backing or padding
material) used throughout the vessel excluding open decks shall be approved
in accordance with the Fire Test Procedures Code, Annex 1, Part
8, or equivalent in accordance with 14A.2(4)(i). This does not
apply to spaces fitted with sprinklers or equivalent fixed fire
extinguishing systems.
-
(g) Organic foams used in upholstered furniture and mattresses shall be of
the combustion modified type.
-
(h) Suspended textile materials such as curtains or drapes shall be approved
in accordance with the Fire Test Procedures Code, Annex 1, Part
7, or equivalent in accordance with 14A.2(4)(i). This does not
apply to spaces fitted with sprinklers or equivalent fixed fire
extinguishing systems.
-
(i) Where upholstery composites and suspended textile materials do not meet
Fire Test Procedures Code standards in accordance with 14A.2(4)(f) and (h),
they may meet equivalent standards as follows:
-
(i) Materials shall be subject to fire protection treatment
processfootnote;
-
(ii) Vessel shall have installed a sprinkler or equivalent fixed fire
extinguishing system, that is compliant with the Fire Safety Systems Code in all aspects
except they may be exempt from Fire Safety Systems Code Chapter 8 section 2.2.2 requirement for 2
sources of power. Or for sprinkler systems equivalent to that
referred to in SOLAS II-2/12, Section 3.8 of the Annex to Resolution
A.800. The system shall be designed to enable simultaneous operation
of all sprinklers fitted in the most hydraulically demanding area.
The minimum area for simultaneous operation may be taken as the
largest enclosed accommodation space protected; or
-
(iii) An equivalent standard acceptable to the Administration.
(5) Surface of Insulation:
(6) Fuel Arrangements:
-
(a) Arrangements for the storage, distribution and utilisation of oil fuel
shall be such as to minimise the risk of fire or explosion.
-
(b) Oil fuel tanks situated within, or adjacent to, the boundaries of
Category 'A' machinery spaces are not to contain oil fuel having a
flashpoint of less than 60°C.
-
(c) Oil fuel, lubricating oil and other flammable oils are not to be carried
in fore-peak tanks.
-
(d) Every oil fuel pipe, which, if damaged, would allow oil to escape from a
storage, settling or daily service tank situated above the double bottom,
shall be fitted with a cock or valve directly on the tank capable of being
closed from a safe position outside the space concerned in the event of a
fire occurring in the space in which such tanks are situated.
-
(e) Means shall be provided to stop fuel transfer pumps, oil fired boilers
and separators from outside the machinery space.
-
(f) Fuel filter bowls shall be of metal construction.
14A.3 Means of Escape
(1) Purpose:
(2) Requirements:
-
(a) Stairways, ladders and corridors serving all spaces normally accessible
shall be arranged so as to provide ready means of escape to a deck from
which embarkation into survival craft may be effected.
-
(b) The arrangement of the vessel shall be such that all compartments are
provided with a satisfactory means of escape. In the case of the
accommodation, two means of escape from every restricted space or group of
spaces shall be provided. Concealed escapes and escape routes shall be
clearly marked to ensure ready exit.
-
(c) Category ‘A’ machinery spaces on motor vessels shall also be provided
with a minimum of two means of escape. Other machinery spaces shall also
have at least two means of escape as widely separated as possible, except
where the small size of the machinery space makes it impracticable.
-
(d) The normal means of access to the accommodation and service spaces below
the open deck shall be arranged so that it is possible to reach the open
deck without passing through a galley, engine room or other space with a
high fire risk, wherever practicable.
-
(e) Where accommodation arrangements are such that access to compartments is
through another compartment, the second escape route shall be as remote as
possible from the main escape route. This may be through hatches of adequate
size, leading to the open deck or separate space to the main escape route.
-
(f) In exceptional circumstances, a single means of escape may be accepted
for spaces, other than accommodation spaces, that are entered only
occasionally, if the escape route does not pass through a galley, machinery
space or watertight door.
-
(g) No escape route shall be obstructed by furniture or fittings.
Additionally, furniture along escape routes shall be secured in place to
prevent shifting if the yacht rolls or lists.
-
(h) All doors in escape routes shall be openable from either side. In the
direction of escape they are all to be openable without a key. All handles
on the inside of weathertight doors and hatches shall be non removable.
Where doors are lockable measures to ensure access from outside the space
shall be provided for rescue purposes.
(3) Lifts are not considered as forming a means of escape.
(4) Adequate deck area shall be provided at muster stations and
embarkation areas having due regard to the expected number of persons. Generally,
muster stations shall be provided close to the embarkation stations. Each muster
station shall have sufficient clear deck space to accommodate all persons assigned
to muster at that station, but at least 0.35m2 per person.
14A.4 Ventilation Systems
(1) Ventilation fans for machinery spaces and enclosed galleys shall be capable of
being stopped, and main inlets and outlets of ventilation systems closed, from
outside the spaces being served. This position shall not be readily cut off in the
event of a fire in the spaces served.
(2) Ventilation ducts for Category 'A' machinery spaces, galleys, spaces
containing vehicles or craft with fuel in their tanks, or lockers storing such
fuels, are generally not to pass through accommodation spaces, service spaces or
control stations. Where this is unavoidable, the trunking shall be constructed of
steel at least 3 millimetres thick or equivalent to the satisfaction of the
Administration. The ducting within the accommodation, service space or control
station shall be fitted with:
-
(a) fire insulation to A-30 (“B-15” on Short Range Yachts) standard to a
point at least 5 metres from the boundary of the machinery space or galley;
and
-
(b) automatic fire dampers located in the deck or bulkhead within
the accommodation, service space or control station where the trunking
passes from the machinery space or galley into the accommodation, service
space or control station.. These automatic fire dampers are also to be
manually closable from outside the galley or machinery space; and
-
(c) fixed means for extinguishing a fire within the galley exhaust duct.
(3) Ventilation ducts for accommodation spaces, service spaces or control stations
are not to pass through Category 'A' machinery spaces, galleys, spaces containing
vehicles or craft with fuel in their tanks, or lockers storing such fuels, unless
the ducts are constructed of steel and arranged to preserve the integrity of the
division.
(4) Store-rooms containing highly flammable products shall be provided with
ventilation arrangements that are separate from other ventilation systems.
Ventilation shall be arranged to prevent the build up of flammable vapours at high
and low levels. The inlets and outlets of ventilators shall be positioned so that
they do not draw from or vent into an area which would cause undue hazard, and shall
be fitted with spark arresters.
(5) Ventilation systems serving Category 'A' machinery spaces shall be independent of
systems serving other spaces.
(6) All enclosed spaces containing free standing fuel tanks shall be ventilated
independently of systems serving other spaces.
(7) Ventilation shall be provided to prevent the accumulation of dangerous
concentrations of flammable gas which may be emitted from batteries.
(8) Ducts provided for tumble driers shall be fitted with filters readily removable
for cleaning purposes and suitably located cleaning and inspection openings.
(9) All fire dampers shall be capable of manual operation. The dampers shall have a
direct mechanical means of release or, alternatively, be closed by electrical,
hydraulic, or pneumatic operation. All dampers shall be manually operable from both
sides of the division. Automatic fire dampers, including those capable of remote
operation, shall have a failsafe mechanism that shall close the damper in a fire
even upon loss of electrical power or hydraulic or pneumatic pressure loss. Remotely
operated fire dampers shall be capable of being reopened manually at the damper.
(10) Fire dampers shall be easily accessible. Where they are placed behind ceilings
or linings, these ceilings or linings shall be provided with an inspection hatch on
which the identification number of the fire damper is marked. The fire damper
identification number shall also be marked on any remote controls provided.
(11) Ventilation ducts shall be of non-combustible material except flexible bellows
of short length not exceeding 600 millimetres used for connecting fans to the
ducting in air-conditioning rooms. Short ducts, however, not generally exceeding 2m
in length and with a cross-section not exceeding 0.02m2 need not be
non-combustible, subject to the following conditions:
-
(a) material having low flame-spread characteristics and, in
each case, a calorific value not exceeding 45 MJ/m2 of their
surface area for the thickness used.
-
(b) they shall be used only at the end of the ventilation device; and
-
(c) they shall not be situated less than 600 millimetres, measured along the
duct, from an opening in an "A" or "B" class division including continuous
"B" class ceilings.
(12) Ventilation ducts shall be provided with hatches for inspection and cleaning.
The hatches shall be located near the fire dampers.
14A.5 Arrangements for ‘Recreational Fire Appliances’
(1) ‘Recreational Fire Appliances’ as defined in Chapter 2, shall meet the
requirements of Annex D
14A.6 Space Heaters
(1) Space heaters, if used, shall be fixed in position and so constructed as to
reduce fire risks to a minimum. The design and location of these units shall be such
that clothing, curtains or other similar materials cannot be scorched or set on fire
by heat from the unit.
14A.7 Fixed Fire Detection and Fire-Alarm Systems
(1) The purpose of this section is to detect a fire in the space of origin and to
provide for an alarm for safe escape and fire-fighting activity.
(2) A fixed fire detection and fire alarm system shall be fitted in all enclosed
spaces except those containing no significant fire risk (toilets, bathrooms, void
spaces, etc). Manually operated call points shall be placed effectively to ensure a
readily accessible means of notification. The fixed fire detection and fire-alarm
system shall be installed in accordance with the requirements of SOLAS II-2/7
and the Fire Safety Systems Code, Chapter
9, and shall be audible externally.
14A.8 Fixed Fire-Extinguishing Systems Not Required by this Section
(1) Where a fixed fire-extinguishing system not required by this Chapter, is
installed, the arrangement shall be to the satisfaction of the Administration.
14A.9 Emergency Training and Drills
(1) See Annex C for requirements
14A.10 Additional Equivalence Considerations
(1) None
14A.11 Alternative Design and Arrangements
(1) Vessels may follow Section 1.9 on Alternative Design and Arrangements for this
chapter as allowed by SOLAS II-2/17.
(2) The engineering analysis required by 1.9(3) shall be prepared and submitted to
the Administration, based on the guidelinesfootnote and shall include, as a minimum, the following
engineering analysis elements:
-
(a) determination of the ship type and space(s) concerned;
-
(b) identification of prescriptive requirement(s) with which the ship or the
space(s) will not comply;
-
(c) identification of the fire and explosion hazards of the ship or the
space(s) concerned, including;
-
(i) identification of the possible ignition sources;
-
(ii) identification of the fire growth potential of each space
concerned;
-
(iii) identification of the smoke and toxic effluent generation
potential for each space concerned;
-
(iv) identification of the potential for the spread of fire, smoke or
of toxic effluents from the space(s) concerned to other spaces;
-
(d) determination of the required fire safety performance criteria for the
ship or the space(s) concerned addressed by the prescriptive requirement(s)
in particular:
-
(i) performance criteria shall be based on the fire safety objectives
and on the functional requirements of this chapter;
-
(ii) performance criteria shall provide a degree of safety not less
than that achieved by using the prescriptive requirements; and
-
(iii) performance criteria shall be quantifiable and measurable;
-
(e) detailed description of the alternative design and arrangements,
including a list of the assumptions used in the design and any proposed
operational restrictions or conditions; and
-
(f) technical justification demonstrating that the alternative design and
arrangements meet the required fire safety performance criteria.
|