11.1 General
11.1.1 Electrical installations should be such that:
-
.1 all electrical auxiliary services necessary for maintaining the craft in normal
operation and habitable conditions will be ensured without recourse to the
emergency source of electrical power;
-
.2 electrical services essential for safety will be ensured under various
emergency conditions; and
-
.3 the safety of passengers, crew and craft from electrical hazards will be
ensured.
The System Safety Assessment (SSA) should include the electrical system, taking into
account the effects of electrical failure on the systems being supplied. In cases where
faults can occur without being detected during routine checks on the installations, the
analysis should take into account the possibility of faults occurring simultaneously or
consecutively.
11.1.2 The electrical system should be designed and installed so that the probability of
the craft being at risk of failure of a service is extremely remote.
11.1.3 Where loss of a particular essential service would cause serious risk to the
craft, the service should be fed by at least two independent circuits both fed in such a
way that no single failure in the electrical supply or distribution systems would affect
both supplies.
11.1.4 The securing arrangements for heavy items, i.e. accumulator batteries, should
prevent excessive movement during the accelerations according to 3.4.4.
11.1.5 Precautions should be taken to minimise risk of supplies to essential and
emergency services being interrupted by the inadvertent or accidental opening of
switches or circuit-breakers.
11.1.6 Electronic equipment essential for propulsion and attitude control purposes
should be approved and installed according to a recognized IEC Standard.
11.2 Main Source of Electrical Power
11.2.1 A main source of electrical power of sufficient capacity to supply all those
services mentioned in 11.1.1 should be provided. The main source of electrical power
should consist of at least two generating sets supplying two main switchboards.
11.2.2 The capacity of these generating sets should be such, that in the event of any
one generating set being stopped or failing in the ground effect mode, it will still be
possible to supply those services necessary to provide the normal operational conditions
of propulsion, attitude control in ground effect and safety. Minimum comfortable
conditions of habitability should also be ensured which include at least adequate
services for cooking, heating or cooling, domestic refrigeration, mechanical
ventilation, and sanitary and fresh water.
11.2.3 The arrangements of the craft's main source of electrical power should be such
that the services referred to in 11.1.1.1 can be maintained regardless of the speed of
the propulsion machinery.
11.2.4 One source of power independent from the main propulsion plant should be capable
of providing the electrical services necessary to start the main propulsion plant from
dead craft condition.
11.2.5 Where charging units or converters constitute an essential part of the electrical
supply system required by this section, the system should be so arranged as to ensure
the same continuity of supply as is stated in 11.2.2.
11.2.6 A main electric lighting system, which should provide illumination throughout
those parts of the craft normally accessible to and used by passengers and crew should
be supplied from the main source of electrical power.
11.2.7 The two main switchboards should be located in a dry space with a minimum risk of
fire.
11.2.8 The connection of generating sets and any other duplicated equipment should be
equally divided between the two switchboards. The generators should operate in single
operation. Equivalent arrangements may be permitted to the satisfaction of the
Administration.
11.2.9 Separation and duplication of electrical supply should be provided for duplicated
consumers of essential services. During normal operation the systems may be connected to
the same power-bus, but facilities for easy separation should be provided. Each system
should be able to supply all equipment necessary to maintain the control of propulsion,
steering, stabilization, navigation, lighting and ventilation, and allow starting of the
largest essential electric motor at any load. Automatic load-dependent disconnection of
non-essential consumers may be allowed.
11.3 Emergency Source of Electrical Power
11.3.1 A self-contained emergency source of electrical power should be provided.
11.3.2 The emergency source of electrical power, any associated transforming equipment,
transitional source of electrical power, emergency switchboard and emergency lighting
switchboard should be located above the waterline in the final condition of damage as
referred to in chapter 1, operable in that condition and readily accessible.
11.3.3 The location of the emergency source of electrical power and any associated
transforming equipment, the transitional source of emergency power, the emergency
switchboard and the emergency electrical lighting switchboards in relation to the main
source of electrical power, any associated transforming equipment and the main
switchboard should be such as to ensure that a fire or other casualty in spaces
containing the main source of electrical power, any associated transforming equipment,
will not interfere with the supply, control, and distribution of emergency electrical
power. As far as practicable, the space containing the emergency source of electrical
power, any associated transforming equipment, the transitional source of emergency
electrical power and the emergency switchboard should not be contiguous to the
boundaries of main machinery spaces or those spaces containing the main source of
electrical power, any associated transforming equipment, or the main switchboard.
11.3.4 Distribution systems should be so arranged that the feeders from the main and
emergency sources be separated both vertically and horizontally as widely as
practicable.
11.3.5 The emergency source of electrical power may be either a generator or an
accumulator battery, which should comply with the following:
-
.1 Where the emergency source of electrical power is a generator, it should be:
-
.1 driven by a suitable prime mover with an independent supply of fuel
having a flash point which meets the provisions of 6.1.1.2.2;
-
.2 started automatically upon failure of the electrical supply from the main
source of electrical power and should be automatically connected to the
emergency switchboard. Those services referred to in 11.4 should then be
transferred to the emergency generating set. The automatic starting system
and the characteristic of it be such as to permit the emergency generator to
carry its full rated load as quickly as is safe and practicable, subject to
a maximum of 15 s; and
-
.3 provided with a transitional source of emergency electrical power
according to 11.4; and
-
.2 Where the emergency source of electrical power is an accumulator battery, it
should be capable of:
-
.1 carrying the emergency electrical load without recharging while
maintaining the voltage of the battery throughout the discharge period
within 12% above or below its nominal voltage;
-
.2 automatically connecting to the emergency switchboard in the event of
failure of the main source of electrical power; and
-
.3 immediately supplying at least those services specified in 11.4.
11.3.6 The emergency switchboard should be installed as near as is practicable to the
emergency source of electrical power.
11.3.7 Where the emergency source of electrical power is a generator, the emergency
switchboard should be located in the same space unless the operation of the emergency
switchboard would thereby be impaired.
11.3.8 No accumulator battery fitted in accordance with this section should be installed
in the same space as the emergency switchboard. An indicator should be mounted in a
suitable space at the craft's operating compartment to indicate when the batteries
constituting either the emergency source of electrical power or the transitional source
of emergency electrical power referred to in 11.3.5.1.3 are being discharged.
11.3.9 The emergency switchboard should be supplied during normal operation from one
main switchboard by an interconnection feeder which should be adequately protected at
the main switchboard against overload and short circuit and which should be disconnected
automatically at the emergency switchboard upon failure of the main source of electrical
power. A manual switchover to the other main switchboard must be possible.
11.3.10 In order to ensure ready availability of the emergency source of electrical
power, only emergency circuits should be fed by the emergency switchboard.
11.3.11 The emergency generator and its prime mover and any emergency accumulator
battery should be so designed and arranged as to ensure that they will function at full
rated power when the craft is upright and when the craft has a list or trimming in
accordance with 8.1.1.12, including any damage cases considered in chapter 1, or is in
any combination of angles within those limits.
11.3.12 Where accumulator batteries are installed to supply emergency, back up or engine
start-up services, provisions should be made to charge them in situ from a reliable
onboard supply. Charging facilities should be designed to permit the supply of services,
regardless of whether battery is on charge or not. Means should be provided, by which
the batteries on board can be checked before each journey (e.g. minimum allowable
voltage at a laid down load). The risk of overcharging or overheating the batteries
should be minimised. Means for efficient air ventilation should be provided. A total
number of two battery systems and two chargers for all battery services except for radio
installations should be sufficient.
11.3.13 For unassisted craft, the emergency electrical power available should be
sufficient to supply all the services that are essential for safety in an emergency. The
emergency source of electrical power should be capable, having regard to starting
currents and the transitory nature of certain loads, of supplying simultaneously at
least the following services for the periods specified hereinafter, if they depend upon
an electrical source for their operation:
-
.1 for a period of 12 h, emergency lighting:
-
.1 at the stowage positions of life-saving appliances;
-
.2 at all escape routes, such as alleyways, stairways, exits from service
spaces, embarkation points, etc.;
-
.3 in the passenger compartments;
-
.4 in the machinery spaces and main emergency generating spaces including
their control positions;
-
.5 in control stations; and
-
.6 at the stowage positions for any fireman's outfits provided in accordance
with chapter 6;
-
.2 for a period of 12 h:
-
.1 the navigation lights, and other lights required by the International
Regulations for Preventing Collisions at Sea, 1972, in force;
.2 electrical internal communication equipment for announcements for
passengers and crew required during evacuation;
.3 fire detection and general alarm system and manual fire alarms; and
.4 remote control devices of fire-extinguishing systems, if electrical;
-
.3 for a period of 4 h on intermittent operation:
-
.1 the daylight signalling lamps, if they have no independent supply from
their own accumulator battery; and
-
.2 the craft's whistle, if electrically driven;
-
.4 for a period of 12 h:
-
.1 the navigational equipment as recommended in chapter 12;
-
.2 essential electrically powered instruments and controls for propulsion
machinery, if alternate sources of power are not available for such devices;
-
.3 the firefighting systems recommended in 6.1.6;
-
.4 the emergency bilge pump and all equipment essential for the operation of
electrically powered remote controlled bilge valves as recommended in
chapter 9; and
-
.5 craft radio facilities and other loads as set out in 13.12.2; and
-
.5 for a period of 12 hours, any essential power drives for directional control
devices including those required to direct thrust forward and astern.
11.3.14 For assisted craft, the emergency source of power should be capable of supplying
simultaneously the following services:
-
.1 for a period of 5 h emergency lighting:
-
.1 at the stowage positions of life-saving appliances;
.2 at all escape routes, such as alleyways, stairways, exits from
accommodation and service spaces, embarkation points, etc;
.3 in the public spaces;
.4 in the machinery spaces and main emergency generating spaces, including
their control positions;
.5 in control stations; and
.6 at the stowage positions for any firemen's outfits fitted in accordance
with chapter 6;
-
.2 for a period of 5 h;
-
.1 main navigation lights, except for "not under command" lights;
-
.2 electrical internal communication equipment for announcements for
passengers and crew required during evacuation;
-
.3 fire-detection and general alarm system and manual fire alarms; and
-
.4 remote control devices of fire-extinguishing systems, if electrical;
-
.3 for a period of 4 h of intermittent operation:
-
.1 the daylight signalling lamps, if they have no independent supply from
their own accumulator battery; and
-
.2 the craft's whistle, if electrically driven;
.4 for a period of 5 h:
-
.1 craft radio facilities and other loads as set out in chapter 13; and
-
.2 essential electrically powered instruments and controls for propulsion
machinery, if alternate sources of power are not available for such devices;
.5 for a period of 12 h, the "not under command" lights; and
.6 for a period of 10 min, power drives for directional control devices, including
those required to direct thrust forward and astern, unless there is a manual
alternative acceptable to the Administration as complying with 4.2.3.
11.3.15 Transitional source of emergency electrical power
The transitional source of emergency electrical power recommended in 11.3.5.1.3 may
consist of an accumulator battery suitably located for use in an emergency which should
operate without recharging while maintaining the voltage of the battery throughout the
discharge period within 12% above or below its nominal voltage and be of sufficient
capacity and so arranged as to supply automatically in the event of failure of either
the main and emergency source of electrical power at least the following services, if
they depend upon an electrical source for their operation for a period of 30 min, the
load specified in 11.3.14.1 to 11.3.14.3.
11.3.16 The provisions of 11.3.15 may be considered satisfied without the installation
of a transitional source of emergency electrical power if each of the services
recommended by that paragraph have independent supplies, for the period specified, from
accumulator batteries suitably located for use in an emergency. The supply of emergency
power to the instruments and controls of the propulsion and direction systems should be
uninterruptible.
11.3.17 Provisions should be made for the periodic testing of the complete emergency
system, including the emergency consumers recommended in 11.3.13 or 11.3.14 and 11.3.15,
and should include the testing of automatic starting arrangements.
11.3.18 Distribution systems should be so arranged that fire in any main vertical zone
will not interfere with services essential for safety in any other such zone. This
provision will be met if main and emergency feeders passing through any such zone are
separated both vertically and horizontally as widely as is practicable.
11.4 Starting Arrangements for Generating Sets
11.4.1 The generating sets should be capable of being readily started in
their cold condition at a temperature of 0°C. If this is impracticable, or if lower
temperatures are likely to be encountered, provisions should be made for heating
arrangements to ensure ready starting of the generating sets.
11.4.2 The main generating set (emergency generator set) should be equipped with
starting devices with a stored energy capability of at least six (three) consecutive
starts. The source of stored energy should be protected to preclude critical depletion
by the automatic starting system. A second source of energy should also be provided for
an additional six (three) starts.
11.4.3 The stored energy of the emergency generating set should be maintained at all
times, as follows:
-
.1 electrical and hydraulic starting systems should be maintained from the
emergency switchboard;
-
.2 compressed air starting systems may be maintained by the main or auxiliary
compressed air receivers through a suitable non-return valve or by an emergency
air compressor which, if electrically driven, is supplied from the emergency
switchboard; and
-
.3 all of these starting, charging and energy storing devices should be located in
the emergency generator space. These devices should not be used for any purpose
other than the operation of the emergency generating set. This does not preclude
the supply to the air receiver of the emergency generating set from the main or
auxiliary compressed air system through the non-return valve fitted in the
emergency generator space.
11.5 Steering and Attitude Control
11.5.1 Where steering and/or attitude control of a craft is essentially dependent on the
continuous availability of electric power, it should be served by at least three
independent circuits, two of which should be fed from the main switchboards and one from
the emergency source of electric power including the transitional source, both located
in such a position as to be unaffected by fire or flooding affecting the main source of
power. Failure of either supply should not cause any risk to the craft or passengers
during switching to the alternative supply and such switching arrangements should meet
the provisions in 4.2.6. These circuits should be provided with short circuit protection
and an overload alarm.
11.5.2 Protection against excess current may be provided, in which case it should be for
not less than twice the full load current of the motor or circuit so protected, and
should be arranged to accept the appropriate starting current with a reasonable margin.
Where three-phase supply is used, an alarm should be provided in a readily observed
position in the craft's operating compartment that will indicate failure of any one of
the phases.
11.5.3 Where such systems are not essentially dependent on the continuous availability
of electric power but at least one alternative system, not dependent on the electric
supply, is installed, then the electrically powered or controlled system may be fed by a
single circuit protected in accordance with 11.5.2.
11.5.4 The provisions of chapters 4 and 15 for power supply of the directional control
systems and stabilization systems of the craft should be met.
11.6 Precautions Against Shock, Fire and Other Hazards of Electrical Origin
11.6.1 Exposed metal parts of electrical machines or equipment which are not intended to
be live but which are liable under fault conditions to become live should be earthed
unless the machines or equipment are:
-
.1 supplied at a voltage not exceeding 55 V direct current or 55 V,
root-mean-square between conductors; auto-transformers should not be used for the
purpose of achieving this voltage; or
-
.2 supplied at a voltage not exceeding 250 V by safety isolating transformers
supplying only one consuming device; or
-
.3 constructed in accordance with the principle of double insulation.
11.6.2 All electrical apparatus should be so constructed and so installed as not to
cause injury when handled or touched in the normal manner.
11.6.3 Main and emergency switchboards should be so arranged as to give easy access, as
may be needed, to apparatus and equipment, without danger to personnel. The sides and
the rear and, where necessary, the front of switchboards should be suitably guarded.
Exposed live parts having voltages to earth exceeding a voltage to be specified by the
Administration should not be installed on the front of such switchboards. Where
necessary, non-conducting mats or gratings should be provided at the front and rear of
the switchboard.
11.6.4 When a distribution system, whether primary or secondary, for power, heating or
lighting, with no connection to earth is used, a device capable of continuously
monitoring the insulation level to earth and of giving an audible and visual indication
of abnormally low insulation values should be provided. For limited secondary
distribution systems the Administration may accept a device for manual checking of the
insulation level.
11.6.5 Cables and wiring
11.6.5.1 Power cables and control or communication cables as well as cables of each main
supply and emergency supply should be installed on separated cable runs. Power and
control cables for emergency consumers should be fire-resistant when they pass through
fire risk areas. Where, for safety reasons, a system has duplicated supply and/or
control cables, the cable routes should be placed as far apart as possible. All metal
sheaths and armour of cables should be electrically continuous and should be earthed.
11.6.5.2 All electric cables and wiring external to equipment should be at least of a
halogen-free flame-retardant type and should be so installed as not to impair their
original flame-retarding properties. Where necessary for particular applications, the
Administration may permit the use of special types of cables such as radio frequency
cables, which do not comply with the foregoing.
11.6.5.3 Cables and wiring serving essential or emergency power, lighting, internal
communications or signals should, so far as practicable, be routed clear of machinery
spaces and their casing and other high fire risk areas. Where practicable, all such
cables should be run in such a manner as to preclude their being rendered unserviceable
by heating of the bulkheads that may be caused by a fire in an adjacent space.
11.6.5.4 Where cables which are installed in hazardous areas introduce the risk of fire
or explosion in the event of an electrical fault in such areas, special precautions
against such risks should be taken to the satisfaction of the Administration.
11.6.5.5 Cables and wiring should be installed and supported in such manner as to avoid
chafing or other damage.
11.6.5.6 Terminations and joints in all conductors should be so made as to retain the
original electrical, mechanical, flame-retarding and, where necessary, fire-resisting
properties of the cable.
11.6.6.1 Each separate circuit should be protected against short circuit and against
overload, except as permitted in section 11.5 or where the Administration may
exceptionally otherwise permit. For supplies with 400 cycles the impedance of the
circuits should be observed.
11.6.6.2 The rating or appropriate setting of the overload protective device for each
circuit should be permanently indicated at the location of the protective device.
11.6.6.3 When the protective device is a fuse it should be placed on the load side of
the disconnect switch serving the protected circuit.
11.6.7 Lighting fittings should be so arranged as to prevent temperature rises which
could damage the cables and wiring, and to prevent surrounding material from becoming
excessively hot.
11.6.8 All lighting and power circuits terminating in a bunker or cargo space should be
provided with a multiple-pole switch outside the space for disconnecting such circuits.
11.6.9.1 Accumulator batteries should be suitably housed, and compartments used
primarily for their accommodation should be properly constructed and efficiently
ventilated.
11.6.9.2 Electrical or other equipment, which may constitute a source of ignition of
flammable vapours, should not be permitted in compartments likely to contain such
vapours.
11.6.10 The following additional provisions from .1 to .7 should be met, and provisions
from .8 to .13 should be met also for non-metallic craft:
-
.1 The electrical distribution voltages throughout the craft may be either direct
current or alternating current and should not exceed:
-
.1 500 V for power, cooking, heating, and other permanently connected
equipment; and
-
.2 250 V for lighting, internal communications and receptacle outlets.
-
.2 For electrical power distribution earthed systems with non hull-return are
acceptable. Where applicable, the provisions of 6.1.4.2.6.3 or 6.1.4.2.6.4 should
also be met.
-
.3 Effective means should be provided so that voltage may be cut off from each and
every circuit and sub-circuit and from all apparatus as may be necessary to
prevent danger.
-
.4 Electrical equipment should be so designed that the possibility of accidentally
touching live parts, rotating or moving parts as well as heated surfaces which
might cause burns or initiate fire is minimised.
-
.5 Electrical equipment should be adequately secured. The probability of fire or
dangerous consequences arising from damage to electrical equipment should be
reduced to an acceptable minimum.
-
.6 The rating or appropriate setting of the overload protective device for each
circuit should be permanently indicated at the location of the protection device.
-
.7 Where it is impracticable to provide electrical protective devices for certain
cables supplied from batteries, e.g. within battery compartments and in engine
starting circuits, unprotected cable runs should be kept as short as possible and
special precautions should be taken to minimise risk of faults, e.g. use of single
core cables with additional sleeve over the insulation of each core, with shrouded
terminals.
-
.8 In order to minimise the risk of fire, structural damage, electrical shock and
radio interference due to lightning strike or electrostatic discharge, all metal
parts of the craft should be bonded together, in so far as possible in
consideration of galvanic corrosion between dissimilar metals, to form a
continuous electrical system, suitable for the earth return of electrical
equipment and to connect the craft to the water when water-borne. The bonding of
isolated components inside the structure is not generally necessary, except in
fuel tanks.
-
.9 Each refuelling point should be provided with a means of bonding the fuelling
equipment to the craft.
-
.10 Metallic pipes capable of generating electrostatic discharges, due to the flow
of liquids and gases, should be bonded so as to be electrically continuous
throughout their length and should be adequately earthed.
-
.11 Primary conductors provided for lightning discharge currents
should have a minimum cross section of 50 mm2 in copper or equivalent
surge carrying capacity in aluminium.
-
.12 Secondary conductors provided for the equalisation of static
discharges, bonding or equipment, etc., but not for carrying lightning discharges
should have a minimum cross-section of 5 mm2 copper or equivalent surge
current carrying capacity in aluminium.
-
.13 The electrical resistance between bonded objects and the basic structure
should not exceed 0.05 Ohm, except where it can be demonstrated that a higher
resistance will not cause a hazard. The bonding path should have sufficient
cross-sectional area to carry the maximum current likely to be imposed on it
without excessive voltage drop.