Interpretation
Procedure for Coating System Approval
1 A Type Approval Certificate showing compliance
with the PSPC 5 should be issued if the results of either method A+D,
or B+D, or C+D are found satisfactory by the Administration.
2 The Type Approval Certificate should indicate
the product and the shop primer tested. The certificate should also
indicate other type approved shop primers with which the product may
be used which have undergone the crossover test in a laboratory meeting
the requirements in Method A, 1.1 of this UI.
3 The documents required to be submitted are identified
in the following sections, in addition for all type approvals the
following documentation is required: Technical Data Sheet showing
all the information required by PSPC 3.4.2.2.
4 Winter type epoxy requires separate prequalification
tests, including a shop primer compatibility test according to PSPC
Annex 1. Winter and summer type coating are considered different unless
Infrared (IR) identification and Specific Gravity (SG) demonstrate
that they are the same.
Method A: Laboratory test
1 A coating pre-qualification test should be carried
out by a test laboratory recognized by the Administration and the
test laboratory should meet the requirements set out in IACS UR Z17.
2 Results from satisfactory pre-qualification
tests (PSPC Table 1: 1.3) of the coating system should be documented
and submitted to the Administration.
3 Type Approval tests should be carried out for
the epoxy-based system with the stated shop primer in accordance with
the PSPC Annex 1. If the tests are satisfactory, a Type Approval Certificate
should be issued to include both the epoxy and the shop primer. The
Type Approval Certificate will allow the use of the epoxy either with
the named shop primer or on bare prepared steel.
4 An epoxy-based system may be used with shop
primers other than the one with which it was originally tested provided
that the other shop primers are approved as part of a system (PSPC
Table 1: 2.3 and Table 1: 3.2) and have been tested according to PSPC
Annex 1, Appendix 1, 1.7, which is known as the "crossover test".
If the test or tests are satisfactory, a Type Approval Certificate
should be issued. In this instance, the Type Approval Certificate
should include the details of the epoxy and a list of all shop primers
with which it has been tested that have passed these requirements.
The Type Approval Certificate will allow the use of the epoxy with
all the named shop primers or on bare prepared steel.
5 Alternatively, the epoxy can be tested without
shop primer on bare prepared steel to the requirements of the PSPC,
Annex 1. If the test or tests are satisfactory, a Type Approval Certificate
should be issued. The Type Approval Certificate should just record
the epoxy. The certificate will allow the use of the epoxy on bare
prepared steel only. If, in addition, crossover tests are satisfactorily
carried out with shop primers which are approved as part of a system,
the Type Approval Certificate should include the details of shop primers
which have satisfactorily passed the crossover test. In this instance,
the Type Approval Certificate will allow the use of the epoxy-based
system with all the named shop primers or on bare prepared steel.
6 The Type Approval Certificate is invalid if
the formulation of either the epoxy or the shop primer is changed.
It is the responsibility of the coating manufacturer to inform the
Administration immediately of any changes to the formulation.
Method B: 5 years' field exposure
1 Coating manufacturer's records, which shall
at least include the information indicated in 2, should be examined
to confirm that the coating system had 5 years' field exposure and
that the current product is the same as that being assessed.
2 Manufacturer's records
- original application records;
- original coating specification;
- original technical data sheet;
- current formulation's unique identification (code or number);
- if the mixing ratio of base and curing agent has changed, a statement
from the coating manufacturer confirming that the composition mixed
product is the same as the original composition. This should be accompanied
by an explanation of the modifications made;
- current technical data sheet for the current production site;
- SG and IR identification of original product;
- SG and IR identification of the current product; and
- if original SG and IR cannot be provided, then a statement from
the coating manufacturer confirming the readings for the current product
are the same as those of the original.
3 Either class survey records from an Administration
or a joint (coating manufacturer and Administration) survey of all
ballast tanks of a selected vessel should be carried out for the purpose
of verification of compliance with the requirements of 1 and 7. The
reporting of the coating condition in both cases should be in accordance
with the IACS Recommendation 87, section 2.
4 The selected vessel should have ballast tanks
in regular use, of which:
- at least one tank is approximately 2,000 m3 or more
in capacity;
- at least one tank shall be adjacent to a heated tank; and
- at least one tank contains an underdeck exposed to the sun.
5 In the case that the selected vessel does not
meet the requirements in 4, then the limitations should be clearly
stated on the Type Approval Certificate. For example, the coating
cannot be used in tanks adjacent to heated tanks or underdeck or tanks
with a volume greater than the size surveyed.
6 In all cases of approval by Method B, the shop
primer should be removed prior to application of the approved epoxy-based
system coating, unless it can be confirmed that the shop primer applied
during construction is identical in formulation to that applied in
the selected vessel used as a basis for the approval.
7 All ballast tanks should be in "GOOD" condition
excluding mechanical damages, without touch up or repair in the prior
5 years.
8 "Good" is defined as: Condition with spot
rusting on less than 3% of the area under consideration without visible
failure of the coating. Rusting at edges or welds, must be on less
than 20% of edges or welds in the area under consideration.
9 Examples of how to report coating conditions
with respect to areas under consideration should be as those given
in IACS Recommendation 87.
10 If the applied NDFT is greater than required
by the PSPC, the applied NDFT will be the minimum to be applied during
construction. This should be reported prominently on the Type Approval
Certificate.
11 If the results of the inspection are satisfactory,
a Type Approval Certificate should be issued to include both the epoxy-based
system and the shop primer. The Type Approval Certificate shall allow
the use of the epoxy-based system either with the named shop primer
or on bare prepared steel. The Type Approval Certificate should reference
the inspection report which should also form part of the Coating Technical
File.
12 The Type Approval Certificate is invalid if
the formulation of either the epoxy-based system or the shop primer
is changed. It is the responsibility of the coating manufacturer to
inform the Administration immediately of any changes to the formulation.
Method C: Existing Marintek B1 approvals
1 Epoxy-based system coatings systems with existing
satisfactory Marintek test reports minimum level B1 including relevant
IR identification and SG, issued before 8 December 2006 can be accepted.
If original SG and IR documentation cannot be provided, then a statement
should be provided by the coating manufacturer, confirming that the
readings for the current product are the same as those of the original.
2 The Marintek test report with IR and SG information
should be reviewed and, if satisfactory, a Type Approval Certificate
should be issued. The certificate should record the report reference
and the shop primer used. The Type Approval Certificate should allow
the use of the epoxy-based system either with the named shop primer,
unless there is evidence to indicate that it is unsuitable, or on
bare prepared steel.
3 The epoxy-based system approved by this method
may be used with other shop primers if satisfactory crossover tests
are carried out with shop primers which are approved as part of a
system, see Method A, 4. In this instance, the Type Approval Certificate
should include the details of the epoxy-based system and a list of
all shop primers which have passed these requirements. The Type Approval
Certificate will allow the use of the epoxy-based system with all
the named shop primers or on bare prepared steel.
4 Such coatings should be applied in accordance
with PSPC Table 1 rather than the application conditions used during
the approval test which may differ from the PSPC, unless these are
more stringent than PSPC Annex 1, for example if the NDFT is higher
or high pressure water washing and or sweep blasting of the shop primer
is used. In such cases these limiting conditions should be added to
the Type Approval Certificate and should be followed during coating
application in the shipyard.
5 The Type Approval Certificate is invalid if
the formulation of either the epoxy-based system or the shop primer
is changed. It is the responsibility of the coating manufacturer to
inform the Administration immediately of any changes to the formulation.
Method D: Coating manufacturer
1 The coating/shop primer manufacturer should
meet the requirements set out in IACS UR Z17, paragraphs 4, 5, 6 and
7 (except for 4.6) and paragraphs 2 to 7 below, which should be verified
by the Administration.
2 Coating manufacturers
-
.1 Extent of engagement – Production of
coating systems in accordance with PSPC and this UI.
-
.2 These requirements apply to both the main coating
manufacturer and the shop primer manufacturer where both coatings
form part of the total system.
-
.3 The coating manufacturer should provide to
the Administration the following information:
- A detailed list of the production facilities.
- Names and location of raw material suppliers will be clearly stated.
- A detailed list of the test standards and equipment to be used,
(Scope of approval).
- Details of quality control procedures employed.
- Details of any sub-contracting agreements.
- List of quality manuals, test procedures and instructions, records,
etc.
- Copy of any relevant certificates with their issue number and/or
date, e.g., Quality Management System certification.
-
.4 Inspection and audit of the manufacturer's
facilities should be based on the requirements of the PSPC.
-
.5 With the exception of early "scale up" from
laboratory to full production, adjustment outside the limitations
listed in the QC instruction referred to below is not acceptable,
unless justified by trials during the coating system's development
programme, or subsequent testing. Any such adjustments must be agreed
by the formulating technical centre.
-
.6 If formulation adjustment is envisaged during
the production process, the maximum allowable limits should be approved
by the formulating technical centre and clearly stated in the QC working
procedures.
-
.7 The manufacturer's quality control system should
ensure that all current production is the same formulation as that
supplied for the Type Approval Certificate. Formulation change should
not be permissible without testing in accordance with the test procedures
in the PSPC and the issue of a Type Approval Certificate by the Administration.
-
.8 Batch records including all QC test results
such as viscosity, specific gravity and airless spray characteristics
should be accurately recorded. Details of any additions should also
be included.
-
.9 Whenever possible, raw material supply and
lot details for each coating batch should be traceable. Exceptions
may be where bulk supply such as solvents and pre-dissolved solid
epoxies are stored in tanks, in which case it may only be possible
to record the supplier's blend.
-
.10 Dates, batch numbers and quantities supplied
to each coating contract should be clearly recorded.
3 All raw material supply should be accompanied
by the supplier's "Certificate of Conformance". The certificate should
include all requirements listed in the coating manufacturer's QC system.
4 In the absence of a raw material supplier's
certificate of conformance, the coating manufacturer should verify
conformance to all requirements listed in the coating manufacturer's
QC system.
5 Drums should be clearly marked with the details
as described on the Type Approval Certificate.
6 Product Technical Data Sheets should comply
with all the PSPC requirements. The QC system will ensure that all
Product Technical Data Sheets are current.
7 QC procedures of the originating technical centre
should verify that all production units comply with the above stipulations
and that all raw material supply is approved by the technical centre.
8 In the case that a coating manufacturer wishes
to have products which are manufactured in different locations under
the same name, then IR identification and SG should be used to demonstrate
that they are the same coating, or individual approval tests will
be required for the paint manufactured in each location.
9 The Type Approval Certificate is invalid if
the formulation of either the epoxy-based system or the shop primer
is changed. It is the responsibility of the coating manufacturer to
inform class immediately of any changes to the formulation. Failure
to inform class of an alteration to the formulation should lead to
cancellation of the certificates for that manufacturer's products
1.5
NDFT (nominal total dry
film thickness)5
|